distribucion english

12
DISTRIBUTION TRANSFORMERS

Upload: korsair

Post on 13-Apr-2015

34 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Distribucion English

CORPORACION COOPERATIVAALKARGO, S. COOPAritz Bidea nº 83 Atela Auzotegia48100 Mungía (Vizcaya) - SPAINTel.:+34 (94) 674.00.04Fax: +34 (94) 674.44.17Apartado 102 / P.O BOX 102e-mail: [email protected] DISTRIBUTION TRANSFORMERS

Page 2: Distribucion English

TEST

All transformers undergo the following individual or routine tests as per IEC-76 , BS171 and UNE 20101:

• Winding resistance measurement• Check on connection elements & polarity• Transformer ratio measurement & coupling check• No load losses & no load current measurements• Load losses measurement• Short-circuit voltage measurement (main connection point)• Dielectric tests• Induced voltage test in windings• Applied voltage test in windings

On request the following type tests can also be performed:

• Heating test• Lighting impulse test• Measuring of noise level• Oil characteristics• Others

OTHER PRODUCTS IN OUR MANUFACTURINGRANGE

• Transformers in silicone (LNAN)• Cast-resin dry type transformers from 50 to 5000 kVA with high voltage class ≤ 36 kV• Medium power transformers up to 30 MVA and 72.5 kV• Earthing transformers & reactances• Impregnated dry transformers• Auto-transformers• Transformers for rectifiers• Special transformers

Note: The data and descriptions in this catalogue refer to our present design and construction techniques, and do not constitute an undertakingon our part unless confirmed as such. We reserve the right to make such modifications and improvements as may be deemed convenient withoutprior notice.

50, 100, 160, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA.

° Preferential power ratings are marked in bold print.

DISTRIBUTION TRANSFORMERS

This catalogue deals with transformers immersed in insulating fluid with natural self cooling (ONAN), three-phase, 50 - 2500 kVAfor indoor or outdoor use, 50/60 Hz, hermetically sealed.

The transformers described in this catalogue are designedand tested in accordance to European UnionHarmonisation Document HD428, UNE 21428 and IEC76 standards.

However, and by request, they can be manufacturedaccording to any other national or international standards,such us

HD-398, BS 171, NF C52.100, DIN 42.500, UNE 20.101,IEC 76

UNE 21320, UNE 48103, UNE EN 60551, UNE 20110,UNE 20145, UNE EN 50180, ETU 5201 E and UNESArecommendations. Another applicable documents are:ANSI C57, NEMA, ESI, HN, UTE.

MANUFACTURING STANDARD

GENERAL CHARACTERISTICS

RATINGS

HIGH VOLTAGEThis material is designed for voltages of ≤ 36 kV. Specific figures are not given for this parameter because of the wide variety of voltagesused. Transformers can be supplied on demand to run at two different primary voltages, the shifth between these input voltages has twobasic alternatives:• with a primary tap changer which can be switched with no load and no applied voltage• or by changing terminals under the cover.

LOW VOLTAGEThe secondary voltage under no load is allocated at 420 V, though other voltages can be supplied on demand. When usage requirestwo voltages, transformers with two simultaneous voltages can be supplied. In this case the no-load voltages are set to 420 and242 V. For the lower voltage output the power is K x Pr.

In simultaneous loads the power distribution is: P + P =Pr where: KPPPrK

= load supplied at 242 V= load supplied at 420 V= rated power= 0,75

1 2

1

2

Page 3: Distribucion English

All transformers are supplied with:

• 3 high voltage bushings• 4 or 7 low voltage bushings• 5-position tap changer on cover, workable with transformer off load• 2 lifting & tank removal eye-bolts• Filling hole with M-40 x 1.5 outside thread and threaded cover• Drainage & sampling plug at bottom of tank• 4 two-way, 90º directional wheels• 2 earthing connections at bottom with M-10 screws

BASIC EQUIPMENT

O P T I O N A L A C C E S S O R I E S

• Two-contact dial thermometer

• Terminal box

• HV plug-in bushing

• Thermostat

• LV and HV cable boxes

• Protection & control block for the followingfunctions:

• LV bar bushing

For conservator tank typetransformers:

• Two contacts Buchholz relay

• Silicagel air breather

• Magnetic level sensor with one or two contacts

• Oil Level indicator

• Others

Two-contact dial thermometer Terminal box

Protection & control block

HV plug-in bushing

LV bar bushing

Silicagel air breather Two contacts Buchholz relay

Detection of gas emissions from dielectric liquid(trip), detection of excessive increase in pressure on tank (trip),dielectric liquid temperature reading and liquid level display(adjustable alarm & trip contacts)

The connections normally used are as follows:

• For rated power levels of 160 kVA or less: Yzn11

• For rated power levels over 160 kVA: Dyn11.

As per IEC 76 and UNE 20101, in normal operating mode:

• 60º K max. in oil• 65º K average in windingsOther temperature rise levels on demand.

Transformers covered by document HD 428 (UNE 21428-1) must have one of the following oil expansion systems:

a) an external conservator tankb) an air chamber under the coverc) a hermetically sealed elastic tank

Alkargo recommends option (c), which is the one considered in this catalogue, as it has the following advantages:

VECTOR GROUP REFERENCE

INSULATION LEVELS

TEMPERATURE RISE

ADVANTAGES OF HERMETIC SEALING

As per IEC 76, BS 171 and UNE 20101 standards these areset in accordance with the highest voltage for the material,being the level immediately above the rated voltage.

1.

2.

3.

4.

5.

6.

Smaller size, as there is no need for an conservator tank or air chamber, making for easier transformer transportation and placement.

Lower overall weight.

Increased sturdiness and less risk of leaks, there being no weak points such as welds between the expansion tank and the cover, oillevel gauge, Silicagel air breather, etc.

Low maintenance due to the absence of elements such as the drier, overpressure valves and liquid level indicators.

No degradation of insulating liquid (oil) by oxidation or absorption of moisture, as there is no contact with the air. The liquid thereforeremains in ideal condition.

Better conservation of seals due to lack of contact with air, which means that they stay more flexible.

Material maximum 12 kV 17,5 kV 24 kV 36 kVadmissible voltage

Withstand voltage 28 kV 38 kV 50 kV 70 kV

Basic insolation level 75 kV 95 kV 125 kV 170 kV

Page 4: Distribucion English

K

C

E

F

L L

H

A

E

J

B

JJ

kVA

A

B

C

D

E

F

G

H

J

K

L

Kg.

l.

Kg.

50

990

720

1380

125

520

40

35

125

80

500

375

115

128

460

100

1070

720

1410

125

520

40

35

125

80

500

375

120

134

590

160

1170

720

1450

125

520

40

35

125

80

500

375

175

195

810

250

1240

870

1540

125

670

40

35

175

150

500

375

235

262

1040

400

1440

870

1590

125

670

40

35

175

150

500

375

260

290

1410

630

1580

960

1680

125

670

40

35

275

150

500

375

310

346

1670

800

1740

1040

1660

125

670

40

35

275

150

500

375

460

485

2240

1000

1860

1120

1740

125

670

40

35

325

150

500

375

490

547

2640

1250

1920

1120

1910

200

820

70

45

325

150

500

375

640

715

3330

1600

1860

1100

2110

200

820

70

45

355

200

500

375

830

927

3910

2000

2040

1160

2160

200

820

70

45

355

200

500

375

1030

1150

4850

2500

2100

1350

2210

200

1070

70

45

355

200

500

375

1170

1300

5550

GD

Highest voltage for material: 36 kV Low voltage B2: 420 V

Oriented grain, very low loss magnetic plate is used following UNE 36128. The type or class of plate is chosen on the basisguaranteed noise level and losses. The net cross section is maintained constant in limbs and yokes throughout the magnetic circuit,as a special configuration does away with the need for cross-section reducing grip bolts (section reduction).

The limbs and yokes are joined by 45º lugless joints, with complete one-piece yoke, and stacking is arranged so that eachplate profile is staggered with regard to the previous one, thus minimising the effect of the gap. The profile is stepped, with the numberof steps required to obtain the best coefficient of useful surface area.

Construction details

This winding is located next to and concentric with the magnetic circuit. Two clearly different types of wire are used depending onthe allocated current:

- Rectangular cross-section with rounded edges as per UNE 21179; or- Strips with conditioned edges.

In the former case each wire is insulated with thermal class A cellulose paper or class H enamel. Strips are used bare.

The rectangular wire winding is set up in a complete layer configuration with one or more concentric channels for cooling.The insulation between layers is always B status resin impregnated.

The width of the strip on strip type windings with conditioned edges covers the whole axial width of the coil, so that eachturn is a layer of winding. As the strip is wound a layer of type B resin impregnated paper is wound with it. This polymerises duringthe drying cycle, giving the winding the strength to withstand the mechanical stresses entailed by short circuits as per IEC - 76 andBS 171 standards.

This is wrapped around the low voltage winding to lie concentric with it, separated by an insulation structure giving the levelof insulation desired.

The conductors used are of two types:• circular cross-section wire• rectangular cross section strips.

The conductors are insulated with thermal class H enamel. The rectangular section wires or strips have thermal class A paperor thermal class H enamel. With both types of wire, the winding configuration is anti-resonant in one section, making it highly resistantto ray type pulse waves.

The insulation between layers is resin impregnated, polymerising during drying to give the winding the strength to withstandthe mechanical stresses entailed by short circuits.

I- MAGNETIC CIRCUIT

II- LOW VOLTAGE WINDING

III- HIGH VOLTAGE WINDING

Rated Power

Lenght (mm)

Width (mm)

Height (mm)

Wheels diameter (mm)

1Distance between wheel axis (mm)

Wheels width (mm)

Wheel free deep (mm)

L.V. bushing height (mm)

Distance between L.V. bushing axis (mm)

H.V. bushing height (mm)

Distance between H.V. bushing axis (mm)

Insolation fluid weight

Insolation fluid volume

Total weight

Page 5: Distribucion English

50

870

720

1270

125

520

40

35

125

80

385

275

115

128

460

100

950

720

1310

125

520

40

35

125

80

385

275

120

134

590

160

1170

720

1350

125

520

40

35

125

80

385

275

175

195

810

250

1240

870

1440

125

670

40

35

175

150

385

275

235

262

1040

400

1440

870

1490

125

670

40

35

175

150

385

275

260

290

1410

630

1540

960

1490

125

670

40

35

275

150

385

275

310

346

1670

800

1740

1040

1560

125

670

40

35

275

150

385

275

460

485

2240

1000

1860

1120

1640

125

670

40

35

325

150

385

275

490

547

2640

1250

1920

1120

1810

200

820

70

45

325

150

385

275

640

715

3330

1600

1860

1100

1990

200

820

70

45

355

200

385

275

830

927

3910

2000

2040

1160

2005

200

820

70

45

355

200

385

275

1030

1150

4850

2500

2100

1350

2055

200

1070

70

45

355

200

385

275

1170

1300

5500

kVA

A

B

C

D

E

F

G

H

J

K

L

Kg.

l.

Kg.

-The purpose of the fixing structureis to hold the windings in the correct axialposition with regard to the magnetic circuit,and to exert the pressure required on thatcircuit to minimise noise level. It comprisesfour beams: two made of layered wood withphenol resin at the top cylinder head and twomade of steel at the bottom one. Grippingfor height and thickness is via threaded steelrods which help to adjust the cover height.Distances between windings and tank aremaintained by two guide feet attached to thebottom beams.

-The tap changer, whose control ison the cover, is set between the cover andthe top of the magnetic circuit. It is a racktype unit with a clogged pinion which actsdirectly on the control shaft.

-The cover is made of plain steelplate reinforced by sections which also serveto attach the vertical rods which raise therest of the components. The cover isconsiderably bigger than the tank frame toprevent rain water getting into the sealseating area.

-The high and low voltage coverbushings are fitted for outdoor service. Ondemand, and according to the rated current,low voltage bushings are mounted on ananti-magnetic plate.

Highest voltage for material: ≤ 24 kV

Low voltage B2: 420 V

The data in the tables are approximate, and correspond to hermetically sealed oil transformers with electrical characteristicsas per the above tables. They are not valid for other loss levels, double voltages, different insulation voltages, silicone

transformers, etc. In these cases, please consult us.

DIMENSIONES & WEIGHTS

Rated Power

Lenght (mm)

Width (mm)

Height (mm)

Wheels diameter (mm)

1Distance between wheel axis (mm)

Wheels width (mm)

Wheel free deep (mm)

L.V. bushing height (mm)

Distance between L.V. bushing axis (mm)

H.V. bushing height (mm)

Distance between H.V. bushing axis (mm)

Insolation fluid weight

Insolation fluid volume

Total weight

The distribution transformer tank is elastic, enabling it to absorb the increase in volume of insulating fluid as it heats updue to the transformer operation without experiment permanent deformations. It comprises the following components:

• supporting frames• base• cooling fins• outer frame

- The supporting frames are welded to the base in a continuous, watertight bead to prevent rusting. They have holes forattaching wheel heads and dragging the transformer.

- The base is bath shaped, with earth connections and a drainage device on the sides.- The cooling fins are the fundamental part of the tank: they form the corrugated side walls and give it the required elasticity.

They are made of cold-rolled steel plate between 1 and 5 mm thick, bent without drawing. Elasticity is obtained by a suitablecombination of height, depth, plate thickness and resulting internal pressure.

- The outer frame of the tank is made of L-section steel, welded to the top of the corrugated side walls. The top of this framehouses the pressure limiters for the seal and bear the holes for the cover/tank fixing screws.

IV- ACTIVE PART

V- TANK

This is the name given to the set of elements which can be removed from the tank of the transformer. Apart from the core and windings,the main elements are:

• fixing and guide structure• tap changer• cover• cover bushing

Page 6: Distribucion English

100

320

1750

4

97,97

98,29

98,51

98,31

97,48

97,87

98,14

97,90

1,81

3,58

56

160

460

2350

4

98,27

98,53

98,70

98,51

97,85

98,17

98,38

98,14

1,54

3,43

59

250

650

3250

4

98,46

98,70

98,84

98,65

98,09

98,37

98,56

98,32

1,37

3,33

62

400

930

4600

4

98,64

98,84

98,98

98,80

98,30

98,56

98,72

98,50

1,22

3,25

65

630

1300

6500

4

98,78

98,96

99,07

98,93

98,47

98,70

98,84

98,66

1,10

3,18

67

800

1550

8100

6

98,81

99,00

99,12

98,98

98,52

98,75

98,91

98,73

1,18

4,44

68

1000

1700

10500

6

98,79

99,00

99,14

99,07

98,50

98,75

98,93

98,84

1,22

4,47

68

1250

2130

13500

6

98,77

98,97

99,13

99,06

98,46

98,72

98,91

98,82

1,25

4,49

70

2000

3100

20200

6

98,84

99,04

99,18

99,14

98,56

98,80

98,98

98,92

1,18

4,44

73

2500

3800

26500

6

98,80

99,01

99,18

99,13

98,51

98,77

98,97

98,92

1,23

4,48

76

1600

2600

17000

6

98,79

99,00

99,16

99,09

98,50

98,76

98,95

98,87

1,23

4,48

71

50

190

1100

4

97,48

97,89

98,17

97,97

96,88

97,37

97,73

97,48

2,26

3,77

52

50

230

1250

4,5

97,13

97,57

97,88

97,59

96,43

96,98

97,36

97,01

2,57

426

52

100

380

1950

4,5

97,72

98,07

98,29

98,03

97,17

97,60

97,88

97,55

2,03

4,02

56

160

520

2550

4,5

98,12

98,39

98,57

98,33

97,66

98,00

98,21

97,92

1,68

3,83

59

250

780

3500

4,5

98,32

98,56

98,70

98,43

97,91

98,20

98,38

98,04

1,49

3,72

62

400

1120

4900

4,5

98,51

98,72

98,84

98,59

98,15

98,41

98,55

98,25

1,32

3,62

65

630

1450

6650

4,5

98,73

98,91

99,02

98,83

98,41

98,64

98,78

98,54

1,16

3,51

67

800

1700

8500

6

98,75

98,94

99,06

98,90

98,44

98,67

98,83

98,62

1,23

4,48

68

1000

2000

10500

6

98,77

98,96

99,08

98,95

98,46

98,70

98,86

98,69

1,22

4,47

68

1250

2360

13500

6

98,75

98,95

99,09

98,99

98,44

98,69

98,86

98,73

1,25

4,49

70

1600

2800

17000

6

98,78

98,98

99,12

99,04

98,47

98,72

98,90

98,81

1,23

4,48

71

2000

3300

20200

6

98,83

99,03

99,16

99,10

98,55

98,78

98,95

98,87

1,18

4,44

73

2500

4100

26500

6

98,78

99,00

99,16

99,09

98,50

98,76

98,95

98,86

1,23

4,48

76

ELECTRICAL CHARACTERISTICS

The two tables below indicate the guaranteed rated figures as per document HD 428, UNE 21428-1 (1996) and IEC-76 standards.These figures are valid for a single secondary voltage, even if there is more than one primary voltage.

Highest voltage for material: ≤ 24 kV

Low voltage B2: 420 V

Highest voltage for material: 36 kV

Low voltage B2: 420 V

F.L. = Full Load

Rated Power (kVA)

No load losses (Wo)

Load losses (Wc) at 75°C

Short-circuit voltage (%) at 75°C

Efficiency (%), cos �=1 4/4 F.L.

3/4 F.L.

2/4 F.L.

1/4 F.L.

Efficiency (%), cos �=0,8 4/4F.L.

3/4 F.L.

4/4 F.L.

1/4 F.L.

Regulation voltage (%) . cos �=1

Regulation voltage (%) . cos �=0,8

Lw= Acoustic pressure level dB(A)

F.L. = Full Load

Rated Power (kVA)

No load losses (Wo)

Load losses (Wc) at 75°C

Short-circuit voltage (%) at 75°C

Efficiency (%), cos �=1 4/4 F.L.

3/4 F.L.

2/4 F.L.

1/4 F.L.

Efficiency (%), cos �=0,8 4/4F.L.

3/4 F.L.

4/4 F.L.

1/4 F.L.

Regulation voltage (%) . cos �=1

Regulation voltage (%) . cos �=0,8

Lw= Acoustic pressure level dB(A)

Page 7: Distribucion English

100

320

1750

4

97,97

98,29

98,51

98,31

97,48

97,87

98,14

97,90

1,81

3,58

56

160

460

2350

4

98,27

98,53

98,70

98,51

97,85

98,17

98,38

98,14

1,54

3,43

59

250

650

3250

4

98,46

98,70

98,84

98,65

98,09

98,37

98,56

98,32

1,37

3,33

62

400

930

4600

4

98,64

98,84

98,98

98,80

98,30

98,56

98,72

98,50

1,22

3,25

65

630

1300

6500

4

98,78

98,96

99,07

98,93

98,47

98,70

98,84

98,66

1,10

3,18

67

800

1550

8100

6

98,81

99,00

99,12

98,98

98,52

98,75

98,91

98,73

1,18

4,44

68

1000

1700

10500

6

98,79

99,00

99,14

99,07

98,50

98,75

98,93

98,84

1,22

4,47

68

1250

2130

13500

6

98,77

98,97

99,13

99,06

98,46

98,72

98,91

98,82

1,25

4,49

70

2000

3100

20200

6

98,84

99,04

99,18

99,14

98,56

98,80

98,98

98,92

1,18

4,44

73

2500

3800

26500

6

98,80

99,01

99,18

99,13

98,51

98,77

98,97

98,92

1,23

4,48

76

1600

2600

17000

6

98,79

99,00

99,16

99,09

98,50

98,76

98,95

98,87

1,23

4,48

71

50

190

1100

4

97,48

97,89

98,17

97,97

96,88

97,37

97,73

97,48

2,26

3,77

52

50

230

1250

4,5

97,13

97,57

97,88

97,59

96,43

96,98

97,36

97,01

2,57

426

52

100

380

1950

4,5

97,72

98,07

98,29

98,03

97,17

97,60

97,88

97,55

2,03

4,02

56

160

520

2550

4,5

98,12

98,39

98,57

98,33

97,66

98,00

98,21

97,92

1,68

3,83

59

250

780

3500

4,5

98,32

98,56

98,70

98,43

97,91

98,20

98,38

98,04

1,49

3,72

62

400

1120

4900

4,5

98,51

98,72

98,84

98,59

98,15

98,41

98,55

98,25

1,32

3,62

65

630

1450

6650

4,5

98,73

98,91

99,02

98,83

98,41

98,64

98,78

98,54

1,16

3,51

67

800

1700

8500

6

98,75

98,94

99,06

98,90

98,44

98,67

98,83

98,62

1,23

4,48

68

1000

2000

10500

6

98,77

98,96

99,08

98,95

98,46

98,70

98,86

98,69

1,22

4,47

68

1250

2360

13500

6

98,75

98,95

99,09

98,99

98,44

98,69

98,86

98,73

1,25

4,49

70

1600

2800

17000

6

98,78

98,98

99,12

99,04

98,47

98,72

98,90

98,81

1,23

4,48

71

2000

3300

20200

6

98,83

99,03

99,16

99,10

98,55

98,78

98,95

98,87

1,18

4,44

73

2500

4100

26500

6

98,78

99,00

99,16

99,09

98,50

98,76

98,95

98,86

1,23

4,48

76

ELECTRICAL CHARACTERISTICS

The two tables below indicate the guaranteed rated figures as per document HD 428, UNE 21428-1 (1996) and IEC-76 standards.These figures are valid for a single secondary voltage, even if there is more than one primary voltage.

Highest voltage for material: ≤ 24 kV

Low voltage B2: 420 V

Highest voltage for material: 36 kV

Low voltage B2: 420 V

F.L. = Full Load

Rated Power (kVA)

No load losses (Wo)

Load losses (Wc) at 75°C

Short-circuit voltage (%) at 75°C

Efficiency (%), cos �=1 4/4 F.L.

3/4 F.L.

2/4 F.L.

1/4 F.L.

Efficiency (%), cos �=0,8 4/4F.L.

3/4 F.L.

4/4 F.L.

1/4 F.L.

Regulation voltage (%) . cos �=1

Regulation voltage (%) . cos �=0,8

Lw= Acoustic pressure level dB(A)

F.L. = Full Load

Rated Power (kVA)

No load losses (Wo)

Load losses (Wc) at 75°C

Short-circuit voltage (%) at 75°C

Efficiency (%), cos �=1 4/4 F.L.

3/4 F.L.

2/4 F.L.

1/4 F.L.

Efficiency (%), cos �=0,8 4/4F.L.

3/4 F.L.

4/4 F.L.

1/4 F.L.

Regulation voltage (%) . cos �=1

Regulation voltage (%) . cos �=0,8

Lw= Acoustic pressure level dB(A)

Page 8: Distribucion English

50

870

720

1270

125

520

40

35

125

80

385

275

115

128

460

100

950

720

1310

125

520

40

35

125

80

385

275

120

134

590

160

1170

720

1350

125

520

40

35

125

80

385

275

175

195

810

250

1240

870

1440

125

670

40

35

175

150

385

275

235

262

1040

400

1440

870

1490

125

670

40

35

175

150

385

275

260

290

1410

630

1540

960

1490

125

670

40

35

275

150

385

275

310

346

1670

800

1740

1040

1560

125

670

40

35

275

150

385

275

460

485

2240

1000

1860

1120

1640

125

670

40

35

325

150

385

275

490

547

2640

1250

1920

1120

1810

200

820

70

45

325

150

385

275

640

715

3330

1600

1860

1100

1990

200

820

70

45

355

200

385

275

830

927

3910

2000

2040

1160

2005

200

820

70

45

355

200

385

275

1030

1150

4850

2500

2100

1350

2055

200

1070

70

45

355

200

385

275

1170

1300

5500

kVA

A

B

C

D

E

F

G

H

J

K

L

Kg.

l.

Kg.

-The purpose of the fixing structureis to hold the windings in the correct axialposition with regard to the magnetic circuit,and to exert the pressure required on thatcircuit to minimise noise level. It comprisesfour beams: two made of layered wood withphenol resin at the top cylinder head and twomade of steel at the bottom one. Grippingfor height and thickness is via threaded steelrods which help to adjust the cover height.Distances between windings and tank aremaintained by two guide feet attached to thebottom beams.

-The tap changer, whose control ison the cover, is set between the cover andthe top of the magnetic circuit. It is a racktype unit with a clogged pinion which actsdirectly on the control shaft.

-The cover is made of plain steelplate reinforced by sections which also serveto attach the vertical rods which raise therest of the components. The cover isconsiderably bigger than the tank frame toprevent rain water getting into the sealseating area.

-The high and low voltage coverbushings are fitted for outdoor service. Ondemand, and according to the rated current,low voltage bushings are mounted on ananti-magnetic plate.

Highest voltage for material: ≤ 24 kV

Low voltage B2: 420 V

The data in the tables are approximate, and correspond to hermetically sealed oil transformers with electrical characteristicsas per the above tables. They are not valid for other loss levels, double voltages, different insulation voltages, silicone

transformers, etc. In these cases, please consult us.

DIMENSIONES & WEIGHTS

Rated Power

Lenght (mm)

Width (mm)

Height (mm)

Wheels diameter (mm)

1Distance between wheel axis (mm)

Wheels width (mm)

Wheel free deep (mm)

L.V. bushing height (mm)

Distance between L.V. bushing axis (mm)

H.V. bushing height (mm)

Distance between H.V. bushing axis (mm)

Insolation fluid weight

Insolation fluid volume

Total weight

The distribution transformer tank is elastic, enabling it to absorb the increase in volume of insulating fluid as it heats updue to the transformer operation without experiment permanent deformations. It comprises the following components:

• supporting frames• base• cooling fins• outer frame

- The supporting frames are welded to the base in a continuous, watertight bead to prevent rusting. They have holes forattaching wheel heads and dragging the transformer.

- The base is bath shaped, with earth connections and a drainage device on the sides.- The cooling fins are the fundamental part of the tank: they form the corrugated side walls and give it the required elasticity.

They are made of cold-rolled steel plate between 1 and 5 mm thick, bent without drawing. Elasticity is obtained by a suitablecombination of height, depth, plate thickness and resulting internal pressure.

- The outer frame of the tank is made of L-section steel, welded to the top of the corrugated side walls. The top of this framehouses the pressure limiters for the seal and bear the holes for the cover/tank fixing screws.

IV- ACTIVE PART

V- TANK

This is the name given to the set of elements which can be removed from the tank of the transformer. Apart from the core and windings,the main elements are:

• fixing and guide structure• tap changer• cover• cover bushing

Page 9: Distribucion English

K

C

E

F

L L

H

A

E

J

B

JJ

kVA

A

B

C

D

E

F

G

H

J

K

L

Kg.

l.

Kg.

50

990

720

1380

125

520

40

35

125

80

500

375

115

128

460

100

1070

720

1410

125

520

40

35

125

80

500

375

120

134

590

160

1170

720

1450

125

520

40

35

125

80

500

375

175

195

810

250

1240

870

1540

125

670

40

35

175

150

500

375

235

262

1040

400

1440

870

1590

125

670

40

35

175

150

500

375

260

290

1410

630

1580

960

1680

125

670

40

35

275

150

500

375

310

346

1670

800

1740

1040

1660

125

670

40

35

275

150

500

375

460

485

2240

1000

1860

1120

1740

125

670

40

35

325

150

500

375

490

547

2640

1250

1920

1120

1910

200

820

70

45

325

150

500

375

640

715

3330

1600

1860

1100

2110

200

820

70

45

355

200

500

375

830

927

3910

2000

2040

1160

2160

200

820

70

45

355

200

500

375

1030

1150

4850

2500

2100

1350

2210

200

1070

70

45

355

200

500

375

1170

1300

5550

GD

Highest voltage for material: 36 kV Low voltage B2: 420 V

Oriented grain, very low loss magnetic plate is used following UNE 36128. The type or class of plate is chosen on the basisguaranteed noise level and losses. The net cross section is maintained constant in limbs and yokes throughout the magnetic circuit,as a special configuration does away with the need for cross-section reducing grip bolts (section reduction).

The limbs and yokes are joined by 45º lugless joints, with complete one-piece yoke, and stacking is arranged so that eachplate profile is staggered with regard to the previous one, thus minimising the effect of the gap. The profile is stepped, with the numberof steps required to obtain the best coefficient of useful surface area.

Construction details

This winding is located next to and concentric with the magnetic circuit. Two clearly different types of wire are used depending onthe allocated current:

- Rectangular cross-section with rounded edges as per UNE 21179; or- Strips with conditioned edges.

In the former case each wire is insulated with thermal class A cellulose paper or class H enamel. Strips are used bare.

The rectangular wire winding is set up in a complete layer configuration with one or more concentric channels for cooling.The insulation between layers is always B status resin impregnated.

The width of the strip on strip type windings with conditioned edges covers the whole axial width of the coil, so that eachturn is a layer of winding. As the strip is wound a layer of type B resin impregnated paper is wound with it. This polymerises duringthe drying cycle, giving the winding the strength to withstand the mechanical stresses entailed by short circuits as per IEC - 76 andBS 171 standards.

This is wrapped around the low voltage winding to lie concentric with it, separated by an insulation structure giving the levelof insulation desired.

The conductors used are of two types:• circular cross-section wire• rectangular cross section strips.

The conductors are insulated with thermal class H enamel. The rectangular section wires or strips have thermal class A paperor thermal class H enamel. With both types of wire, the winding configuration is anti-resonant in one section, making it highly resistantto ray type pulse waves.

The insulation between layers is resin impregnated, polymerising during drying to give the winding the strength to withstandthe mechanical stresses entailed by short circuits.

I- MAGNETIC CIRCUIT

II- LOW VOLTAGE WINDING

III- HIGH VOLTAGE WINDING

Rated Power

Lenght (mm)

Width (mm)

Height (mm)

Wheels diameter (mm)

1Distance between wheel axis (mm)

Wheels width (mm)

Wheel free deep (mm)

L.V. bushing height (mm)

Distance between L.V. bushing axis (mm)

H.V. bushing height (mm)

Distance between H.V. bushing axis (mm)

Insolation fluid weight

Insolation fluid volume

Total weight

Page 10: Distribucion English

All transformers are supplied with:

• 3 high voltage bushings• 4 or 7 low voltage bushings• 5-position tap changer on cover, workable with transformer off load• 2 lifting & tank removal eye-bolts• Filling hole with M-40 x 1.5 outside thread and threaded cover• Drainage & sampling plug at bottom of tank• 4 two-way, 90º directional wheels• 2 earthing connections at bottom with M-10 screws

BASIC EQUIPMENT

O P T I O N A L A C C E S S O R I E S

• Two-contact dial thermometer

• Terminal box

• HV plug-in bushing

• Thermostat

• LV and HV cable boxes

• Protection & control block for the followingfunctions:

• LV bar bushing

For conservator tank typetransformers:

• Two contacts Buchholz relay

• Silicagel air breather

• Magnetic level sensor with one or two contacts

• Oil Level indicator

• Others

Two-contact dial thermometer Terminal box

Protection & control block

HV plug-in bushing

LV bar bushing

Silicagel air breather Two contacts Buchholz relay

Detection of gas emissions from dielectric liquid(trip), detection of excessive increase in pressure on tank (trip),dielectric liquid temperature reading and liquid level display(adjustable alarm & trip contacts)

The connections normally used are as follows:

• For rated power levels of 160 kVA or less: Yzn11

• For rated power levels over 160 kVA: Dyn11.

As per IEC 76 and UNE 20101, in normal operating mode:

• 60º K max. in oil• 65º K average in windingsOther temperature rise levels on demand.

Transformers covered by document HD 428 (UNE 21428-1) must have one of the following oil expansion systems:

a) an external conservator tankb) an air chamber under the coverc) a hermetically sealed elastic tank

Alkargo recommends option (c), which is the one considered in this catalogue, as it has the following advantages:

VECTOR GROUP REFERENCE

INSULATION LEVELS

TEMPERATURE RISE

ADVANTAGES OF HERMETIC SEALING

As per IEC 76, BS 171 and UNE 20101 standards these areset in accordance with the highest voltage for the material,being the level immediately above the rated voltage.

1.

2.

3.

4.

5.

6.

Smaller size, as there is no need for an conservator tank or air chamber, making for easier transformer transportation and placement.

Lower overall weight.

Increased sturdiness and less risk of leaks, there being no weak points such as welds between the expansion tank and the cover, oillevel gauge, Silicagel air breather, etc.

Low maintenance due to the absence of elements such as the drier, overpressure valves and liquid level indicators.

No degradation of insulating liquid (oil) by oxidation or absorption of moisture, as there is no contact with the air. The liquid thereforeremains in ideal condition.

Better conservation of seals due to lack of contact with air, which means that they stay more flexible.

Material maximum 12 kV 17,5 kV 24 kV 36 kVadmissible voltage

Withstand voltage 28 kV 38 kV 50 kV 70 kV

Basic insolation level 75 kV 95 kV 125 kV 170 kV

Page 11: Distribucion English

TEST

All transformers undergo the following individual or routine tests as per IEC-76 , BS171 and UNE 20101:

• Winding resistance measurement• Check on connection elements & polarity• Transformer ratio measurement & coupling check• No load losses & no load current measurements• Load losses measurement• Short-circuit voltage measurement (main connection point)• Dielectric tests• Induced voltage test in windings• Applied voltage test in windings

On request the following type tests can also be performed:

• Heating test• Lighting impulse test• Measuring of noise level• Oil characteristics• Others

OTHER PRODUCTS IN OUR MANUFACTURINGRANGE

• Transformers in silicone (LNAN)• Cast-resin dry type transformers from 50 to 5000 kVA with high voltage class ≤ 36 kV• Medium power transformers up to 30 MVA and 72.5 kV• Earthing transformers & reactances• Impregnated dry transformers• Auto-transformers• Transformers for rectifiers• Special transformers

Note: The data and descriptions in this catalogue refer to our present design and construction techniques, and do not constitute an undertakingon our part unless confirmed as such. We reserve the right to make such modifications and improvements as may be deemed convenient withoutprior notice.

50, 100, 160, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA.

° Preferential power ratings are marked in bold print.

DISTRIBUTION TRANSFORMERS

This catalogue deals with transformers immersed in insulating fluid with natural self cooling (ONAN), three-phase, 50 - 2500 kVAfor indoor or outdoor use, 50/60 Hz, hermetically sealed.

The transformers described in this catalogue are designedand tested in accordance to European UnionHarmonisation Document HD428, UNE 21428 and IEC76 standards.

However, and by request, they can be manufacturedaccording to any other national or international standards,such us

HD-398, BS 171, NF C52.100, DIN 42.500, UNE 20.101,IEC 76

UNE 21320, UNE 48103, UNE EN 60551, UNE 20110,UNE 20145, UNE EN 50180, ETU 5201 E and UNESArecommendations. Another applicable documents are:ANSI C57, NEMA, ESI, HN, UTE.

MANUFACTURING STANDARD

GENERAL CHARACTERISTICS

RATINGS

HIGH VOLTAGEThis material is designed for voltages of ≤ 36 kV. Specific figures are not given for this parameter because of the wide variety of voltagesused. Transformers can be supplied on demand to run at two different primary voltages, the shifth between these input voltages has twobasic alternatives:• with a primary tap changer which can be switched with no load and no applied voltage• or by changing terminals under the cover.

LOW VOLTAGEThe secondary voltage under no load is allocated at 420 V, though other voltages can be supplied on demand. When usage requirestwo voltages, transformers with two simultaneous voltages can be supplied. In this case the no-load voltages are set to 420 and242 V. For the lower voltage output the power is K x Pr.

In simultaneous loads the power distribution is: P + P =Pr where: KPPPrK

= load supplied at 242 V= load supplied at 420 V= rated power= 0,75

1 2

1

2

Page 12: Distribucion English

CORPORACION COOPERATIVAALKARGO, S. COOPAritz Bidea nº 83 Atela Auzotegia48100 Mungía (Vizcaya) - SPAINTel.:+34 (94) 674.00.04Fax: +34 (94) 674.44.17Apartado 102 / P.O BOX 102e-mail: [email protected] DISTRIBUTION TRANSFORMERS