Scully Intellitrol ® Technical Manual Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options Scully Signal Company / Tel. 617 692 8600 / Fax. 617 692 8620 / 800 2 SCULLY (272 8559) 70 Industrial Way, Wilmington, MA 01887-3479, USA / [email protected] / www.scully.com MaxSafety ® SYSTEMS IEC 61508 Certified SIL 2 / SIL 3 Capable FS Functional Safety Type Approved TÜVRheinland ®

Upload: others

Post on 29-Jan-2022

23 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: 61375 SIL Intellitrol SIL RevB

Scully Intellitrol®Technical Manual

Over�ll Prevention Control Unit withGround Veri�cation & Vehicle Identi�cation Options

Scully Signal Company / Tel. 617 692 8600 / Fax. 617 692 8620 / 800 2 SCULLY (272 8559)70 Industrial Way, Wilmington, MA 01887-3479, USA / [email protected] / www.scully.com

MaxSafety®

SYSTEMS

IEC 61508Certi�ed

SIL 2 / SIL 3CapableFS

Functional SafetyType Approved

TÜVRheinland®

Page 2: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Table of Contents

Introduction 5.

General 6.

1.1 Description

1.2 Monitoring functions

1.3 Output capabilities

1.4 Communications

1.5 Bypass

1.6 Additional Equipment

1.7 Display Panel

1.8 Approvals

1.9 Constraints

1.10 Internal Architecture

1.11 Technical Speci�cations

1.12 Con�gurations

Mechanical Installation 13.

2.1 Warnings

2.2 Water Proo�ng

2.3 European Installations

2.4 North American Installations

Electrical Installation 14.

3.1 Non-Intrinsically Safe (IS) Connections

3.2 Intrinsically Safe (IS) Connections

3.3 EMI Shield Kit Installation Instructions

Page 3: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Table of Contents

System Setup 19.

4.1 CPU Jumper Settings

4.2 VIP List

4.3 Bypass Key, Add/Erase Procedures

Initial System Check 23.

5.1 Inspect Wiring

5.2 Recommended Test Equipment

5.3 Scul-Test Loading Rack Tester

5.4 Model ST-2-DSWJ Tester

5.5 Fault Conditions

System Operation 26.

6.2 Normal Loading

6.3 After a Normal Load

6.4 Intellitrol Not Permitting

6.5 Bypassing Normal Operating Modes

Maintenance 28.

7.1 Preventative Maintenance

7.2 Warranty

7.3 Troubleshooting Guide

7.4 Installing Replacement Parts

7.5 Parts Available

Mechnical Service Hot-Line/Notes 35

Diagram Appendix 36.

9.1 Dwg. No. 63038C – Intellitrol Enclosure Outline, Model Series ICC-

9.2 Dwg. No. 63038 – Intellitrol Enclosure Outline, Model Series IC-

Page 4: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Table of Contents

9.3 Dwg. No. 63039 – Sculcon Plug and Cable Assembly Outline

9.4 Dwg. No. 61337C – Mech. Installation, Intellitrol Model Series ICC-

9.5 Dwg. No. 61337, Mech. Installation, Intellitrol Model Series IC-

9.6 Dwg. No. 61335C – (2-Wire, Optic or Therm.) Sculcon Field Wiring Diag.

9.7 Dwg. No. 61335 – (2-Wire, Optic or Therm.) Sculcon Field Wiring Diagram with Deadman.

9.8 Dwg. No. 61394C – Multiple Sculcon (2-wire and 5-wire) Field Wiring Diag.

9.9 Dwg. No. 61506 - Multi-drop Communications Field Wiring

9.10 Dwg. No. 63040SIL – SIL Intellitrol Control Module Outline

9.11 Dwg. No. 61290 Pg.-1 – System Diagram, FM & CSA, Intellitrol

9.12 Dwg. No. 61290 Pg.-2 – System Diagram, FM & CSA, Intellitrol

9.13 SIL Speci�c Information

Page 5: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Intoduction

Page 5.

Scully Signal Company was incorporated in 1936 with the invention of the Ventalarm Signal®,a whistling tank-�ll signal designed to replace �oat devices for high level liquid indication and over�ll prevention. It was an immediate success in the United States and Canada and soon replaced unreliable �oats in many tank applications.

Scully Signal Company then followed in 1950 with an Automatic and Continuous Self-Checking concept and patents. This brought a new level of fail-safe operations to Automatic Level Control and Over�ll Prevention Systems with its "Dynamic Self-Checking®" patents and controls, which are installed worldwide with major oil and chemical companies plus military aviation refueling operations.

Scully's level controls check their own operation around the clock and have been applied to numerous monitoring operations in several industries such as �ame safeguard control monitoring systems in re�neries for both oil and chemical operations as well as top and bottom loading operations forterminals and tank trucks worldwide.

Summing up an astonishing fail-safe record worldwide in petrochemical operations this past quarter of a century, Dynamic Self-Checking, the electronic heart-beat system that fails safe "unless incorrectly installed or deliberately bypassed!"

SIL - Safety Integrity Level, the latest industry standard in safety.

The Intellitrol is Scully's most advanced loading rack monitoring system. The Intellitrol was recentlyevaluated by TÜV Reinland and certi�ed as part of a SIL II Over�ll Prevention System when used in conjunction wih Scully Sensors. This functional safety assessment and certi�cation is a standards based evaluation of the safety equipment and its various failure modes. Scully's DynamicSelf-Checking design was key in the achievement of this �rst in the industry certi�cation for road tanker over�ll systems.

SIL is an end to end system assessment of safety equipment. In an over�ll system, such as theIntellitrol, it includes all devices from the sensors to the control relay in the Intellitrol. Each device must have apublished Failure in Time (FIT) number for both safe and unsafe failure modes. In doing a functional safety calculation, failure contributions (FITS) of all system elements must be aggregated so an overall system prediction can be made and a SIL rating be calculated.

Page 6: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

General

Page 6.

1.1 Description The Intellitrol is intended to serve as a secondary over�ll protection system for loading operations. It is intended for use in hazardous locations and is packaged in an explosion-proof (�ameproof) enclosure and has both International and US approvals and certi�cations.

The Intellitrol performs a variety of monitoring functions and provides a number of outputs to control valves, pumps and other systems including Terminal Automation Systems (TAS). It has an integrated display to indicate system and monitoring status, a bypass capability, and communications for integration with TAS and other systems.

The Intellitrol contains a pair of microprocessors, each with its own relay that monitors critical functions. Only when both processors detect a safe condition will both relays close and make outputs permissive.

The Intellitrol is designed to be Faylsafe® and in the event of a failure (power, sensors, or internal electronics) the unit will enter a non-permissive (safe) state.

This state-of-the-art Dynamic Self-Testing® system controller provides over�ll prevention and optional vehicle ground veri�cation and vehicle identi�cation operating in a single enclosure. The Intellitrol also provides the user with comprehensive diagnostic information, both locally on the exterior of the control unit housing and remotely to the terminal automation system via RS-485 communications.

1.2 Monitoring functions

1.2.1 Over�ll The Intellitrol monitors 5-wire optic sensors, 2-wire optic and 2-wire thermistor sensors that are compliant with EN13922 and API-1004 standards. The Intellitrol does not support 3-wire thermistor sensors such as the SP-BLH or SP-BLHK.

The system automatically determines which sensor type is attached. The Intellitrol is compatible with on-vehicle electronics like the Intellicheck and the Onboarder and interprets their output signals according to the interface used.

1.2.2 Ground The Intellitrol can be con�gured via an internal jumper setting to monitor static ground veri�cation based on:

• Ground Bolt/Ground Ball using Scully pioneered Dynamically Self-Testing® ground veri�cation systems or

• Resistive ground veri�cation systems

Page 7: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

General

Page 7.

1.2.3 Vehicle Identi�cation Prover The Intellitrol is capable of monitoring Scully Truck Identi�cation Modules (TIMs). The TIM is a small truck-mounted device which gives every vehicle a unique identi�er that can be read by the Vehicle Identi�cation Prover (VIP) feature of the Intellitrol. This identi�cation can be compared to a program mable list stored in the non-volatile RAM on the CPU of the Intellitrol for a Go/No-Go decision or can be read by a TAS and used for other functions such as billing and automatic compartment size determination for loading using preset meters.

1.2.4 Deadman Switch The Intellitrol is capable of monitoring a deadman switch which must be held closed by an operator to obtain a permissive state. If the deadman handle is released, the switch will open and the Intellitrol will go non-permissive.

1.3 Output capabilities

1.3.1 Form A ( Powered ) Relay contacts One set of fuse-protected relay contacts is available for output. These contacts are also used for internal monitoring of relays and must only be used for AC power switching. If a TAS requires voltage-free switching, the Form C contacts should be used. The Main Display on the front panel indicates relay status.

1.3.2 Form C (Volt free) Relay contacts A set of volt free contacts is available for low voltage switching applications. These contacts are switched together with the Form A contacts and cannot operate separately.

1.3.3 Truck Present A transistor switch is available to indicate that a truck is connected. Typical use is to control a gate to prevent drive-offs while connected to the Intellirol.

1.4 Communications The Intellitrol has an RS-485 interface which can be used to perform maintenance and serves as a communications interface for Terminal Automation Systems. Through this interface, the TAS can obtain Intellitrol status including truck present, sensor, and ground status as well as directly reading TIM information. For more details on the operation of this interface please contact Technical Services.

Page 8: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

General

Page 8.

1.5 Bypass The Intellitrol has the capability to be bypassed for some fault conditions when connected to a vehicle. The bypass capability is accessed using a bypass key, sold separately. The bypass key is compared to an internal list stored in non-volatile RAM for authorization. If the key is authorized to bypass the unit, the Intellitrol will recognize it and bypass the fault (over�ll, ground or vehicle ID). An over�ll sensor that becomes wet while loading cannot be bypassed.

1.6 Additional Equipment

1.6.1 Sculcon Junction Box A Sculcon Junction Box is highly recommended because it is used to interface between the Intelli trol's intrinsically safe connections and a vehicle connection. It comes with a plug and cable assembly for truck connection. The Sculcon Box enables cable replacement without requiring that the Intellitrol door be opened or the seal on the Intellitrol door be broken.

1.6.2 Deadman Control Switch A Deadman Control Switch is used with the Intellitrol when the operator must be present and actively involved at all times during the loading operation. Thus, the operator must hold the dead man switch closed during the entire loading operation; otherwise the Intellitrol will go non-permis sive. The Deadman is optional.

1.7 Display Panel The Intellitrol Display Panel is designed to be seen at the terminal by an operator located in the lane area of the tanker delivering or receiving a load. The display contains sections with unique functions which are listed in Figure 1.

1 2 4 5 6 7 83

Optic PulseOut

Communication

Ground

Service

Dynacheck

AuthorizedUnauthorized

Vehicle Identification

Standby

In

Terminal

Vehicle

Automatic & Continous Self-Checking

Compartment

Red (Non-Permissive)Main Status Indicator

Green (Permissive)Main Status Indicator

Wet / Faulty SensorIndicators

Communications Indicators

Bypass Port

Dynacheck Indicator

Ground Fault Indicator

5-Wire Optic ModeStatus Indicators

Service Indicator

Vehicle Identi�cationProver Indicators (VIP)

Figure 1: Main Status and Diagnostic Display Panel Indicators

Page 9: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

General

Page 9.

1.7.1 Display Panel Indicators Note: References below to �ashing slow and fast are compared to Dynacheck �ashing rate.

Main Status Bars • Red Bar On, (Non-Permissive) - Flashing slow, faulty sensor bypassed - Flashing fast, main output relay shorted • Green Bar On, (Permissive) - Flashing, ground or vehicle identi�cation bypassed

Compartment 8-LED's (Fault Indicators) • Off, No truck/dry sensor • Red, Wet or warming sensor - Flashing slow = open 2-wire sensor - Flashing fast = shorted 2-wire sensor Note: When a compartment fault is detected:

A compartment LED on indicates a fault. It may be faulty wiring, thermistor sensors not warmed up, or wet compartments.

• For 2-wire only, 6 or 8 compartments are monitored, depending on jumper settings. LED's on indicate that one or more compartments are faulty and produces a non-permissive condition preventing product transfer.

• For 5-wire only, 1 to 12 compartments are monitored and one compartment at a time is displayed. Up to two compartment LED's are displayed per faulty compart ment and produces a non-permissive condition preventing product transfer. 1-12 compartments are monitored. 1-8, and 9-12 are indicated by LED No.8 on plus one additional LED 1-4. Adding the two LED numbers, (8+1) = 9, and (8+1+2+3+4) = 12, and so on indicates which of 12 compartments is faulty.

Ground, 1 LED • Red, No ground bolt/ground ball detected or no resistive short detected • FLASHING Red, Ground veri�cation function bypassed

Communication, 2 LED's Requires RS485 com link and VIP/TIM Connection • "Terminal" - Yellow, Communications in progress to TAS • "Vehicle" - Yellow, Communications in progress to TIM

Optic Pulse, 2 LED's • "In" - Green, Receiving pulses from 5-wire sensors • "Out" - Green, Transmitting pulses to 5-wire sensors

Page 10: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

General

Page 10.

Service, 1 LED • FLASHING Red, Operational problem with the Intellitrol

Dynacheck, 1 LED • FLASHING Yellow, Normal operation, once per second • OFF, Operational problem with the Intellitrol

Vehicle Identi�cation Prover, 3 LED's • "AUTHORIZED" - Green, Truck Identi�cation Module (TIM) serial number has been read and found in authorization list. - Flashing Green, VIP function bypassed • "UNAUTHORIZED" - Red, Truck Identi�cation Module (TIM) serial number is not found in authorization list.

• "STANDBY" - Yellow, Truck Identi�cation Module (TIM) has not been read.

1.8 Approvals All Intellitrol units fall under the approvals for:

• FM • NEMA 4 rating, Watertight and corrosion resistant. • NEMA 7 rating, Explosion-proof with intrinsically safe outputs for Class I, Division 1, Groups C & D. • ATEX - Ex d ia IIB T4 (Tamb = -40oC to +60oC) Gb

1.9 Constraints The Intellitrol Control Unit has been designed to be impact-resistant, however, do not subject it to excessive mechanical or thermal stresses. Do not allow the unit to come in contact with aggressive substances.

The Intellitrol may only be repaired by quali�ed technical personnel by replacing the internal control or display module with equivalent modules. The internal control module and display board modules are not �eld repairable.

Do not open the Intellitrol door when an explosive gas atmosphere is present. To avoid static discharge buildup, clean only with a damp cloth.

Page 11: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

General

Page 11.

1.10 Internal Architecture

RS485COMM

TRUCK PRESENT

6

5

1

2

3

FORM CVOLT FREEOUTPUT

4TB2

TB3

FORM A LINE OUTPUT

3

TB2

HOT

HOT 2

1

FUSE5A

NEUT

123456789101234

TB4TB6

RED

GREEN

DISPLAY PANEL

J1

1

3

2

4TB1

Dynacheck

GND

GND

1

32

TB5

10

8

BYPASSPORT

COMPARTMENT

COM

VIPGNDSERV

O.P.

1 2 3 4 5 6 7 8

3

6

I.S.CONNECTIONS

NO

NC

COM

NO

SENSORS 1-8GND SENSE

GND RTNDEADMAN

+28VDC+28VDC

+5VDC

K1-B1/2 RELAYK1-B1/2 RELAY

K2-A1/2 RELAY

K2-A1/2 RELAY

U8U8

CPU2

F8 FUSE 5A

F5F5

CPU1

K2-B1/2 RELAYK2-B1/2 RELAY

K1-A1/2 RELAY

K1-A1/2 RELAYPS1PS1

Figure 2: Intellitrol Block Diagram

Page 12: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

General

Page 12.

1.11 Technical Speci�cations

1.11.1 Temperature Operating: -40 to +60 Degrees C (-40 to +140 Degrees F) Storage: -45 to +85 Degrees C (-50 to +185 Degrees F) 1.11.2 Power Requirements Voltage: 230 V +/-10% 50Hz or 120V +/- 5% 60Hz Consumption: 50 Watts maximum

1.11.3 Outside Dimensions See Appendix 9.1 & 9.2 for mounting details.

1.11.4 Weight 14.1 kgs (31 lbs)

1.12 Con�gurations The following models of the Scully Intellitrol are available in Europe and North America. All fall under Section 1.8 Approvals and Section 1.11 Technical Speci�cations.

1.12.1 European Table, ATEX European series uses M25 X 1.5 (ISO) METRIC conduit entries. Default Con�guration: (230VAC)

Model Description Part NumberICC-OG Over�ll Prevention and Ground Veri�cation 09547ICC-OGV Over�ll Prevention, Ground Veri�cation and Vehicle Identi�cation Prover 09548

Model Description Part NumberIC-OG Over�ll Prevention and Ground Veri�cation 09549IC-OGV Over�ll Prevention, Ground Veri�cation and Vehicle Identi�cation Prover 09550

1.12.2 North American Table, FM/CSA North American series uses 3/4” NPT SAE conduit threads. Default Con�guration: (120VAC)

Page 13: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Mechanical Installation

Page 13.

When choosing a location on the loading rack for the Intellitrol, keep in mind that, while it can be exposed to the elements, the main status indicators and diagnostic display panel on the front of the Intellitrol should be readily visible and within easy reach to the user. The control unit should be mounted vertically, at eye level, in a location where the front cover can open 120 degrees for servicing.

Refer to the Intellitrol Enclosure Outline and Sculcon Plug and Cable Assembly Drawings in Appendices 9.1 - 9.3 for physical dimensions, location of mounting bolts, electrical gland/cable conduit entry locations, and enclosure bonding stud. The enclosure bonding stud is provided for proper electrical bonding (grounding) of the enclosure to earth ground. Use only the three conduit entry holes provided for wiring. The left and right side holes are for power and control wiring. The bottom hole is for intrinsically safe sensor wiring only. Do not drill any additional holes in the enclosure, as doing so violates the enclosure's hazardous location approval and voids the warranty

2.1 Warnings • All electrical gland/cable conduit entries entering the enclosure must have a seal �tting installed within 18 inches (45.72 cm), of the enclosure to comply with the enclosure's approval requirements. • The electrical gland/cable conduit entry in the bottom of the enclosure marked “Intrinsically Safe Entry” is for the sensor wiring between the Intellitrol plug and cable assembly and for the optional deadman switch wiring only. To maintain intrinsic safety, this gland/cable conduit entry must not be used for any other wiring.

2.2 Water Proo�ng To avoid future maintenance issues regarding water in�ltration into the housing via the electrical gland/cable conduit entries, we strongly recommend the following precautions:

• Minimize long vertical gland/cable conduit runs into the sides of the enclosure as they promote water channeling to the gland/cable conduit seal �tting packing. • Carefully install the cable conduit/glands on the sides of the enclosure, taking extra precaution to make certain that the installation is correct and sealed properly (as required by code).

2.3 European Installations To maintain the �ame proof rating of the enclosure, the cable gland �ttings at all entries to the enclosure should be equipped with a �ber washer between the cable gland and the enclosure to properly seal the threads against water in�ltration.

2.4 North American Installations To maintain NEMA 4 and NEMA 7 ratings, all threaded joints of the conduits entering the enclosure must be sealed with a copper or lead based anti-seize/sealant.

Page 14: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Electrical Installation

Page 14.

Refer to the Installation Wiring Diagrams for the Intellitrol Control Module and Sculcon Junction Box Plug and Cable Assemblies in Appendices 9.6 - 9.9.

3.1 Non-Intrinsically Safe (IS) Connections All Non-IS connections are at the top of the control module and must never be intermixed with IS wiring.

3.1.1 Power Selection The Intellitrol is �eld selectable for either 120 or 230 VAC by setting red jumper(s) J10 and J11 at the top of the board. • 120 VAC, Insert 2 horizontal jumpers, one in J10 and one in J11 • 230 VAC, Insert a single vertical jumper between J10 and J11 Note: Refer to Appendix 9.6. See J10 and J11 con�gurations.

3.1.2 Ground • TB1-1, Green wire door ground • TB1-2, Green wire box ground • TB1-3, AC power ground • TB1-4, Extra AC power ground

It is imperative to Intrinsic Safety that the unit be connected to earth ground. A green terminal block is located at the top left of the control module to terminate an incoming ground connection. Do not modify the other connections on this terminal block.

3.1.3 AC Power Connection • TB2-1, Neutral • TB2-2, Hot

3.1.4 Switched Outputs Powered • TB2-3, Power in • TB2-4, Power out

These connections are used internally to monitor relay status and use a normally open switch for line voltage use.

Caution: Must be the same phase as the power in. Must not be used for low voltage DC switching.

Page 15: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Electrical Installation

Page 15.

Unpowered • TB3-1, Normally Open (NO) • TB3-3, Normally Closed (NC) • TB3-2, Common (COM)

This set of dry Single Pole Double Throw (SPDT) relay contacts are available for connection of low voltage devices. In the event of a failure all switched power and the NO connections of the unpow ered output will fail safe. The NC contact of the unpowered output will remain closed should power be lost and is not fail safe. The NC contact should NOT be used for safety related functions.

3.1.5 Status Output/Input Good Ground Output • TB3-5, Transistor Emitter • TB3-6, Transistor Collector, via a fuse and resistor

This output is a low side transistor switch and will conduct when a truck is detected. Connection is as shown below.

Caution: Must be the same phase as the power in.

3.1.6 RS485 Communications Terminal • TB5-1, ground terminal • TB5-2, (TD/RD) "B" terminal • TB5-3, (TD/RD) "A" terminal.

Remote communications are available through connector TB5. Appendix 9.9 shows a typical Intellitrol multi drop communications wiring scheme for connection details. While it is possible for an Intellitrol to share a RS-485 communications line with other equipment, we recommend that each Intellitrol controller have a dedicated RS-485 communications line to simplify troubleshooting.

Figure 3: TB3, 5-6 Opto-Coupler

Page 16: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Electrical Installation

Page 16.

3.2 Intrinsically Safe (IS) Connections Caution: DO NOT RUN WIRES connected to Intrinsically Safe connections next to Non Intrinsically Safe wires or connections. Doing so creates risk and an explosion may occur under adverse conditions.

All Intrinsically Safe (IS) connections are made through connectors TB4 and TB6 at the bottom of the box. Connections from TB4 are typically wired one-to-one from the Intellitrol to the terminal block in the Sculcon box. Different cable con�gurations are required for connection to 2-wire or 5-wire trucks.

3.2.1 Sculcon Junction Box Plug and Cable Assembly The Sculcon Junction Box is the preferred way to connect to the IS-Interface. Refer to Appendix 9.3 for the typical Sculcon junction box outline diagram showing physical dimen sions, location of mounting bolts and gland/cable conduit entry location details. Refer to Appendices 9.6 - 9.8 for wiring diagrams showing the interconnection details for the Sculcon junction box plug and cable assembly to the Intellitrol. 3.2.2 European Standard Sensors • Both 2-wire and 5-wire trucks connect through a 10-pin plug and 10-pin connector (per EN13922) • Or alternately one similar to the North American standard.

3.2.3 North American Standard Sensors • 2-wire trucks use an 8- or 10-pin plug on a 10-pin cable. • 5-wire trucks use a 6-pin plug on a 6-pin cable wired to the same connection. Table 1 below describes the connections and function of TB4, Pins 1-10.

ConnectionPin Number 1 2 3 4 5 6 7 8 9 10

Terminal Number 1 2 3 4 5 6 7 8 9 10

TB4 Pins

Connection Sculcon Junction Box & Cable Plug Pin / Socket Receptable

2-Wire8 Compartment

2-Wire6 Compartment

5-Wire12Compartment

Sensor1

Sensor2

Sensor3

Sensor4

Sensor5

Sensor6

Sensor1

Sensor2

Sensor3

Sensor4

Sensor5

Sensor6

Sensor7

Sensor8

GND/TIM

Verify

GND

GND/TIM

Verify

GND

GND/TIM

Verify

Pulseto

Sensors

Pulsefrom

Sensors

Powerfrom

Sensors

GNDDiag.

Page 17: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Electrical Installation

Page 17.

Deadman Control • TB6-3, NO, Deadman Switch Input • TB6-4, Return

This Normally Open (NO) connection can optionally be used for a Deadman (switch closure) input signal. When this option is enabled, the Intellitrol will permit only when the deadman switch is closed.

3.2.4 J1 Front Display Panel Connection J1 is located at the bottom left corner of the control board. J1 is a 6-pin ribbon header that provides an IS connection from the controller to the Front Display Panel.

Caution: Make sure to note the orientation of this connector before removing.

Page 18: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Electrical Installation

Page 18.

3.3 EMI Shield Kit Installation Instructions In order to minimize Electro Magnetic Interference (EMI), ferrite �lters need to be installed on the three access cables entering the Intellitrol Controller. To reduce susceptibility to external EMI, the snap-on ferrite �lters should be installed after the wiring connections are completed inside the Intellitrol. Make sure to leave only enough wire near the connectors to accommodate the snap-on ferrites. The kit contains three snap-on EMI �lters. Simply snap one EMI �lter over each of the wires exiting the control box in all three locations shown.

Control Module: 1. Power in on the top side 2. Control out/Modbus top side 3. I.S. outputs at bottom

KEEP ALL LEADS AS SHORT AS POSSIBLE

P/N 28455

POWER

P/N 28454

CONTROL

P/N 28455

I.S.

Page 19: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

System Setup

Page 19.

1 - 2 TB3-5/6 CONFIG Con�gures TB3 Pins 5-6 to indicate Good Ground (installed) or Truck Present (open)"3 - 4 DEADMAN ENABLE Enable Deadman Switch Input5 - 6 DEADMAN DISABLE Disable Deadman Switch Input7 - 8 VAPOR ENABLE Not Used9 - 10 VAPOR DISABLE Not Used11 - 12 VIP ENABLE Enable Vehicle Identi�cation Proving13 - 14 VIP DISABLE Disable Vehicle Identi�cation Proving15 - 16 GND ENABLE Enable Ground Proving17 - 18 GND DISABLE Disable Ground Proving19 - 20 ADD KEY S/N Add Bypass Key Serial Number21 - 22 NORMAL OPERATION Normal Operation23 - 24 ERASE KEY LIST Erase Bypass Key Serial Number List

J5 Function Name Description

4.1 CPU Jumper Settings The Intellitrol has a number of features and functions that can be enabled through internal jumper settings. The jumpers on the CPU board are listed below.

4.1.1 Jumper Selectable Options • J5 OPERATING MODE SETTINGS (see 4.1.2 below) • J8 & J1 COMM MODBUS ADDRESS (see 4.1.3 below) • J7 COMM PROTOCOL (see 4.1.4 below)

4.1.2 J5, OPERATING MODE SETTINGS Enable/Disable (purchased options only). The Intellitrol options which are purchased can be disabled via jumper plugs on the CPU board. Moving jumpers for non purchased options has no effect.

Note: The last three jumpers control Enrolling Bypass Key serial numbers into the Intellitrol's nonvolatile memory. Refer to Section 4.3 for more detail.

3.1.4 Switched Outputs Setting communications speeds and feeds Two sets of jumpers are used for setting device Modbus. Jumper J8 sets the tens group and jumper J1 sets the ones group. The Modbus address is the sum of the two jumpers.

Page 20: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

System Setup

Page 20.

4.1.4 J7, COMM PROTOCOL RS485 (J7 Jumper Setup) • J7, allow the user to select: - Parity, (NONE/ODD/EVEN) - Baud Rate, (1.2, 2.4, 4.8, 9.6, 19.2 KB/S) - Data Pack, (7 or 8 Bits)

Note: Jumper Terminals: Black denotes default installed jumpers, except J5, operating mode settings are dependent on options purchased.

RESET

Figure 4: CPU Board Layout

Page 21: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

System Setup

Page 21.

4.1.5 Control Board Jumper Settings Several modes can be selected using jumpers on the main Control Board.

CHANNEL, (Number of Compartments) • J31, Blue - Sets 6 channel mode for 2-wire Sensors • J32, Blue - Sets 8 channel mode for 2-wire Sensors

GND BOLT/BALL OR AUTOMATIC GROUND TYPE DETECTION (Type of ground system check) • J8, Black - Inserted sets resistive ground; otherwise ground bolt/ground ball

THRESHOLD • J4, Black - Inserted sets thermistor threshold = 3.8V for SP-BLK & BLUK type sensors; otherwisethermistor threshold = 3.5V SP-BL & BLU type sensors.

JUMP START • J21, 22 and 23, Red - Inserted disables Jump Start limiting IS output voltage for ATEX applications. All three MUST always be in for ATEX installations. Otherwise remove the three jumpers to enable Jump Start for installations requiring preheating of thermistor sensors.

4.2 VIP List This feature is optional and must be ordered. Trucks and Tankers can be out�tted with a Truck Identi�cation Module (TIM) that gives the vehicle a unique serial number. These numbers may be stored on the Intellitrol in non-volatile RAM so that the information may be passed to a terminal controller that works in conjunction with the Intellitrol system. The serial numbers must be entered into the Intellitrol via the RS485 communication port.

4.3 Bypass Key, Add/Erase Procedures Before use, each Bypass Key must �rst be programmed into the Intellitrol's permanent memory. Power must be on.

Warning: The following procedure must not be performed in a �ammable hazardous environment. The Intellitrol door cannot be open while fuel or a tanker carrying �ammable substances is present.

Page 22: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

System Setup

Page 22.

4.3.1 Adding Bypass Key entries: 1. Unbolt and open the Intellitrol door. Store the bolts in a safe place. 2. Move the "Normal Operation" jumper on J5 to the "Add Key S/N" position (refer to Figure 4: CPU Board Layout). 3. Push the "Reset" button (top center of CPU board). 4. Close the door and wait for both Optic Pulse and Communications to blink together continuously at double the Dynacheck rate. The Intellitrol is now ready for entering a bypass key serial number. 5. Position a bypass key up to the bypass port. The Intellitrol will read the bypass key serial number incrementing the "Compartment Number" LED. After all 8 compartment LED's light up, the large green permissive light will �ash brie�y to indicate that the bypass key serial number has been stored in memory. 6. To add additional bypass keys, repeat Step 5 above. When all bypass key serial numbers have been added, proceed to Step 7. 7. Open the Intellitrol door and return the jumper on J5 to the "Normal Operation" position. 8. Push the "Reset" button. 9. Close and properly secure the Intellitrol door using the original bolts. 4.3.2 Erase Bypass Key entries: It may at some point be necessary to delete the list of "authorized" Bypass Key serial numbers store within the Intellitrol's permanent memory (i.e. if a Bypass Key is lost). To delete the list of "authorized" Bypass Keys, do the following:

Warning: The following procedure must not be performed in a �ammable hazardous environment. The Intellitrol door cannot be open while fuel or a tanker carrying �ammable substances is present.

Caution: All bypass key entries will be erased.

1. Unbolt and open the Intellitrol door. Store the bolts in a safe place. 2. Move the "Normal Operation" jumper J5 to the "ERASE KEY LIST" position (refer to Figure 4: CPU Board Layout). 3. Push the "Reset" button (top center of CPU board). 4. The large red non-permissive indicator will �ash brie�y and the Compartment, Optic Pulse, and Communication LED's will blink at double the Dynacheck rate to indicate that all bypass key entries have been deleted from memory. 5. Return the jumper on J5 to the "Normal Operation" position. 6. Push the "Reset" button. 7. Close and properly secure the Intellitrol door using the original bolts.

4.3.3 External Bypass key entry/deletion Bypass key serial numbers may be added or deleted one by one from the Intellitrol remotely via external software through the communications port.

Page 23: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Initial Systems Check

Page 23.

Performing an Initial System Check is essential and proves that the Intellitrol installation is performing safely and correctly.

5.1 Inspect Wiring 1. All electrical gland/cable conduit entries must have a seal �tting installed within 18 inches (45.72 cm) of the enclosure to comply with approval requirements. 2. The electrical gland/cable conduit entry in the bottom of the enclosure marked “Intrinsically Safe Entry” is for the sensor wiring between the control unit plug and cable assembly and for the optional deadman switch wiring only. To maintain intrinsic safety, this gland/cable conduit entry must not be used for any other wiring.

5.2 Recommended Test Equipment Scully Signal Company provides two options for testing the Intellitrol. The SIL Intellitrol comes with a Scul-Test Loading Rack Tester which provides a quick and simple method of isolating "non-per mits" to either truck or loading rack equipment faults. For individual compartment checks, cable continuity or �oat switch detection, use the Universal Loading Rack Tester Model ST-2-DSWJ. While use of Scully Signal Company test equipment is not required, the test equipments provide all of the proper over�ll prevention system signals required to verify the new installation without requiring actual vehicles for the testing.

5.3 Scul-Test Loading Rack Tester The Scul-Test Loading Rack Tester simulates trucks with optic sensors plus optional TIM, Ground Bolt or resistive ground con�gurations. The con�guration to be tested is set via jumpers on the rear of the Scul-Test unit. There are three jumper positions with two factory set jumpers. The factory default is set to Ground Bolt and TIM (two outer jumpers installed). If using a Ground Bolt only, the jumpers should stay in the factory default setting. If using resistive ground veri�cation, reposition the jumpers so only the center jumper is inserted.

If the Intellitrol is con�gured for VIP, the TIM must be added to the Intellitrol's TIM list (refer to Section 4.2).

Once jumpers are set, install the Scul-Test unit in place of the existing Sculcon junction box cover.

GND BOLT

TIMRESISTIVE GND

Figure 5: Rear view of Scul-Test unit

Page 24: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Initial Systems Check

Page 24.

5.3.1 Operating Instructions 1. Insert key and turn to enable. 2. Connect rack plug and cable to tester socket. 3. A permit on the rack equipment indicates it is operating properly. Make sure a permit is maintained as you �ex the rack plug and cable assembly. 4. Disconnect rack plug and cable from tester socket. 5. Return key to disable and remove key.

5.4 Model ST-2-DSWJ Tester The Model ST-2-DSWJ Tester provides a rotary switch to select the following functional safety checks: • Cable Continuity • Float Switch Detection • Thermistor Sensor Detection • Optical Sensor Detection

5.4.1 Operational Testing Sequence 1. No vehicle or tester connected to Intellitrol. 2. Power up Intellitrol. 3. Intellitrol will go through a power up sequence, including the testing of all internal func tions and operating parameters. 4. Checks and enables display panel LED's in sequence. 5. Red non-permissive indicator will light after 15 seconds. 6. Yellow Dynacheck LED will �ash indicating that the Intellitrol is ready to accept a vehicle. If the Intellitrol is connected to a terminal automation system, the yellow terminal LED will also �ash each time the Intellitrol is polled by the automation system.

5.4.2 Equipment Attachment Set the ST-2-DSWJ tester to Thermistor Sensor Detection mode. Attach the black or green 2-wire thermistor or 2-wire optic plug from the Intellitrol to the 2-wire thermistor or 2-wire optic socket (SJ- 8S-2 bayonet pin style) on the right side of the housing.

5.4.3 Two-Wire Thermistor Sensor Operation Testing The ST-2-DSWJ tester uses one "Channel Test" button/switch per thermistor sensor and each corresponding sensor will be tested when that button is depressed. When the tester is attached to the thermistor socket, the Intellitrol will detect that it is attached to a “thermistor” equipped vehicle and proceed to warm up the sensors (the tester has traditional thermistor sensors inside). While the sensors are warming up, the 6 (or 8) red compartment indica tor lights at the top of the Intellitrol's diagnostic display panel will light, indicating 6 (or 8) wet sensors. As each thermistor sensor warms up, the red compartment indicator, corresponding to that sensor, will go out indicating a dry sensor. When all of the thermistor sensors are warmed up (up to 75 seconds required) the Intellitrol will permit, and the green main status indicator will come on. Verify that the Intellitrol's main output relay contact has closed (turned on) and that product can be transferred. This can be done by verifying that this permissive signal is available at the product meter(s) external permissive input terminal(s). Some metering systems also have a visible indicator

Page 25: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Initial Systems Check

Page 25.

(LED) to indicate that the external permissive signal is satis�ed. For each thermistor sensor selected, verify that the Intellitrol goes non-permissive and shuts down the Rack/Gantry. The corresponding compartment indicator light on the Intellitrol diagnostic display panel will light when the test button/switch is pushed. If more than one plug (or two different styles of plugs) is used on this installation for 2-wire thermistor or 2-wire optic operation, repeat the above tests for the other plug.

5.4.4 Five-Wire Optic Sensor Operation Testing Set the ST-2-DSWJ tester to Optic Sensor Detection mode. If the installation uses a single plug for both 2-wire thermistor or 2-wire optic and 5-wire optic modes, leave the plug connected as per the above. If the installation uses separate plugs for 2-wire thermistor or 2-wire optic and 5-wire optic operating modes, attach the optic plug from the Intellitrol to the optic socket. This will be either the SJ-6W-3 bayonet pin style socket on the left side of the housing for a blue "6W" style optic plug, or the SAE J- 560 style socket on the back of the tester housing for a "6X" style optic plug. When attached to this optic socket, the Intellitrol will detect that it is attached to a 5-wire optic equipped vehicle and proceed immediately to permit. The Intellitrol's diagnostic display panel will light, indicating an "optic out" pulse from the Intellitrol and an "optic in" pulse from the tester. As the Intellitrol permits, the green main status indicator will light up. Verify that the output to the metering system again turns on and that product can be transferred. Verify that when push-button/switch no. 2, no. 4 or no. 6 on the tester is pushed, the Intellitrol goes non-permissive and shuts down product �ow. Compartment indicator light no. 1 on the Intellitrol diagnostic display panel will light when one of these tester buttons is pushed.

If more than one plug (or two different styles of plugs) is used on this installation for 5-wire optic operation, repeat the above tests for the other plug.

5.4 Model ST-2-DSWJ Tester If the Intellitrol fails the power up diagnostic test, the Service LED will �ash ON-OFF and the Dynacheck light will be off. After making sure that the Intellitrol's plug(s) are not connected to a truck, remove power from the unit for 15 seconds and reapply. See that the Intellitrol goes through the power-up sequence per above. If not, refer to the Troubleshooting Guide in Section 7.3. There can not be a vehicle attached to the Intellitrol during power-up (or during a reset). If there is a vehicle attached during power-up, the Intellitrol will fail its diagnostic tests.

If the Intellitrol does not permit the tester in either of the above modes, refer to the diagnostic display panel for speci�c information on identifying the cause of the problem.

Page 26: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

System Operation

Page 26.

Most of the detailed instructions and cautions for operation of the Intellitrol system and accessories have already been discussed. The basics of loading a vehicle are described below. Refer to Figure 6 for details of the Intellitrol's main status indicators and diagnostic display panel.

1 2 4 5 6 7 83

Optic Pulse

OutCommunication

Ground

Service

Dynacheck

Authorized

Unauthorized

Vehicle Identi�cation

Standby

In

Terminal

Vehicle

Automatic & Continous Self-Checking

Compartment

Red (Non-Permissive)Main Status Indicator

Green (Permissive)Main Status Indicator

Wet / Faulty SensorIndicators

Communications Indicators

Bypass Port

Dynacheck Indicator

Ground Fault Indicator

5-Wire Optic ModeStatus Indicators

Service Indicator

Vehicle Identi�cationProver Indicators (VIP)

Figure 6: Main Status and Diagnostic Display Panel Indicators

Page 27: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

System Operation

Page 27.

6.1 Normal Loading The Intellitrol is capable of automatically detecting the presence of 2-wire and 5-wire over�ll sensors. In operation it constantly monitors the truck plug while running diagnostics. Once a truck is detected the system determines the sensor type and monitors for dry condition. Optic sensors are detected within a second. Thermistor sensors must heat up before indicating a dry condition. The heat-up time for thermistor sensors can take up to 75 seconds. This is a normal condition.

6.2 After a Normal Load Disconnect the plug from the vehicle to be loaded. The Intellitrol will return to its non-permissive state and the diagnostic display panel will �rst �ash all of the 8 compartment indicators and then clear (go blank) within a few seconds. This indicates that the Intellitrol's plug is ready to be connected to the next vehicle.

6.3 Intellitrol Not Permitting If the Intellitrol main display does not go green, the reason for the problem will be indicated in the front panel display (see Section 7.3 Troubleshooting Guide for details). This condition can be bypassed with the use of a properly registered bypass key

6.4 Bypassing Normal Operating Modes 6.4.1 Bypassing in General Before bypassing always verify that it is safe to do so. To bypass a detected fault condition the bypass key must be held against the side of the Intellitrol front panel at the bypass port for 10-20 seconds. When in bypass mode the main display will blink. When blinking red, faulty sensors are bypassed. When blinking green the ground or VIP is bypassed. • The maximum bypass time is settable via the communications port from 15 to 60 minutes. • Bypass operation automatically ends when the vehicle is disconnected. • If more than one fault condition exists preventing loading (e.g. ground and VIP), the bypass key must be pulled away from the bypass port and placed up to the port a second time. • A wet sensor can only be bypassed at initial truck hookup. • A Deadman cannot be bypassed.

Page 28: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Maintenance

Page 28.

7.1 Preventative Maintenance The Intellitrol should be inspected annually. The o-ring and corrosion pack should be replaced at this time.

7.2 Warranty

7.2.1 Intellitrol Control Unit The Intellitrol Control Unit is warranteed by Scully Signal Company ("Scully") to be free from defects in material and workmanship under normal use and service for a period of three years. Warranty covers manufacturing defects. Damage speci�cally resulting from improper use or incorrect installation is not covered.

7.2.2 General Terms All equipment returned to Scully that has a manufacturing date code that exceeds the warranty period should be accompanied by an invoice or work order that states the date of installation. Under these warranties, Scully shall be responsible only for actual loss or damage suffered and then only to the extent of Scully's invoiced price of the product. Scully shall not be liable in any case for labor charges for indirect, special, or consequential damages. Scully shall not be liable in any case for the removal and/or reinstallation of defective Scully equipment.

These warranties shall not apply to any defects or other damages to any Scully equipment caused by misuse or negligence, and this warranty shall not apply to any Scully equipment that has been altered or tampered with by anyone other than Scully factory representatives. These warranties are the only warranties, expressed or implied, upon which products are sold by Scully, and Scully makes no warranty of suitability for any particular purpose in respect to the products sold.

Scully products or parts thereof assumed to be defective by the purchaser within the stipulated warranty period should be returned to the seller, local distributor, or directly to Scully for evaluation and service. Whenever direct factory evaluation, service, or replacement is necessary, the customer must �rst, by either email or phone, obtain a Returned Material Authorization Number (RMA) from Scully Company directly. No material may be returned without an RMA number assigned to it or without proper factory authorization.

Any returns must be returned freight prepaid to: Scully Signal Company 70 Industrial Way Wilmington, MA 01887 U.S.A. Attention: Service Dept.

Returned warranty items will be repaired or replaced at the discretion of the Scully Service Department according to Scully Product Warranty Policy and the Scully Returned Materials Procedure. Any Scully items under the Scully Warranty Policy that are deemed not repairable by the Scully Service Department will be replaced at no charge or a credit issued for that item subject to the customer's request.

Page 29: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Maintenance

Page 29.

7.3 Troubleshooting Guide

The following table summarizes errors indicated via the front panel and their most likely causes. Problems covered are the: • Intellitrol Self Check failure • Unit's plug and cable assembly(s) • Vehicle trying to get a permissive signal to load at the rack. This chart and the troubleshooting guide should be consulted prior to requesting technical service help. If after consulting the chart you are unable to resolve the problem contact Scully Technical Services at 1-800 Scully and be prepared to communicate the status of the indicators on the front panel.

Warning: Certain checks may require access to the inside of the control unit to verify or change con�guration jumpers. Any activity requiring the opening of the unit should only be performed by quali�ed personnel. The area must be secured and vapor free before opening the enclosure to avoid explosion.

EN13922

INTELLITROL®

DYNAMIC

SELF-CHECKING®

1 2 4 5 6 7 83

Optic Pulse

OutCommunication

Ground

Service

Dynacheck

Authorized

Unauthorized

Vehicle Identi�cation

Standby

In

Terminal

Vehicle

Automatic & Continous Self-Checking

Compartment

Red (Non-Permissive)Main Status Indicator

Green (Permissive)Main Status Indicator

Wet / Faulty SensorIndicators

Communications Indicators

Bypass Port

Dynacheck Indicator

Ground Fault Indicator

5-Wire Optic ModeStatus Indicators

Service Indicator Vehicle Identi�cationProver Indicators (VIP)

Page 30: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Maintenance

Page 30.

Rack not permitting

@

*

#

**

Red

Non

Perm

it Ba

r

Gree

n Pe

rmit

Bar

Com

part

men

t LED

s

Optic

Out

Optic

In

Grou

nd

Serv

ice

Com

m. T

erm

inal

Com

m. V

ehic

le

Auth

oriz

ed

Unau

thor

ized

Stan

dby

Vehicle Id

OPERATING CONDITION

Assumes ground proving and VIP enabled, lights fordisabled options will always be off

Dyna

chec

k

Flashing

Flashing at Dynacheck rate (once per second)

Flashing slow (once every two seconds)

Flashing fast (twice per second)

7.3.1 Table-2: Front Panel Display Trouble Shooting Chart Table-2a: Front Panel Display Trouble Shooting Chart

On

On On

On On

On

On

On

On

@

@

@ @

@

@

Rack not permitting; No vehicle connected, vehicleconnected with faulty TIM or deadman openVehicle connected, and indicated sensor is wet orthermistor sensor still warmingNo vehicle connected and an I/O pin (1-8) of theScully connector shorted or 2-wire sensor shorted2-wire sensor open

Hard-wired output relay or vehicle connected andbypassing wet sensorVehicle connected and rack permitting, all sensorsdryVehicle connected and bypassing Ground Provingand/or VIPVehicle connected; main processor pulsing 5-wireoptic sensorsMain processor not receiving 5-wire optic pulsesback from 5-wire sensorsVehicle connected, main processor pulsing 5-wireoptic sensors and optic return being sensedVehicle not connected or vehicle connected andground proving successfulVehicle connected and ground proving fault. Eitheropen or Ground Bolt / Ground Ball shorted

Vehicle connected, Ground proving bypassed

No system error detected

System error detected

Off

Off

Off

Off

Off

Off

Off

Off

Off Off

Off

Off

-

- - - -

- - - - - - -

- - -

- - - - -

- - - - -

- - - - -

- - - - -

-- - - - -

- - - - -

- - - -

- - -

- - -

- - - -

- - - -

- - - -

- - - -

-

**

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

- - - - -

- - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

-

-

-

-

-

-

-

Page 31: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Maintenance

Page 31.

Table-2b: Front Panel Display Trouble Shooting Chart

Terminal communications line faulty

@

*

#

**

Red

Non

Perm

it Ba

r

Gree

n Pe

rmit

Bar

Com

part

men

t LED

s

Optic

Out

Optic

In

Grou

nd

Serv

ice

Com

m. T

erm

inal

Com

m. V

ehic

le

Auth

oriz

ed

Unau

thor

ized

Stan

dby

Vehicle Id

OPERATING CONDITION

Assumes ground proving and VIP enabled, lights fordisabled options will always be off

Dyna

chec

k

Flashing

Flashing at Dynacheck rate (once per second)

Flashing slow (once every two seconds)

Flashing fast (twice per second)

On

On

On

On

On

Intellitrol not communicating with terminal

Intellitrol communicating with terminal

Vehicle communications error

Vehicle not connected/not communicating

Intellitrol communicating with the vehicle

Vehicle connected, TIM good, and authorized

Vehicle connected, VIP bypassed

Vehicle connected, TIM good but not unauthorized,i.e. ID not in VIP list

Vehicle not connected, or unable to read TIMs

Intellitrol waiting for TAS command

Intellitrol operational

Unrecoverable system error occurred

No Power; front panel bad/not connected

All other displays = bad front panel or unit

Off

Off

Off Off

Off

Off

Off

Off

Off

Off

Off Off Off Off Off Off Off Off Off Off Off Off Off

Off

-

-- - - -

- - - - - - -

- -

- - - -

----

- - -

---

- - - -

- - - - -

- - - - -

-- - - - -

- - - - -

-- - - -

--- - -

--- - -

- - -- -

- - -- -

-

-

---

--

--

--

-

-

-

-

-

-

-

-

-

-

- - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

*

*

**

*

*

*

*

*

**

*

*

**

*

-

-

-

-

Page 32: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Maintenance

Page 32.

7.4 Installing Replacement Parts Warning: Opening the Intellitrol exposes Non-Intrinsically safe circuits to the atmosphere. Always assure the location is secured and is non-hazardous before opening an explosion proof housing.

The Intellitrol contains only two �eld replaceable modules. Order a replacement with the correct part number corresponding to the options purchased.

• Control Module • Front Panel display

7.4.1 Control Module Replacement Procedure • Disconnect the unit from power • Unbolt and open the Intellitrol door • Unplug all connectors, noting orientation of J1 ribbon to front panel • Remove factory grounds from TB1 cable to front panel from green J1 terminal

7.4.2 Control Module Reassembly • Inspect new module and reset jumpers to match the unit removed. While most will match particular attention should be paid to CHANNEL jumper J31 & J32 which sets 6/8 compartment mode. The jumpers are always shipped in the 8 Compartment mode and must be reset on site if 6 compartment mode is used. • Re-assemble unit in the reverse order used for removal.

Warning: The blue and black wires from the IS Barrier Heat sink assembly are an integral part to safety and MUST all be reconnected to assure continued Intrinsic Safety!

7.4.3 Front Panel Replacement • Disconnect the unit from power - Remove the front cover screws and front panel assembly - Note orientation of connector on rear of front panel - Re-assemble in reverse direction

7.5 Parts Available The following lists contain the common spare �eld replaceable parts available for the Intellitrol control unit and accessory items. Please consult the factory for any parts not mentioned below.

Page 33: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Maintenance

Page 33.

7.5.1 Table-3: List of Replacement Parts

*To order lens mask in text other than English, add: • S for Spanish • F for French • G for German • I for Italian • D for Danish

Example: 32085S = Lens Mask, Spanish Text, Over�ll & Grounding

1 Module Assembly, SIL-O 08983OSIL 08979OSIL 1 Module Assembly, SIL-OG 08983OGSIL 08979OGSIL Module Assembly, SIL-OGV 08983OGVSIL 08979OGVSIL2 Cover Bolt, M8 x 1.25 x 25mm 50005 103 Main Fuse (F1), 1A, Hi-interrupt 26373 14 Contact Fuse (F5, F8), 5A, Hi-interrupt 26372 65 Cover O-ring (gasket) 31340 16 Corrosion Inhibitor 40268 18 Lens Assembly (with 6 mounting screws) 09181 08980 19 Display Module (with backing plate) 08981 110 Display Cable Feed-through 08982 111 Lens Mounting Screw, 8-32 x 3/4 50080 612 Retaining Ring, Cover Hinge 54039 213 Text Mask (English), Over�ll and Ground 32085* 1 Text Mask (English), Over�ll, Ground and 32086* Vehicle ID

Item Description Part NumberATEX FM Qty.

1

3

2

5

4

6

10

12

9

8

11

13

Page 34: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Maintenance

Page 34.

7.5.2 Table-4: List of Accessories

08939 Bypass Key Authorizer08863 Deadman Control Switch Assembly08951 Intelliview® 2 Terminal Software09001 RS-232 to RS-485 Converter Kit (for communications)08958 SC-8OB Sculcon Junction Box with 8B Style Black Poly Plug and 6 meter (20 ft) Blue Straight Cable (for 2-wire or 5-wire sensors - 4-bayonet pins - 10 contact pins)08959 SC-8B Sculcon Junction Box with 8B Style Green Poly Plug and 6 meter (20 ft) Blue Straight Cable (for 2-wire or 5-wire sensors - 4 bayonet pins - 10 contact pins)08729 SC-8A Sculcon Junction Box with 8A Style Green Poly Plug and 9 meter (30 ft) Orange Coiled Cable (for 2-wire sensors - 2 bayonet pins - 10 contact pins)08156 SC-6A Sculcon Junction Box with 6A Style Green Poly Plug and 9 meter (30 ft) Orange Coiled Cable (for 2-wire sensors - 2 bayonet pins - 8 contact pins)08159 SC-6W Sculcon Junction Box with 6W Style Blue Poly Plug and 9 meter (30 ft) Blue Coiled Cable (for 5-wire sensors - 3 bayonet pins - 6 contact pins)

Part Number Description

Page 35: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Technical Service Hot-Line/Notes

Page 35.

Technical Service Hot-Line Scully's Technical Service Department can be reached at the corporate headquarters in Wilmington, MA U.S.A. by telephone at (617) 692-8602; by FAX at (617) 692-8620; and by email at [email protected]. If calling from within the United States, our toll free Technical Service Hot- Line Number is (800) 272-8559.

Our technical service department staff is available from 8 AM to 5 PM Eastern Standard Time to answer any questions which may arise regarding the installation, operation or service of the Scully Intellitrol and accessories.

Notes

Page 36: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Diagram Appendix

Page 36.

235.

0 M

M

FOR

I.S

. SE

NS

OR

WIR

ING

ON

LYM

25 X

1.5

(IS

O) M

ETR

IC

MO

UN

TIN

G B

OLT

CE

NTE

RS

FOR

8 M

M D

IA. B

OLT

S

177.

8 M

M

43.2

MM

181.

0 M

M

212.

8 M

M

INTR

INS

ICA

LLY

EN

TRY

SA

FE

85.8

MM

212.

8 M

M

EN

CLO

SU

RE

EA

RTH

BO

ND

ING

STU

D

Aut

omat

ic &

Con

tinuo

us S

elf-

Che

ckin

g

4

RD

ynac

heck

Op

tic P

ulse

Ser

vice

Gro

und

In

32

1

Out

R

Com

mun

icat

ion

7

Term

inal

Vehi

cle

65

8

Com

par

tmen

t

347.

7 M

M

85.8

MM

63.5

MM

FOR

PO

WE

R A

ND

CO

NTR

OL

WIR

ING

M25

X 1

.5 (I

SO

) ME

TRIC

PO

RT

63.5

MM

85.8

MM

CO

MM

UM

ICAT

ION

S W

IRIN

GFO

R A

DD

ITIO

NA

L O

UTP

UT

&M

25 X

1.5

(IS

O) M

ETR

IC P

OR

T

9.1 Dwg. No. 63038C – Intellitrol Enclosure Outline, Model Series ICC

Page 37: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Diagram Appendix

Page 37.

9.2 Dwg. No. 63038 – Intellitrol Enclosure Outline, Model Series IC

FOR

I.S

. SE

NS

OR

WIR

ING

ON

LY3/

4-14

NP

T C

ON

DU

IT P

OR

T

MO

UN

TIN

G B

OLT

CE

NTE

RS

FOR

3/8

- IN

CH

DIA

. BO

LTS

CO

MM

UM

ICAT

ION

S W

IRIN

GFO

R A

UX

. OU

TPU

TS &

3/4-

14 N

PT

CO

ND

UIT

PO

RT

3/4-

14 N

PT

CO

ND

UIT

PO

RT

PO

WE

R A

ND

CO

NTR

OL

WIR

ING

8.38

7.13

Term

inal

Out

9.25

7.00

1.70

SA

FEE

NTR

Y

INTR

INS

ICA

LLY

8.38

Vehi

cle

Aut

omat

ic &

Con

tinuo

us S

elf-

Che

ckin

g

In Gro

und

Ser

vice

Dyn

ache

ckR

R

BO

ND

ING

STU

DE

NC

LOS

UR

E E

AR

TH

3.38

2.50

Com

par

tmen

t

51

23

Op

tic P

ulse

48

67

Com

mun

icat

ion

3.3813

.69

3.38

2.50

Page 38: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Diagram Appendix

Page 38.

9.3 Dwg. No. 63039 – Sculcon Plug and Cable Assembly Outline

7.33

7.87

(200

.0 m

m

5 63 42

(186

.2 m

m)

3.94

(100

.0 m

m)

CO

ND

UIT

HU

B (C

AB

LE G

LAN

D)

Ø1.

06 (2

7 m

m) K

NO

CK

OU

T FO

R

1

3.94

(65.

5 m

m)

2.58

(100

.0 m

m)

(81.

3 m

m)

3.20

1.44

(36.

6 m

m)

Ø1.

06 (2

7 m

m) H

OLE

FO

RC

ON

DU

IT H

UB

(CA

BLE

GLA

ND

)

MO

UN

TIN

G C

EN

TER

S F

OR

#8 (4

mm

) HE

X S

OC

KE

TH

EA

D S

CR

EW

S (4

PLA

CE

S)

Page 39: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Diagram Appendix

Page 39.

9.4 Dwg. No. 61337C – Mech. Installation, Intellitrol Model Series ICC

AD

DIT

ION

AL

OU

TPU

T C

ON

TRO

L&

CO

MM

UN

ICAT

ION

S W

IRIN

G

OV

ER

FILL

PR

EV

EN

TIO

N S

YS

TEM

ON

PLU

G A

SS

EM

BLY

TO

CO

NN

EC

T TO

WIR

ING

US

ING

SE

PAR

ATE

INTR

INS

ICA

LLY

SA

FE

TYP

E-A

CA

BLE

4

Op

tic P

ulse

Ser

vice

Dyn

ache

ck

In Gro

und

1

Out2

Vehi

cle

Aut

omat

ic &

Con

tinuo

us S

elf-

Che

ckin

gR

R

Com

mun

icat

ion

Term

inal

65

34

Com

par

tmen

t

87

3

VE

HIC

LE.

2

MA

INS

PO

WE

R A

ND

OU

TPU

TC

ON

TRO

L W

IRIN

G

3

1

5. A

NY

UN

US

ED

HO

LES

IN T

HE

FLA

ME

PR

OO

F E

NC

LOS

UR

E M

US

T B

E

PLU

GG

ED

US

ING

A C

ER

TIFI

ED

FLA

ME

PR

OO

F S

TOP

PE

R P

LUG

.

AN

D T

HE

INTE

LLIT

RO

L H

OU

SIN

G A

T A

LL C

AB

LE P

OR

T E

NTR

IES

.

4. U

SE

FIB

ER

SE

ALI

NG

WA

SH

ER

S B

ETW

EE

N T

HE

CA

BLE

GLA

ND

FIT

TIN

GS

4. I

ND

US

TRIA

L C

AB

LE G

LAN

D F

ITTI

NG

.

OF

THE

INTE

LLIT

RO

L H

OU

SIN

G T

O A

VO

ID C

ON

DE

NS

ATIO

N C

HA

NN

ELI

NG

.

CA

BLE

OR

IN A

CO

ND

UIT

. NO

OTH

ER

SIG

NA

LS A

RE

TO

BE

RU

N IN

CA

BLE

JU

NC

TIO

N B

OX

MU

ST

BE

RU

N U

SIN

G D

ED

ICAT

ED

TY

PE

-A

OF

THE

INTE

LLIT

RO

L H

OU

SIN

G A

ND

TH

E S

CU

LCO

N P

LUG

AN

D

2. T

HE

INTR

INS

ICA

LLY

SA

FE W

IRIN

G B

ETW

EE

N T

HE

BO

TTO

M P

OR

T

INTE

ND

ED

TO

RE

PR

ES

EN

T C

OD

E C

OM

PLI

AN

CE

.

DE

TAIL

S S

HO

WN

AR

E F

OR

RE

FER

EN

CE

ON

LY A

ND

AR

E N

OT

RE

GU

LATI

ON

S F

OR

INS

TALL

ATIO

NS

IN H

AZ

AR

DO

US

LO

CAT

ION

S

3. M

INIM

IZE

LO

NG

VE

RTI

CA

L R

UN

S O

F C

AB

LE IN

TO T

HE

TO

P P

OR

TS

1. I

NS

TALL

ATIO

N M

US

T C

OM

PLY

WIT

H N

ATIO

NA

L A

ND

LO

CA

L

INS

TALL

ATIO

N N

OTE

S

3. F

LAM

EP

RO

OF

Exd

CA

BLE

GLA

ND

FIT

TIN

G.

THIS

CA

BLE

OR

CO

ND

UIT

.

EQ

UIP

ME

NT

SC

HE

DU

LE (T

YP

ICA

L)

2. S

CU

LCO

N P

LUG

AN

D C

AB

LE U

NIT

.

1. I

NTE

LLIT

RO

L C

ON

TRO

L U

NIT

.

SE

E N

OTE

6S

EE

NO

TE 6

6. I

F C

ON

DU

IT IS

FE

D F

RO

M O

VE

RH

EA

D S

UIT

AB

LE C

ON

DE

NS

ATIO

N T

RA

P

SH

OU

LD B

E IN

STA

LLE

D.

Page 40: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Diagram Appendix

Page 40.

9.5 Dwg. No. 61337, Mech. Installation, Intellitrol Model Series IC

CO

MM

UN

ICAT

ION

S W

IRIN

G(3

/4"

CO

ND

UIT

)

PLU

G A

SS

EM

BLY

TO

CO

NN

EC

T TO

OV

ER

FILL

PR

EV

EN

TIO

N S

YS

TEM

ON

WIR

ING

IN S

EPA

RAT

EIN

TRIN

SIC

ALL

Y S

AFE

3/4"

CO

ND

UIT

7

Op

tic P

ulse

Ser

vice

Dyn

ache

ck

Gro

und

In2 Out

1

Vehi

cle

Aut

omat

ic &

Con

tinuo

us S

elf-

Che

ckin

gR

R

6 Term

inal

Com

mun

icat

ion

Com

par

tmen

t

43

57

8

3

VE

HIC

LE.

2

MA

INS

PO

WE

R A

ND

OU

TPU

TC

ON

TRO

L W

IRIN

G (3

/4"

CO

ND

UIT

)

3

1

54

5. A

PP

LY A

NTI

SE

IZE

/ S

EA

LAN

T TO

TH

E C

ON

DU

IT T

HR

EA

DS

AT

ALL

4. M

INIM

IZE

LO

NG

VE

RTI

CA

L R

UN

S O

F C

ON

DU

IT IN

TO T

HE

TO

P C

ON

DU

IT

PO

RTS

OF

THE

INTE

LLIT

RO

L H

OU

SIN

G T

O A

VO

ID C

ON

DE

NS

ATIO

N.

THR

EA

DE

D J

OIN

TS T

O P

RE

VE

NT

WAT

ER

INFI

LTR

ATIO

N IN

TO C

ON

DU

IT.

4. E

XP

LOS

ION

PR

OO

F C

ON

DU

IT O

UTL

ET

BO

DY.

5. C

ON

DU

IT S

EA

L FI

TTIN

G W

ITH

INTE

GR

AL

DR

AIN

.

6. E

XP

LOS

ION

PR

OO

F JU

NC

TIO

N B

OX

(IF

RE

QU

IRE

D).

7. W

ATE

RTI

GH

T IN

DU

STR

IAL

EN

CLO

SU

RE

CO

ND

UIT

HU

B.

INS

TALL

ATIO

N N

OTE

S

1. S

EA

L FI

TTIN

GS

MU

ST

BE

INS

TALL

ED

WIT

HIN

18

INC

HE

S O

F

2. I

NS

TALL

ATIO

N M

US

T C

OM

PLY

WIT

H A

LL F

ED

ER

AL,

STA

TE

THE

INTE

LLIT

RO

L E

NC

LOS

UR

E.

PLU

G A

LL U

NU

SE

D C

ON

DU

IT E

NTR

IES

.

AN

D L

OC

AL

RE

GU

LATI

ON

S F

OR

INS

TALL

ATIO

NS

IN H

AZ

AR

DO

US

LOC

ATIO

NS

. DE

TAIL

S S

HO

WN

AR

E F

OR

RE

FER

EN

CE

ON

LY A

ND

AR

E N

OT

INTE

ND

ED

TO

RE

PR

ES

EN

T C

OD

E C

OM

PLI

AN

CE

.

3. T

HE

INTR

INS

ICA

LLY

SA

FE W

IRIN

G B

ETW

EE

N T

HE

BO

TTO

M C

ON

DU

IT

PO

RT

OF

THE

INTE

LLIT

RO

L H

OU

SIN

G A

ND

TH

E S

CU

LCO

N P

LUG

AN

D C

AB

LE J

UN

CTI

ON

BO

X M

US

T B

E R

UN

IN D

ED

ICAT

ED

CO

ND

UIT

.

NO

OTH

ER

CO

ND

UC

TOR

S A

RE

TO

BE

RU

N IN

TH

IS C

ON

DU

IT.

6

1. I

NTE

LLIT

RO

L C

ON

TRO

L U

NIT

.

2. S

CU

LCO

N P

LUG

AN

D C

AB

LE U

NIT

.

3. E

XP

LOS

ION

PR

OO

F C

ON

DU

IT U

NIO

N.

EQ

UIP

ME

NT

SC

HE

DU

LE (T

YP

ICA

L)

DE

AD

MA

N

Page 41: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Diagram Appendix

Page 41.

9.6 Dwg. No. 61335C – (2-Wire, Optic or Therm.) Sculcon Field Wiring Diagram

Page 42: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Diagram Appendix

Page 42.

9.7 Dwg. No. 61335 – (2-Wire, Optic or Therm.) Sculcon Field Wiring Diagram with Deadman.

Page 43: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Diagram Appendix

Page 43.

9.8 Dwg. No. 61394C – Multiple Sculcon (2-wire and 5-wire) Field Wiring Diagram

Page 44: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Diagram Appendix

Page 44.

9.9 Dwg. No. 61506 - Multi-drop Communications Field Wiring Diagram

Page 45: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Diagram Appendix

Page 45.

9.10 Dwg. No. 63040SIL – SIL Intellitrol Control Module Outline

Page 46: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Diagram Appendix

Page 46.

9.11 Dwg. No. 61290 Pg.-1 – System Diagram, FM & CSA, Intellitrol

NO

TES

:

SC

ULL

Y

IC-a

EN

CLO

SU

RE

SC

ULL

Y S

EN

SO

RS

(SE

E N

OTE

2):

SP

-TO

, SP

-TO

T

DIV

ISIO

N 1

OU

TDO

OR

AR

EA

1. T

HE

INS

TALL

ATIO

N M

US

T C

OM

PLY

WIT

H T

HE

INS

TALL

ATIO

N R

EQ

UIR

EM

EN

TS O

F TH

EC

OU

NTR

Y, S

TATE

/PR

OV

INC

E, A

ND

LO

CA

LITY

OF

US

E.

SP

-IFT

, SP

-IFT

(SS

)S

P-F

U, S

P-F

UT

EX

PLO

SIO

N-P

RO

OF

UN

SP

EC

IFIE

D A

PPA

RAT

US

:M

US

T N

OT

BE

SU

PP

LIE

DB

Y N

OR

CO

NTA

IN, U

ND

ER

N

OR

MA

L O

R A

BN

OR

MA

LC

ON

DIT

ION

S, A

SO

UR

CE

OF

PO

TEN

TIA

L, W

ITH

RE

SP

EC

TTO

EA

RTH

, IN

EX

CE

SS

OF

250

VO

LTS

RM

S O

R 2

50V

OLT

S D

C.

INTE

LLIT

RO

L S

ER

IES

SC

ULL

Y D

UM

MIE

S:

ELE

CTR

ON

IC D

UM

MY

MO

DE

L S

D-n

E (F

M O

NLY

)

ELE

CTR

ON

IC D

UM

MY

MO

DE

L S

D-n

CE

(CS

A O

NLY

)

SC

ULL

Y G

RO

UN

D B

OLT

2. T

HE

BA

SIC

SE

NS

OR

MO

DE

LS L

ISTE

D S

HA

LL IN

CLU

DE

ALL

VA

RIA

TIO

NS

OF

THE

BA

SIC

MO

DE

L A

S L

ISTE

D IN

EA

CH

SE

NS

OR

MO

DE

LS A

PP

RO

VAL

LIS

TIN

G.

}CL.

I, D

IV. 1

, GP

S. C

& D

}

}C

L. I,

DIV

. 1, G

PS

. C &

D}

CO

NTR

OL

UN

ITS

a=O

, OG

, OG

V, O

GF,

OG

VF

(NO

ELE

CTR

ON

IC C

OM

PO

NE

NTS

)JU

NC

TIO

N B

OX

(OP

TIO

NA

L)

BY

PAS

S A

UTH

OR

IZE

R(P

OR

TAB

LE)

CL.

I, D

IV. 1

, GP

S. C

& D

CL.

I, D

IV. 1

, GP

S. C

& D

(CLA

SS

IFIE

D) L

OC

ATIO

NS

" A

ND

TH

E N

ATIO

NA

L E

LEC

TRIC

AL

CO

DE

AN

SI/

NFP

A 7

0.

3. IN

TH

E U

NIT

ED

STA

TES

, TH

E IN

STA

LLAT

ION

SH

OU

LD B

E IN

AC

CO

RD

AN

CE

WIT

H

CL.

I, D

IV. 1

, GP

S. C

& D

CL.

I, D

IV. 1

, GP

S. C

& D

AN

SI/

ISA

RP

12.

6,"I

NS

TALL

ATIO

N O

F IN

TRIN

SIC

ALL

Y S

AFE

SY

STE

MS

FO

R H

AZ

AR

DO

US

CL.

I, D

IV. 1

, GP.

D}

SP

-BL,

SP

-BLU

SP

-US

TS

P-I

O, S

P-I

OT,

SP

-IO

T(S

S)

Page 47: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Diagram Appendix

Page 47.

9.12 Dwg. No. 61290 Pg.-2 – System Diagram, FM & CSA, Intellitrol

SC

ULL

Y S

EN

SO

RS

(SE

E N

OTE

2):

MO

NIT

OR

INTE

LLIC

HE

CK

SC

ULL

Y

SC

ULL

Y S

EN

SO

RS

(SE

E N

OTE

2):

DIV

ISIO

N 1

OU

TDO

OR

AR

EA

ON

BO

AR

DE

RM

ON

ITO

R

SC

ULL

Y

DIV

ISIO

N 2

OU

TDO

OR

AR

EA

DIV

ISIO

N 1

OU

TDO

OR

AR

EA

VO

LTS

DC

.

TO E

AR

TH, I

N E

XC

ES

S O

F P

OTE

NTI

AL,

WIT

H R

ES

PE

CT

CO

ND

ITIO

NS

, A S

OU

RC

E O

FN

OR

MA

L O

R A

BN

OR

MA

LB

Y N

OR

CO

NTA

IN, U

ND

ER

M

US

T N

OT

BE

SU

PP

LIE

DU

NS

PE

CIF

IED

AP

PAR

ATU

S:

250

VO

LTS

RM

S O

R 2

50O

R

GP

S C

& D

CL.

I, D

IV. 2

,

GP

S C

& D

CL.

I, D

IV. 2

,

}C

L. I,

DIV

.1, G

P. C

& D

INTE

LLIT

RO

L S

ER

IES

a=O

, OG

, OG

V, O

GF,

OG

VF

IC-a

CO

NTR

OL

UN

ITS

SC

ULL

Y

EX

PLO

SIO

N-P

RO

OF

CL.

I, D

IV. 1

, GP

S. C

& D

EN

CLO

SU

RE

JUN

CTI

ON

BO

X (O

PTI

ON

AL)

(NO

ELE

CTR

ON

IC C

OM

PO

NE

NTS

)

CL.

I, D

IV. 1

, GP

S. C

& D

(PO

RTA

BLE

)B

YPA

SS

AU

THO

RIZ

ER

(FM

ON

LY)

GP

S C

& D

CL.

I, D

IV. 2

,

MO

DU

LE (T

IM)

TRU

CK

I.D

.

CL.

I, D

IV. 1

, GP

S. C

& D

}S

P-I

O, S

P-I

OT,

SP

-IO

T(S

S)

SP

-FU

, SP

-FU

TS

P-I

FT, S

P-I

FT(S

S)

SP

-US

T

SP

-TO

, SP

-TO

T

SP

-IR

SP

-IFT

, SP

-IFT

(SS

)S

P-F

U, S

P-F

UT

Page 48: 61375 SIL Intellitrol SIL RevB

Intellitrol® - Technical Manual

Diagram Appendix

Page 48.

9.13 SIL Speci�c Information Caution: System is only operating in SIL mode when used with SIL Sensors like Scully SP-FU, SP-TO or Dynaprobes.

Table 5: Summary of the Safe Failure Fraction (SFF)S

FF =

λ S +

λ DD

= λ

- λ D

U

λ

λ

λ

42.6

80

68.

408

196

7.48

9 2

65.3

31

397.

996

207

8.57

8

λ S

37.1

27

54.

263

119

8.59

0 2

07.0

43

310.

565

128

9.98

0

λ D

5.55

3

14.

145

76

8.89

9

58.

288

8

7.43

2

788

.597

λ DD

3.

332

8.48

7

571

.339

35

.773

5

3.65

9

583

.158

λ DU

2.

221

5.65

8

199

.560

2

2.51

5

33.

773

2

07.4

39

MT

TF d

20

555.

6

8070

.5

148.

5

1958

.5

130

5.7

SFF

94

.795

91

.729

89

.959

9

1.51

4

91.

514

9

0.11

6

Inte

llitr

ol w

/o s

enso

rs

Pow

erSu

pply

Exte

nsio

nBr

d.M

ain

Brd.

Proc

esso

r1

Proc

esso

r2

Tota

l *

117

2

195.

578

140

4

348

2.57

8

139.

6

2218

.178

55.1

213

3.67

8

116

1

405.

980

13

92

268

1.98

0

137

.7

142

7.68

48.

3

13

38.2

8

1

789

.597

12

800.

597

1.9

790.

497

6.8

79

5.39

7

0

583

.158

0

583.

158

0

5

83.1

58

0

583

.158

1

208

.439

12

219

.439

1.9

209

.339

6.8

21

4.23

9

1415

5

95

12.9

60

081.

7

1

6787

.5

99.1

45 9

0.59

8

99.

145

9

3.75

6

98.

639

90

.653

87.

659

9

0.00

53

Tota

lIn

telli

trol

+ Se

nsor

Sing

leCh

anne

l

Inte

llitr

ol w

/si

ngle

5-w

irese

nsor

(SP-

FU)

Inte

llitr

ol w

/tw

elve

5-w

irese

nsor

s (S

P-FU

)

Inte

llitr

ol w

/2-

wire

sen

sors

(SP-

TO)

Inte

llitr

ol w

/Th

erm

isto

r se

nsor

s(D

ynap

robe

s)

Sing

leCh

anne

lTo

tal

Inte

llitr

ol+

Sens

ors

Sing

leCh

anne

l**

Tota

lIn

telli

trol

+ Se

nsor

s

Tota

lIn

telli

trol

+ Se

nsor

s

Sing

leCh

anne

l**

< 6

0 %

S

IL1

S

IL2

S

IL3

80 %

- <

90

%

SIL

2

SIL

3

SIL

4

90 %

- <

99

%

SIL

3

SIL

4

SIL

4

> 9

9 %

S

IL3

S

IL4

S

IL4

Hard

war

e fa

ult t

oler

ance

***

Safe

Fai

lure

Frac

tion

01

2

Tab

le 6

: Har

dw

are

safe

ty in

tegr

ity: a

rchi

tect

ural

cons

trai

nts

on t

ype

A s

afet

y-re

late

d s

ubsy

stem

s.

< 6

0 %

Not

allo

wed

S

IL1

S

IL2

80 %

- <

90

%

SIL

1

SIL

2

SIL

3

90 %

- <

99

%

SIL

2

SIL

3

SIL

4

> 9

9 %

S

IL3

S

IL4

S

IL4

Hard

war

e fa

ult t

oler

ance

***

Safe

Fai

lure

Frac

tion

01

2

Tab

le 7

: Har

dw

are

safe

ty in

tegr

ity: a

rchi

tect

ural

cons

trai

nts

on t

ype

B s

afet

y-re

late

d s

ubsy

stem

s.

* N

umb

ers

for

Pro

cess

or 1

& P

roce

ssor

2 ar

e in

clud

ed in

the

Mai

n B

rd. n

umb

er.

** A

dd

ition

al 2

-wire

sen

sors

or

ther

mis

tor

sens

ors

do

not

affe

ct t

he

calc

ulat

ions

.

***A

har

dw

are

faul

t to

lera

nce

of N

mea

ns t

hat

N+

1 co

uld

cau

se a

loss

of

the

safe

ty fu

nctio

n

Page 49: 61375 SIL Intellitrol SIL RevB

Over�ll Prevention Control Unit (with Ground Veri�cation & Vehicle Identi�cation Option)

Notes:

Page 49.

Page 50: 61375 SIL Intellitrol SIL RevB

Dynamic Self-Testing® Over�ll Prevention Systems

MaxSafety®

SYSTEMS

Scully Signal Company70 Industrial Way,Wilmington, MA 01887-3479, USA Tel: 800 272 8559 / 617 692 8600 email: [email protected]

Scully Systems Europe NVEksterveldlaan 31a2820 Bonheiden / Belgium Tel: +32 (0) 15 56 00 70 email: [email protected]

Scully UK LtdMeridian House, Unit 33,37 Road One Winsford Industrial Estate,Winsford Cheshire CW7 3QG / UK

Tel.: +44 (0) 1606 553805 email: [email protected]

61375SIL Rev BAugust 2014

For over seventy-�ve years Scully has been engineering and building products

to the highest safety and reliability standards. We design and manufacture all

of our systems under one roof to ensure complete quality control over our

manufacturing and testing operations. Scully is ISO certi�ed and all of our

products are 100% made in the U.S.A. In addition, we back up our products

with the best service in the industry. We have direct sales and service

personnel in the U.S.A., The United Kingdom, and Europe and

are represented in over 50 countries.

For more information and 24 hour technical assistance,

call Scully Signal Company at 1-800-2SCULLY (1-800-272-8559).

Scully Headquarters in Wilmington, MA U.S.A.

Copyright © 2014 Scully Signal Company. MaxSafety, Sculcon and Scully are registered

trademarks of Scully Signal Company. The names and logos of other companies mentioned

herein may be trademarkes of their respective owners. This document is for informational

purposes only. Scully makes no warranties, expressed or implied, in this document.

All Rights Reserved. Speci�cations are subject to change without notice.

Scully - Setting Standards in Safety and Dependability since 1936.