SCE Property 1

Tribhuwan Choubey – SCE/TDBU/ECQ

Pilot Relay Schemes

Communication Aided Protection Schemes

Page 2: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Introduction

• Relays at the Transmission terminals talk with each other using telecommunication media.

• Pilot relays do not pick up for faults outside their defined zone of protection.

• Pilot relays pick up instantaneously for faults within their defined zone of protection.

• For increased reliability some type of backup protection is also provided

SCE Property 2

Page 3: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

2- Zone Distance Relay

SCE Property 3

Page 4: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Pilot relay telecommunication

SCE Property 4

Page 5: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Relay communication

SCE Property 5

• Leased Telephone Line ( 56 or 64kbps over copper)• Power Line Carrier (PLC – 64kbps) – Twisted copper

wire for 2/ 3 terminals• Microwave or UHF radio (Multiplexed – 1.544 mbits/

sec DS1 signal – 24 channels)• Dedicated Optical Fiber (Single Mode – 10 miles or

Multi mode – 60 miles)• SONET (Multiplexed Symmetrical Optical Network -

Synchronous)• T1 Multiplexing – 1.544 mbits/ sec (Asynchronous –

voice and data communication)

Page 6: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Microwave Tower

SCE Property 6

Page 7: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Microwave Tower

SCE Property 7

Page 8: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Microwave Telecom Equipment• Microwave Radio frequency spectrum: 1850-19909,

2130-2200, 6525-6875 and 12200-12700 MHz• Operation: Two frequency duplex operation• Telecom Equipment: Transmitters, Receivers, Order

wires, Filters, Power Supplies, switching devices• Microwave RF Apparatus specifications: T-8505• Carrier Frequency and Bandwidth : FCC Rules 94.65

and 94.71• Frequency Stability: FCC rules 94.67• Baseband I/O level: < -35dBm/ -15dBm per channel• Power Supply: 48V DC

SCE Property 8

Page 9: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Microwave Telecom Equipment• Each terminal is equipped with hot standby transmitter.• Switching circuitry is bilateral in between transmitters• The input to the receivers from the antenna is connected

through an RF Hybrid• Switching time for manual operation < 20 msec.• Switching time for automatic operation < 25 msec.• Operation of either or both of these switches cause a

“Guard” or “Off Normal” lamps • Hot standby operation of Transmitters and Receivers

allows uninterrupted operation on failure of one equipment

SCE Property 9

Page 10: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

SONETcommunication

SCE Property 10

SONET - Synchronous Optical Network

Page 11: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

SONET Data Service

SCE Property 11

Page 12: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Fiber optic communication

SCE Property 12

Page 13: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Fiber optic Data Losses

SCE Property 13

Page 14: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

T1 Extended Super Frame

SCE Property 14

Page 15: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Categories of Pilot RelayingFollowing categories of protection schemes are typically applied in pilot relaying.• Phase comparison• Directional comparison blocking• Remote tripping• Transfer trip • Line differential

SCE Property 15

Page 16: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Pilot Relaying Philosophy500 KV Pilot Relaying Schemes:• Redundant Pilot relaying systems• Redundant Transfer Trip relaying systems• One set of electromechanical relays as

backup protection system.• Mix of communication system like Power

Line Carrier (PLC) and Microwave are used for communication redundancy

SCE Property 16

Page 17: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Pilot Relaying Philosophy220 KV Pilot Relaying Schemes:• One Pilot relaying systems• One set of electromechanical relays or

another Pilot relaying scheme with microwave as communication channel are used as backup protection system

• Mix of communication system like Power Line Carrier (PLC) or Microwave are used for communication redundancy

SCE Property 17

Page 18: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Pilot Relaying Philosophy• Principle of Differential Relaying is applied for

instantaneous tripping for in zone faults• Four wires, normally termed as Pilot Wires, run

in between substations to compare current between terminals (Typical F/C 15ms – 25ms)

• HCB Relays from Westinghouse (ABB) are predominantly used as Pilot relays for lines up to 20 miles.

• HCB relay contains Sequence filters, DC polar unit with Operating and Restraining coils, Insulating and Saturating Transformers

SCE Property 18

Page 19: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Differential Relaying Philosophy

SCE Property 19

Page 20: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Pilot Relaying Philosophy

SCE Property 20

Page 21: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Pilot Relaying Philosophy• Westinghouse (ABB) LCB relays are used for

Pilot Relaying for Transmission lines from 20 to 250 miles length.

• The communication medium is Fiber Optics• The relay contains Sequence Filter, Transmitter

Modulator ( 1 Ph -> FM), Receiver De Modulator (FM –> 1Ph), Phase comparison Unit (compare currents at Local/ Remote terminal)

• For out of zone fault, the signals would be out of phase and in phase for fault in the zone.

SCE Property 21

Page 22: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Pilot Relaying Philosophy

SCE Property 22

Page 23: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Phase Comparison Relaying• Relay combination used with phase comparison systems are SLD or

SKBU carrier relaying and CO( Residual Ground)/ ICC (Directional ground).

• Phase comparison relaying compares current phasors at local and remote terminals. Line and Neutral potential are not required.

• Faults in the protected zone would cause the currents to trip in less than 3 cycles

• Fault detector turns on carrier signal during Fault• Transmitter generates blocking pulse during negative half cycle. • During external fault both transmitters produce additive blocking

pulse for the full cycle.• During internal fault out of phase pulse cancel blocking pulse,

allowing the relay to trip.

SCE Property 23

Page 24: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Phase Comparison Relaying• SPCU relays are used for Phase comparison for Phase and Phase to

Ground faults• Microwave is used for communication of current phasors. Guard signals

are transmitted for communication health. Relay trips in 9 cycles on loss of guard signal. Noise on communication channel will block tripping.

• SRU/ UIO as auxiliary relay for annunciation purpose• Directional comparison blocking ( SLYP/ SLYN) compares current

direction at both terminals to determine in zone or out of zone faults to block tripping

• SLYP provides Zone1 element ( 80% of line: instantaneous trip with TT), Zone2 (125% of Line) (Instantaneous for in zone fault and TT or blocking signal for out of zone faults) and Zone3 (180% of line sends blocking signal out of zone faults)

• SLYN provides Directional overcurrent, trip for in zone faults and block for out of zone faults

SCE Property 24

Page 25: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

DCB Philosophy• Impedance relays trip instantaneously for z1 faults

covering 80% of line• Over reaching impedance relays with z2 faults operate

with time delay covering 125% of the line• Directional comparison Blocking (DCB) allows over

reaching relays to trip instantaneously by blocking out of zone faults

• Thus Phase Distance Relays and ground over current relays can provide instantaneous protection for in zone faults

• Only one Communication channel is used for sending blocking signal only , used with PLC schemes

SCE Property 25

Page 26: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

DCB Relaying Philosophy

SCE Property 26

Page 27: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Typical Transfer Trip Relaying • Transfer Trip schemes are another flavor of Directional comparison

schemes, where two relays communicate to trip rather than block.• The two frequencies transmitted through two communication

channels are:– Guard frequency to keep guard relays closed to block tripping over

channel noise– Tripping Frequency to allow tripping relay to pickup and trip circuit

breakers• Basic Transfer trip Schemes:

– Direct Transfer Trip (DTP)• Direct Overreaching Transfer Trip (DOTT) – 125%• Direct Under reaching Transfer Trip (DUTT) – 80%

– Permissive Transfer Trip• Permissive Overreaching Transfer Trip (POTT) – 125 %• Permissive Under reaching Transfer Trip (PUTT) –80%

SCE Property 27

Page 28: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Typical PUTT Relaying Scheme• Typical PUTT Relaying Scheme would have following components:

– 3 GCX (Directional Distance Relays ( Z1, Z2 and Z3 protection)– Z2 and Z3 timer provides backup delayed tripping to POTT– 1 JBCG directional Ground Relays– 2 Transmitter and Receiver systems– 2 Transfer Trip communication channels – 1 Ground Fault detector relay (SC)– 1 HD Balance relay to be used as backup for Transfer Tripping– Trip signal at Remote terminal is enabled only when both transmitters

are keyed to trip simultaneously, if Local and Remote permissive trip signal is available

– Loss of Guard signal for six cycles continuously will disable the channel equipment and if it continues for more than 2 seconds resulting into alarm and if alarm is continuous, then the relays are made inactive

SCE Property 28

Page 29: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

PUTT Relaying Philosophy

SCE Property 29

Page 30: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Typical POTT Relaying Scheme• Typical POTT Relaying Scheme would have following components:

– 3 CEY (Impedance relay with zone 2 timer- starts at fault detection)– 1 SLYG directional Ground Relays– 2 GE Type 40 Transmitter and Receiver systems– 2 Transfer Trip communication channels (Primary/ Secondary)– When a terminal receives the shift from Guard to trip frequency and a

trip signal is present from Local relay, the local CB will trip– Zone 2 timer is reset after the fault is cleared– If zone 2 timer times out it will trip the local CBs irrespective of Tone

signals from receiver to provide a backup protection– If the fault is out of zone, then relay at the remote terminal will not

pickup and removes the Guard frequency, preventing local relay to trip– Loss of Guard signal for six cycles continuously will disable the channel

equipment and continuous alarm will deactivate the relays

SCE Property 30

Page 31: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

POTT Relaying Philosophy

SCE Property 31

Page 32: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Digital POTT Relaying Scheme• Some of the new microprocessor based relays being used in the industry are as

follows:• D60 Hybrid POTT Relays from GE• L90 Differential with DTT from GE• PLC Transfer Trip via RFL-9780• MW Transfer Trip via RFL-9745• FO Transfer Trip via RFL-9745• SEL 421 – POTT/ DTT with PLC from Schweitzer Electric• SEL-311L – Differential with DTT from Schweitzer Electric• SEL-311C – POTT from Schweitzer Electric• Communication Details:

– Serial RS485 communication Port– Ethernet full duplex network– Modbus communication Protocol– IEC61850 communication data architecture– Communication speed 9600MB/sec

SCE Property 32

Page 33: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Issues in Relay Communication

• Optical fiber cable damage or too high output from communications interface causes loss of channel signal alarm and may need attenuation or proper splice tray connection.

• T1 communication standard (DS1) requires transmittal of at least one pulse within any eight bit sequence. Loss of synchronization and unlocked frequency clocks could result in frame slips. Resulting in data loss.

• Leased Phone Lines need CSU channels as demarcation point between vendor and customer’s communication terminals. Interference on the cable/ CSU may cause loss of signal.

SCE Property 33

Page 34: SCE Property1 Tribhuwan Choubey – SCE/TDBU/ECQ Pilot Relay Schemes Communication Aided Protection Schemes

Issues in Relay Communication

• High induced voltages across pilot wire possibly caused by faults or lightning could cause induced fluxes and rise in ground voltage. This is remediated through provision of neutralizing reactors, voltage limiting circuits or surge suppressors.

• Open or shorted pilot wires are monitored and resulting erroneous trip signals are blocked.

SCE Property 34