morsettiera misura

5
L1 L2 L3 N R S  T N 1  2 R RR  S  SS  T  TT  3  N  RATED VOLTAGES Test block unit  600V T erminal Block 800V Jumper plugs 600V CAT IV RATED CONNECTION CAPACITY Test block unit  tted w ith ERB8-C6 cover  1,5...6 mm² Maximum clampling capacity of terminal block 16 mm²  2x6 mm² CURRENT RATINGS Perpendicular plug connections (T=-5°C..30°C) 32 A Perpendicular plug connections (T=-5°C..60°C) 14 A Longitudinal line of Terminal block 76 A 549265 END10E-6I-4T-EPI Endesa 549206 UF 10E-6I-4T-EPI Unión Fenosa 54920 5 ID 10E-6I-4T -EPI Iberdrola 549207 VSG 10E-6I-4T-EPI Viesgo 549208 HC 10E-6I-4T-EPI Hidrocantábrico 549244 REE 10E-6I-4T-EPI Red Eléctrica de Es paña Shipment details: Weight: 516 g Packaging : 1 Un. Shipping box: 20 Un. Code Reference Specications Measuring category IV is for measurements made at the origin of low voltage instalation. Environment testing conditions: relative humidity 80%, sea level elevation 2000 m, pollution degree 2. Current limits as per environment temperature:  - temperature -5 ºC ..+30 ºC current 32A, - temperature -5 ºC ..+40 ºC current 24A, - temperature -5 ºC ..+60 ºC current 14A, Class II DOUBLE INSULATION fully protected plugs Uimp Impulse rated Voltage 8KV . HAND HELD PLUGGING CONNECTIONS INDIRECT MEASURING KWH METER TEST BLOCK with removable (jumper plugs) perpendicular disconnections Terminal block RB8 (without partition) 1 T erminal block RB8-R (with right partition) 3 T erminal block RB8-RL (with dual partition) 6 Jumper plug ECD600-2P 3 EN 60715 TH35-7.5 rail (128mm) 1 Multifunction end plate, stopper, panel xing and seal device 2 Marking strip 1 Sealable and screwless transparent cover IP40 - IK08 1 Self drilling xing screws 2 Components SPECIFICATIONS ORDERING DATA D V E 800V 16mm² 76A EN 60947-7-1 For protected Testing Plugs as per EN 61010-031 10E 6I- 4T -EPI

Upload: remotectrl

Post on 02-Mar-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Morsettiera misura

7/26/2019 Morsettiera misura

http://slidepdf.com/reader/full/morsettiera-misura 1/4

L1

L2

L3

N

R

S

 T

N

1   2R RR   S   SS   T   TT   3   N

 RATED VOLTAGES

Test block unit  600V

Terminal Block 800VJumper plugs 600V CAT IV

RATED CONNECTION CAPACITY

Test block unit fi tted w ith ERB8-C6 cover   1,5...6 mm²

Maximum clampling capacity of terminal block 16 mm²

  2x6 mm²

CURRENT RATINGSPerpendicular plug connections (T=-5°C..30°C) 32 A

Perpendicular plug connections (T=-5°C..60°C) 14 A

Longitudinal line of Terminal block 76 A

549265 END 10E-6I-4T-EPI Endesa549206 UF 10E-6I-4T-EPI Unión Fenosa

549205 ID 10E-6I-4T-EPI Iberdrola

549207 VSG 10E-6I-4T-EPI Viesgo

549208 HC 10E-6I-4T-EPI Hidrocantábrico

549244 REE 10E-6I-4T-EPI Red Eléctrica de EspañaShipment details:

Weight: 516 g Packaging : 1 Un. Shipping box: 20 Un.

Code Reference  Specifications

Measuring category IV is for measurements made at the origin of

low voltage instalation.

Environment testing conditions: relative humidity 80%, sea level

elevation 2000 m, pollution degree 2.Current limits as per environment temperature:

  - temperature -5 ºC ..+30 ºC current 32A,

- temperature -5 ºC ..+40 ºC current 24A,- temperature -5 ºC ..+60 ºC current 14A,

Class II DOUBLE INSULATION fully protected plugs

Uimp Impulse rated Voltage 8KV.

HAND HELD PLUGGING CONNECTIONS

INDIRECT MEASURING

KWH METER TEST BLOCK

with removable (jumper plugs) perpendicular disconnections

Terminal block RB8 (without partition) 1Terminal block RB8-R (with right partition) 3Terminal block RB8-RL (with dual partition) 6Jumper plug ECD600-2P 3EN 60715 TH35-7.5 rail (128mm) 1Multifunction end plate, stopper, panel fixing and seal device  2Marking strip 1Sealable and screwless transparent cover IP40 - IK08 1Self drilling fixing screws 2

Components

SPECIFICATIONS

ORDERING DATA

DVE

800V 16mm² 76AEN 60947-7-1

For protected Testing Plugs as per EN 61010-031

10E 6I-4T-EPI

Page 2: Morsettiera misura

7/26/2019 Morsettiera misura

http://slidepdf.com/reader/full/morsettiera-misura 2/4

L1

L2

L3

N

R

S

 T

N

7   81 2   3   4   5   6   9   NL1 L2   L3

Terminal block RB8-SS P2 (with perpendicular disconnector) 3Terminal block RB8-P1 (with longitudinal and perpendicular disconnector) 3Terminal block RB8 (with longitudinal disconnector) 7EN 60715 TH35-7.5 rail (160mm) 1Multifunction end plate, stopper, panel fixing and seal device 2RMD Marking strip 1Sealable and screwless transparent cover IP40 - IK08 1Self drilling fixing screws 2

Components

 RATED VOLTAGESTest block unit  600V

Terminal Block 800V

Jumper plugs 600V CAT IV

RATED CONNECTION CAPACITYTest block unit fi tted with ERB8-C6 cover 1,5...6 mm²

Maximum clampling capacity of terminal block 16 mm²

  2x6 mm²

CURRENT RATINGS

Perpendicular plug connections (T=-5°C..30°C) 32 A

Perpendicular plug connections (T=-5°C..60°C) 14 ALongitudinal line of Terminal block 76 A

549291 UNB 13E 9I-4T EPI -

Shipping details:Weight: 632 g Packaging : 1 Un. Shipping box: 20 Un.

Code Reference  Specifications

Measuring category IV is for measurements made at the origin of

low voltage instalation.Environment testing conditions: relative humidity 80%, sea level

elevation 2000 m, pollution degree 2.

Current limits as per environment temperature:

  - temperature -5 ºC ..+30 ºC current 32A,- temperature -5 ºC ..+40 ºC current 24A,

- temperature -5 ºC ..+60 ºC current 14A,

Class II DOUBLE INSULATION fully protected plugs

Uimp Impulse rated Voltage 8KV.

HAND HELD PLUGGING CONNECTIONS

INDIRECT MEASURING

KWH METER TEST BLOCK

with buit in perpendicular disconnections

800V 16mm² 76A

EN 60947-7-1DVE

ORDERING DATA

SPECIFICATIONS

For protected Testing Plugs as per EN 61010-031

13E 9I-4T-EPI

Page 3: Morsettiera misura

7/26/2019 Morsettiera misura

http://slidepdf.com/reader/full/morsettiera-misura 3/4

IP 20 Protection

granted

 Access to the plug sockets, to the longitudinal sliding link, to theRB8 terminal block fastening screws, all meet the fingerprooftest thereby affording an IP20 protection as per EN 60947-1

standard.

Fully protected

plugs used

The sockets of each element are so designed as to take protectedplugs fitted with fixed sleeve, as stipulated by the EN 61010-031standard. They afford the required insulation for the workingvoltage (higher than 33 V a.c.).The 10,5 mm. pitch of the RB8 terminal block also allows for

simultaneous insertion of standard Ø 4 mm. plugs.

Open circu it

indication

Longitudinal disconnection provides an easy visual red stripeindication when the sliding link is in the open position.Fitted with a rugged screw operated by means of insulated 5

mm. width screwdriver.

Recess for the

 jumper plugs

The removable jumper plugs are housed on both side endbrackets and remain always protected by the sealableenveloping cover.Each end bracket can house either one 4-pole or two 2-pole

plugs.

Fastening and

sealing

Fixing of both test block unit to panel and end brackets to Dinrail is carried out by the same fastening screw. The sealedenveloping cover offers safe protection and prevents removal ofthe screw.The enveloping cover is fastened and sealed on both endbrackets by means of an ergonomic clip latch system. Sealingwire to be used, 1,5 mm. max.

Connections up to

16 mm²

Whenever transformers lie at some distance and the use of alarger cable section is therefore required, Unibloc  test blockunits make the task of using 16 mm2 stranded wire cable mucheasier by means of a modeller for cable end terminals built inat both end brackets, which enables to set on the spot suchterminals with no extra tools.

Dual marking

system

Unibloc test block units use two marking possibilities :On the front, showing to the controller the circuit beingoperated.On both top and bottom sides, showing connection points to the

panel builder.

Unibloc test block units can be delivered in several differentconfigurations.Insulated colour coded plug sockets can be fitted for an easieridentification of circuits.Jumper comb bars are available when cross-connection +earthing necessary. A special RBT8 earthing terminal block asper EN 60947-7-2 standard is also available.

Blank spacer 

This accessory to be used for filling in unused spacing wheneverless than 10 or 13 elements are required in both Unibloc 10E or13E test block units.

Cover options

Enveloping covers for Unibloc test block units are made of fireresistant transparent polycarbonate, offering an IP 40 degreeof protection and an IK08 impact strength as per EN 50102standard.Optional non-transparent covers can also be supplied.

 Additionally, both types of covers can have one or both predrilledtop/bottom sides providing an easier connection of incomingcables atop the base plate.

Other accessories

Page 4: Morsettiera misura

7/26/2019 Morsettiera misura

http://slidepdf.com/reader/full/morsettiera-misura 4/4

L1

N

L1

N

 A

L1

N

~   ~

L1

N

L1

N

 A

V

L1

N

L1

N

 A

L1

N

~

~

L1

N

L1

N

 A

V

1 Normal working condition

2 Current and voltage testings

3 Full equipment disconnection

4 Auxiliary equipment connections

5 External power supply

Disconnection pro cedures

Longitudinal (on current line) sliding-link disconnector is operated by a5x1 screwdriver on a M4 screw at 1.5 Nm torque.

Sliding-link opens when slided to transformer’s side.

Perpendicular disconnectors are connected by inserting the safety jumper plugs on the unique side matching socket.

Disconnected Jumper plugs can be housed in the stopper’s receptacle.

 All sockets can take insulated safety 4 mm Ø test plugs with a 10 mmtotal width.

1 Normal working condition

2 Current and voltage testings

3 Full equipment disconnection

4 Auxiliary equipment connections

5 External power supply

Disconnection pro cedures

Longitudinal (on current line) sliding-link disconnector is operated by a5x1 screwdriver on a M4 screw at 1.5 Nm torque.

Sliding-link opens when slided to transformer’s side.

Perpendicular disconnectors are connected by inserting the unloseablesafety jumper plugs on the unique side matching socket.

Jumper plugs are disconnected when in vertical position.

 All sockets can take insulated safety 4 mm Ø test plugs with a 10 mm

total width.

OPERATION FUNCTIONS for removable jumper plugs (10E)

OPERATION FUNCTIONS for buit in jumper plugs (13E)

1 2 3 4 5

1 2 3 4 5

OVERALL SIZES

Type 10E 6I-4T-EPI Type 13E 9I-4T-EPI

87060174/081023

S.A.EL. S.r.l. STRUMENTAZIONE APPARECCHIATURE ELETTRONICHEVia Romagna, 1/3 - 20090 Segrate (Milano) - Tel. +39 02 2139902 Fax +39 02 2135573http://www.saelsrl.com E-mail:[email protected]