N2 Integration with the NAE Technical Bulletin Code No. LIT-1201683 Issued February 4, 2019 Refer to the QuickLIT website for the most up-to-date version of this document. Document Introduction............................................................................................................. 2 Switchable Communications Protocols........................................................................................... 2 Related Documentation............................................................................................................. 3 N2 Integration with the NAE Overview..................................................................................... 3 N2 Device Point Mapping Tables Overview............................................................................. 4 Supported Application Specific Controllers (ASCs).............................................................. 4 Detailed Procedures.................................................................................................................. 5 Adding N2 Integrations....................................................................................................................... 5 Adding N2 Field Devices Manually (Online or Offline).................................................................... 7 Adding N2 Field Devices Online Using Auto Discovery............................................................... 11 Adding Extensions to an Object...................................................................................................... 13 Adding a Resource File Extension...................................................................................................... 16 Adding a Trend Extension................................................................................................................... 17 Adding a Totalization Extension.......................................................................................................... 18 Adding an Alarm Extension................................................................................................................. 19 Adding an Averaging Extension.......................................................................................................... 20 Deleting Extensions from an Object............................................................................................... 21 Copying Extensions to a Field Device or Field Point (Offline Only)............................................ 22 Adding N2 Field Points to an Archive Database............................................................................ 23 Adding Field Points Using Assisted Mode Definition................................................................... 25 Adding Field Points Using Manual Mode Definition...................................................................... 28 N2 FEC, FAC, and VMA Point Limits...................................................................................... 33 N2 Device Point Mapping Tables............................................................................................ 34 AHU.................................................................................................................................................... 34 Unitary (UNT)..................................................................................................................................... 35 VAV Controller................................................................................................................................... 35 VMA 1400 Series............................................................................................................................... 35 Phoenix Fume Hood (PHX).............................................................................................................. 36 Metasys Integrator Unit.................................................................................................................... 36 Vendor Device (VND)........................................................................................................................ 37 ILC...................................................................................................................................................... 37 Intelligent Fire Controller (IFC)........................................................................................................ 37 TC-9100 Terminal Unit Controller.................................................................................................... 38 Lab and Central Plant Controller/Digital Controller (LCP/DC9100).............................................. 41 DX-9100 Extended Digital Controller.............................................................................................. 47 Extension Module (XTM and XT)..................................................................................................... 79 TEC1100............................................................................................................................................. 82 TEC210x............................................................................................................................................. 83 1 N2 Integration with the NAE Technical Bulletin

Upload: others

Post on 07-Apr-2020

11 views

Category:

Documents


0 download

TRANSCRIPT

N2 Integration with the NAE Technical BulletinCode No. LIT-1201683

Issued February 4, 2019Refer to the QuickLIT website for the most up-to-date version of this document.

Document Introduction.............................................................................................................2Switchable Communications Protocols...........................................................................................2

Related Documentation.............................................................................................................3N2 Integration with the NAE Overview.....................................................................................3N2 Device Point Mapping Tables Overview.............................................................................4Supported Application Specific Controllers (ASCs)..............................................................4Detailed Procedures..................................................................................................................5

Adding N2 Integrations.......................................................................................................................5Adding N2 Field Devices Manually (Online or Offline)....................................................................7Adding N2 Field Devices Online Using Auto Discovery...............................................................11Adding Extensions to an Object......................................................................................................13Adding a Resource File Extension......................................................................................................16Adding a Trend Extension...................................................................................................................17Adding a Totalization Extension..........................................................................................................18Adding an Alarm Extension.................................................................................................................19Adding an Averaging Extension..........................................................................................................20Deleting Extensions from an Object...............................................................................................21Copying Extensions to a Field Device or Field Point (Offline Only)............................................22Adding N2 Field Points to an Archive Database............................................................................23Adding Field Points Using Assisted Mode Definition...................................................................25Adding Field Points Using Manual Mode Definition......................................................................28

N2 FEC, FAC, and VMA Point Limits......................................................................................33N2 Device Point Mapping Tables............................................................................................34

AHU....................................................................................................................................................34Unitary (UNT).....................................................................................................................................35VAV Controller...................................................................................................................................35VMA 1400 Series...............................................................................................................................35Phoenix Fume Hood (PHX)..............................................................................................................36Metasys Integrator Unit....................................................................................................................36Vendor Device (VND)........................................................................................................................37ILC......................................................................................................................................................37Intelligent Fire Controller (IFC)........................................................................................................37TC-9100 Terminal Unit Controller....................................................................................................38Lab and Central Plant Controller/Digital Controller (LCP/DC9100)..............................................41DX-9100 Extended Digital Controller..............................................................................................47Extension Module (XTM and XT).....................................................................................................79TEC1100.............................................................................................................................................82TEC210x.............................................................................................................................................83

1N2 Integration with the NAE Technical Bulletin

Document IntroductionThis document describes how to integrate an N2 network in the Metasys® system with the Network AutomationEngine (NAE). This document also describes how to add field devices using an archive database or Discovery, addN2 field points, and create extensions to an object. The N2 device point mapping tables allow you to manually mappoints into the NAE using the System Configuration Tool (SCT). This document lists the devices and points that youcan manually map into the NAE, but does not include information on installing, configuring, or updating an NAE.

This document also contains point mapping limitations for newer model Advanced Application Field EquipmentControllers (FACs), Field Equipment Controllers (FECs), and VAV Modular Assemblies (VMAs). At CCT 10.1, thesedevices can be switched between the N2 and MS/TP communications protocols. When determining the number ofpoints that may be mapped from a newer controller that is being used as an N2 device, it is important to look at thepoint limitations of the new device as well as the point limitations of the device which you are mapping it as (forexample, when defining a VMA16xx as a UNT in the mapping table). In all cases, the point limit is the smaller ofwhat you find in the two tables.

Switchable Communications ProtocolsRelease 10.1 of CCT can be used to switch the Field Bus communications protocol in FEC Field Controllers to beeither the standard BACnet®Master-Slave/Token-Passing (MS/TP) or the N2 protocol. BACnet MS/TP is the defaultcommunications protocol for all new controllers. Switchable communications protocols provide a cost-effectiveupgrade and modernization path for customers with existing N2 controllers. The Modernization Guide for LegacyN2 Controllers (LIT-12012005) and the controller-specific documentation provide installation and commissioningsupport and include tips for efficient and safe replacement. Refer to the N2 Compatibility Options chapter of theController Tool Help (LIT-12011147) for information about mapping N2 Objects in controllers with switchablecommunications protocols.

The N2 capable FEC controllers can be used as functional replacements for legacy N2 controllers. The N2 capableFEC controllers:• have the I/O quantities and characteristics of the FEC family controllers• must be programmed with CCT, which has similar, but not identical programming capabilities as HVACPro,

GX9100, GPL, and other legacy tools• support SA Bus devices• support WRZ wireless sensors from the controller using the WRZ-7860 receiver• are available in Buy American and panelized versions (most models)• support backup schedules in the event of loss of network connection (Advanced Application Field Equipment

Controller [FAC] Series models)

The N2 capable FX-PC controllers can be used as functional replacements for legacy N2 controllers. The N2 capableFX-PC controllers:

The N2 capable FEC controllers:• do not support Zone Bus (for example, TMZ sensors and M100 actuators) or XT-Bus (System 91) devices (for

example, XT, XTM, and XP modules)• do not support a wireless connection to the N2 bus• do not support NxE passthru• are not listed for UL864 UUKL. N2 is not supported as part of the Metasys 9th Edition listing for Smoke Control

System Equipment

2N2 Integration with the NAE Technical Bulletin

Related DocumentationTable 1: N2 Device Point Mapping Tables Related Documentation

See DocumentFor Information OnMetasys® SCT Help (LIT-12011964)Mapping Points

Lighting Control Objects Technical Bulletin (LIT-636105)Programming the Intelligent Lighting Controller(ILC)

IFC-1010/2020 Programming Technical Bulletin(LIT-448060)

Programming the Intelligent Fire Controller (IFC)

Appendix C of the DX-9100 Configuration Guide(LIT-6364030)

Mapping to programmable function module items(PMK, PMO, PMA)

NAE Commissioning Guide (LIT-1201519)Configuring the NAE

NAE55/NIE55 Installation Instructions (Part No.24-10051-43)

Installing the NAE/NIE

Modernization Guide for Legacy N2 Controllers(LIT-12012005)

Technology and general rules for replacing legacyN2 controllers with N2 capable FEC controllers

N2 Integration with the NAE OverviewFor a Metasys network with N2 integration, note the following:

• Devices connected to N30s appear as native N30 objects and when the N30 connects to an NAE, all objectsand devices appear as native NAE objects and devices.

• N2 integration supports Metasys Integrator® units.• Metasys system/N2 integration supports Pass through downloading to Application Specific Controllers (ASCs)

using the XTM Configurator, HVAC PRO software, N2 Loader user interface (UI), and GX-9100 tool software.Refer to the Passthrough section in the Metasys SCT Help (LIT-12011964).

• Metasys system/N2 integration stores configuration information for N2 devices separate from the object anddevice definitions in the NAE. The data is stored in the archive database in the SCT if the NAE is offline or in theNAE archive database if the NAE is online.

• Practical performance is defined in project design.• The NAE35 has a hard limit of a maximum of 50 devices on the N2 trunk.• The NAE45 and NAE55 have a suggested maximum of 100 devices on the N2 trunk.• The NCE25 has a hard limit of a maximum of 32 devices on the N2 trunk.

Note: The N2 Pulse Counter object is called the Accumulator object.

The Insert Field Device and Insert Point wizards guide you through the process of discovering controllers, andimporting and mapping N2 points. When you are online with an NAE through the Site Management Portal UI, notthrough the SCT, the Insert Field Device wizard can use Auto Discovery to discover controllers connected to eachN2 trunk. With Auto Discovery, manual entry of controller addresses and controller types is unnecessary. You canthen map field points within each controller using N2 controller configuration files or manual point definition. Thedatabase created at the NAE using Auto Discovery can then be uploaded to an archive database in the SCT forstoring or editing.

If two controllers on an N2 trunk have the same address, the controller should display with a status of DuplicateAddress. However, auto discovery cannot identify all duplicates, depending on timing and the type of devices. It ispossible that one or both of the duplicate controllers do not appear in the list of discovered controllers. If a controlleris not shown at an expected address, multiple controllers may exist with the same address.Important: BD, ADF and ADI points addressed from 1 - 64 are Read-Write for device types of AHU, UNT and

VAV. The VND device type allows Read-Write for addresses 1 - 255.

3N2 Integration with the NAE Technical Bulletin

N2 Device Point Mapping Tables OverviewThe point mapping tables indicate:

• which controller points you can map to the NAE• if the NAE can command (or override) the controller points (whether they are read only or read/write)• whether the points support override status• the NAE point types the controller points map to

Table 2 lists the point type abbreviations.

Table 2: Point Type AbbreviationsDefinitionAbbreviationAnalog InputAI

Binary InputBI

Analog OutputAO

Binary OutputBO

Analog Data FloatADF

Analog Data IntegerADI

Binary (byte) DataBD

Logic ResultsLRS

Programmable Module Constants (written to Electrically-Erasable Programmable Read-OnlyMemory [EEPROM])

PMK

Programmable Module OutputsPMO

Programmable Module LogicPML

Programmable Module AccumulatorPMA

Supported Application Specific Controllers (ASCs)With the exception of the N2 Dialer, the NAE supports all current N2 devices including Metasys system (AS), Facilitator(FA) models, and the VAV Modular Assembly (VMA) 1400 Series controller. Table 3 shows the firmware versionsof all currently supported ASCs.

Note: Some controllers are unique to a local market and may not be available on a global basis.

Table 3: Firmware Revision of Current ACSsCommentsRevisionDevice/Controller TypeRoom Controller1.xDR-9100

Room Controller2.xDR-9100

Room Controller2.xDR-9101

Plant Controller1.xDC-9100

Plant Controller2.xDC-9100

Digital Controller1.xDO-9100

Digital Controller1.xDX-9100 (V.1)

Digital Controller2.xDX-9100 (V.2)

Digital Controller1.x-3.xTC-910x

N2 Lighting Control Data (LCD) Thermostat1.xTEC1100

Extension Module1.xXT-9100

4N2 Integration with the NAE Technical Bulletin

Table 3: Firmware Revision of Current ACSsCommentsRevisionDevice/Controller TypeExtension Module1.xXTM-101

Extension Module1.xXTM-105

Extension Module1.xXTM-905

Lab and Central Plant ControllerAllLCP-xxx

Metasys Integrator Unit9.0 or laterMetasys Integrator Unit

Unitary ControllerAllUNT

Variable Air Volume (VAV) ControllerAllVAV

Air Handling Unit ControllerAllAHU

Phoenix Interface ModuleAllPHX

VAV Modular AssemblyAllVMA1400

Metasys System Compatible (by others) includingTEC1100, TEC210x and VMA1832

AllVND (Vendor Device)

ILCAllILC1

Intelligent Fire ControllerAllIF-1010/2020

1 Information for ILCs is not valid for MicroLite lighting controllers. For MicroLite panels, use the information for Vendor Devices(VND) instead.

Detailed ProceduresThese procedures show how to add field devices using an archive database or Discovery, add N2 points, and createextensions to an object.

Adding N2 IntegrationsThe two N2 trunks (N2A and N2B) are part of the default NAE database, and you only need to Select N2 Trunk(integration) from the Navigation Tree. You need to Add an N2 trunk only if one or both N2 trunks have been deletedfrom the default database.

To add N2 integrations:

1. On the Insert menu, click Integration. The Insert Integration Wizard starts (Figure 1).2. Follow the prompts to configure the integration using Table 4.

5N2 Integration with the NAE Technical Bulletin

Figure 1: Insert Integration Wizard

Table 4: Insert Integration WizardPurposeScreenSelect the type of integration. For example, N2 trunk,LONWORKS® network, or BACnet® system integration.

Object Type

Select the supervisory device which connects to the trunk youare integrating.

Destination

Type a unique name for the trunk. A unique name is requiredfor each integration under a device. By default, the name ofthe object being entered has a number appended to keep itunique; therefore, if adding an N2 trunk to a site for the firsttime, the default name is N2 Trunk1.

Identifier

Configure information about the integration such as trunknumber and a brief description. Selecting the Advanced buttonallows you to edit the BACnet Object Identifier.1

Configure

View the basic parameters of the integration just added.Summary

1 When selecting or adding a second N2 trunk, you must change the default trunk number (which is 1) on the Hardwaretab to 2.

3. Click Finish.

6N2 Integration with the NAE Technical Bulletin

Adding N2 Field Devices Manually (Online or Offline)You can add N2 field devices manually whether your system is online or offline using the Insert Field Device Wizard.

To add N2 field devices manually:

1. On the Insert menu, click Field Device. The Insert Field Device Wizard starts (Figure 2).

Figure 2: Insert Field Device Wizard Destination Screen

2. Select the trunk where you want to insert the device and click Next. The Insert Field Device Wizard SelectDefinition screen appears (Figure 3).

3. On the Select Definition Mode screen, select the Manual device definition radio button.

Note: When using the SCT, the Assisted device definition radio button appears dimmed because that methodis unavailable when the system is offline.

7N2 Integration with the NAE Technical Bulletin

Figure 3: Insert Field Device Wizard Select Definition Screen

4. Select the type of device and an N2 address for the device you are creating. All N2 addresses in the drop-downcombo box are valid N2 addresses because the list is updated each time a new controller object is created. Afterchoosing an N2 address, click Next. Auto Discovery is only available online for field devices. See the Adding N2Field Devices Online Using Auto Discovery section in this document.

5. Click Next. The Insert Field Device Wizard Identifier screen appears (Figure 4).

8N2 Integration with the NAE Technical Bulletin

Figure 4: Insert Field Device Wizard Identifier Screen

6. Choose a unique name (within the parent object) for the new controller object and click Next. The Insert FieldDevice Wizard Configure screen appears (Figure 5).

The fields of the Configure screen have default data based on the previous information entered. This informationincludes the object type and naming parameters of the new controller being created. When you use the ManualDevice Definition, the default name is always the controller type (for example, Air Handling Unit (AHU), , or VMA)plus an incremental number. The incremental number ensures that the suggested name is unique within thecontext of the parent object, in this case an N2 integration.

9N2 Integration with the NAE Technical Bulletin

Figure 5: Insert Field Device Wizard Configure Screen

7. Click Next. The Insert Field Device Wizard Summary screen appears (Figure 6).

10N2 Integration with the NAE Technical Bulletin

Figure 6: Insert Field Device Wizard Summary Screen

8. If you are satisfied with the Summary, click Finish (otherwise click Back and correct any problems).

The object is created, and you are given the opportunity to add extensions to the new controller object. See theAdding Extensions to an Object section in this document for more information.

Adding N2 Field Devices Online Using Auto DiscoveryWhen you are logged in to an NAE through the Metasys system, you can automatically discover field devices. Theauto discovery process cannot be used through the SCT; however, the devices that are discovered on the networkand added to the NAE database (through the Site Management Portal UI) can be uploaded to the SCT for archivingand editing.

Using this procedure requires that the NAE be online and connected to an N2 network. To connect to an N2 network,verify your NAE is connected to the N2 bus via an N2 port.

Note: Auto discovery does not find N2 devices tunneling over an Ethernet network.

To add N2 field devices online using Auto Discovery:

1. On the Insert menu, select Field Device. The Insert Field Device Wizard Destination screen appears (Figure 2).2. Select the N2 trunk you want to map the field devices to and click Next. The Select Definition Mode screen

appears (Figure 7).

11N2 Integration with the NAE Technical Bulletin

The Assisted Mode and Invoke Auto Discovery options are not available from the SCT. The information discoveredonline can be uploaded to an archive database in the SCT.

Figure 7: Insert Field Device Wizard (Online Only) Select Definition Mode Screen

3. Click the Invoke Auto Discovery button. The Auto Detect Utility starts (Figure 8).

12N2 Integration with the NAE Technical Bulletin

Figure 8: Auto Detect Utility (Online Only) Screen

4. Select the device you want to map. If the device is already mapped, you are notified. If the device is not mapped,the Insert Field Device Identifier screen appears (Figure 4).

5. Enter a unique identifier for the device. The Insert Field Device Wizard Configure screen appears (Figure 5).6. Click Next. The Insert Field Device Summary screen appears (Figure 6).7. If you are satisfied with the Summary, click Finish (otherwise click Back and correct any problems). The object

is created and you are given the opportunity to add extensions to the new controller object. See the AddingExtensions to an Object section in this document for more information.

8. When you have added all discovered devices, use the SCT to upload the NAE database to an archive databasein the SCT.

Adding Extensions to an ObjectAdd trend, totalization, alarm, and resource file extensions to increase the functionality of a field device or field pointobject.

After creating a field device object or a field point object, the Extension Wizard automatically starts (skip to Step 3).

To add extensions to an object:

1. Select an object.2. On the Action menu, select Show Extensions. The Extension Wizard starts (Figure 9).

13N2 Integration with the NAE Technical Bulletin

Figure 9: Extension Wizard

3. Click the New button in the row next to the type of extension you want to add, and follow the prompts on theWizard that appears. See the Adding a Resource File Extension, Adding a Totalization Extension, or Adding anAlarm Extension sections in this document for more information.

4. Follow the prompts to configure the extension and click Finish when you are done. The ExtensionWizard appearswith the new extension listed in the appropriate row (Figure 10).

14N2 Integration with the NAE Technical Bulletin

Figure 10: Extension Wizard with Extension Added

5. Click the Done button when you are finished adding extensions. If the Extension Wizard launched automaticallyafter creating a new field device object, the Field Device Extension screen opens (Figure 11).

15N2 Integration with the NAE Technical Bulletin

Figure 11: Field Device Extension Screen

6. Add field points under the newly created controller object by selecting the New button in the Field Points panelof the Field Device Extension Wizard. See the Adding N2 Field Devices Manually (Online or Offline) section forinstructions on adding N2 points.

Adding a Resource File ExtensionWhen using an HVAC PRO (PRN) file as a resource file, be sure you use the long print file format because it providesthe Metasys system with more information than the short print file format. For example, the long print file formatimports the units of measure while the short file format does not import this information into the Metasys system.The short print file format imports metric HVAC PRO files with imperial attributes that must be individually changedto Metric. To prevent this problem, use the long print file format when importing an HVAC PRO file. To configure thelong print file format, launch HVAC PRO and select File > Print Format > Long.

The resource file object extension is the most important extension to the N2 controller objects. N2 configuration filesare imported in the Resource File Wizard. These files provide predefined point information that is used for the creationof N2 point objects in the Insert Field Point Wizard. Resource files enable the assisted point definition mode in theInsert Point Wizard. They also provide the view information used in the Engineering view of the N2 trunks. If the N2device does not have a resource file extension, Assisted mode is not available in the Insert Point Wizard.

To add a resource file extension:

1. In the Extension Wizard, click the New button in the Resource File row. The Insert Resource File Wizard SelectFile screen appears (Figure 12).

16N2 Integration with the NAE Technical Bulletin

Figure 12: Insert Resource File Wizard Select File Screen

2. Click the Browse button and locate the resource file to import to the object. The default file type is based uponthe file type expected for the parent-controller object. For example, for a UNT controller, the default file type is.prn. After you select a file, the Wizard validates the file based on the controller type of the newly created object.If the selected file does not appear to be correct for the controller, a red error message appears in the user textarea of the Resource File Wizard showing the expected controller type from within the selected file.

3. After you select a valid import file, click Next. The Insert Resource Wizard Configure screen appears.

The description property shows the original file location and file name of the selected import file as reference.The converted XML file based on the selected file is not accessible to the user.

4. If the Configure screen looks correct, click Next. The Insert Resource Wizard Summary screen appears.5. Click Finish. The Extensions Wizard appears with the new Resource File listed under Resource Files.

Adding a Trend ExtensionAdding trend extensions to objects allows you to collect historical data for one or more attributes of an object, thenview that data and/or have the data forwarded to an ADS/ADX for long-term storage. Use Trend Study to view Trendextensions frommultiple items at the same time. For more information on Trend Studies, refer to the Metasys systemHelp.

To add a trend extension:

17N2 Integration with the NAE Technical Bulletin

1. In the Extensions Wizard, click the New button in the Trend row. The Insert Trend Wizard Select Attribute screenappears. The trended attribute defaults to Present Value. To trend a different attribute, click other... The attributelist appears (Figure 13).

Figure 13: Insert Trend Wizard Select Attribute Screen

2. Select an attribute and follow the prompts in the Wizard to complete the addition of a Trend Extension.3. Click Finish. The Extensions Wizard appears with the new attribute listed under Trend.

Adding a Totalization Extension1. In the Extensions Wizard, click the New button in the Totalization row. The Insert Totalization Wizard Select

Attribute screen appears (Figure 14).

18N2 Integration with the NAE Technical Bulletin

Figure 14: Insert Totalization Wizard Select Attribute Screen

2. Select an object in the top of the screen and an attribute in the bottom and click Next.

Note: Click other to display a list of available attributes.3. Select Totalization type from the available radio buttons on the right (if available).4. Follow the prompts in the Wizard to complete the addition of a Totalization Extension.5. Click Finish. The Extensions Wizard appears with the new attribute listed under Totalization.

Adding an Alarm Extension1. In the Extensions Wizard, click the New button in the Alarm row. The Insert AlarmWizard Select Attribute screen

appears (Figure 15).

19N2 Integration with the NAE Technical Bulletin

Figure 15: Insert Alarm Wizard Select Attribute Screen

2. Select an object you want to add the Alarm extension to in the top of the screen and an attribute in the bottomand click Next.

Note: Click other to display a list of available attributes.3. Follow the prompts in the Wizard to complete the addition of an Alarm Extension.4. Click Finish. The Extensions Wizard appears with the new attribute listed under Alarm.

Adding an Averaging Extension1. In the ExtensionsWizard, click the New button in the Averaging row. The Insert AveragingWizard Select Attribute

screen appears (Figure 16).

20N2 Integration with the NAE Technical Bulletin

Figure 16: Insert Averaging Wizard Select Attribute Screen

2. Select an object you want to add the Averaging extension to at the top of the screen and an attribute at thebottom. Click Next.

Note: Click other to display a list of available attributes.3. Follow the prompts in the Wizard to complete the addition of an Averaging Extension.4. Click Finish. The Extensions Wizard appears with the new attribute listed under Averaging.

Deleting Extensions from an Object1. Select a field device or a field point that contains extensions you want to delete.2. On the Action menu, select Show Extensions. The Extension Wizard starts (Figure 17).

21N2 Integration with the NAE Technical Bulletin

Figure 17: Extension Wizard

3. Select the check boxes next to the extensions you want to delete.4. Click Delete for each extension.

When you click the Delete button in any extension row, it only deletes the checked extensions in that row. Forexample, you have to click both the Totalization delete button and the Averaging delete button to delete bothchecked extensions. See Figure 17.

5. Click Done when finished.

Copying Extensions to a Field Device or Field Point (Offline Only)1. Select a field device or a field point that contains extensions you want to copy.2. On the Action menu, click Show Extensions. The Extension Wizard starts (Figure 17).3. Check the extensions that you want to copy and click the Copy Checked Extensions button at the bottom of the

Wizard.4. Click Done.5. In the Navigation Tree, select the field device or field point to which you want to add these extensions.6. On the Edit menu, click Paste. The copied extensions are added to the field device or field point you have

selected. A message appears stating the extension paste has completed.7. Click OK.8. Drag the field device or field point to the Display frame (right pane) to verify that the new extensions are correct.

22N2 Integration with the NAE Technical Bulletin

Figure 18: Totalization and Averaging Extensions Pasted into AHU-1

Adding N2 Field Points to an Archive Database1. On the Insert menu, click Field Point. The Insert Point Wizard Destination screen appears (Figure 19).

23N2 Integration with the NAE Technical Bulletin

Figure 19: Insert Point Wizard Destination Screen

2. Choose a controller or folder in which to insert the new field points and click Next. The Insert Point Wizard SelectDefinition Mode screen appears (Figure 20).

24N2 Integration with the NAE Technical Bulletin

Figure 20: Insert Point Wizard Select Definition Mode Screen

Note: There are two methods of adding field points in the SCT and online UI. If you have created a ResourceFile extension for the field device to which you are adding points, then Assisted mode definition is available.Otherwise, the Assisted button is grayed out and your only choice for adding field points is manual mode.Depending on which mode you are using, see the Adding Field Points Using Assisted Mode Definitionor Adding Field Points Using Manual Mode Definition sections in this document.

Adding Field Points Using Assisted Mode DefinitionIf you have created a Resource file extension for the field device to which you are adding points, then assisted modedefinition is enabled. Assisted mode definition is the fastest way to add field points to a field device.

To add field points using assisted mode definition:

1. On the Insert Point Wizard Select Definition Mode screen (Figure 20), select the Assisted radio button.2. Click the Use Point Definition File button. The Point Mapping Utility starts (Figure 21).

25N2 Integration with the NAE Technical Bulletin

Figure 21: Point Mapping Utility

3. Select individual points to map by double-clicking them, or click the Map All button to map all available pointsfrom the file. Each point that is mapped appears in the Points to Map Summary panel on the right and is alsomarked with a green check mark to show that it is a mapped point (Figure 22).

26N2 Integration with the NAE Technical Bulletin

Figure 22: Point Mapping Utility with All Points Mapped

Note: In the Point Mapping Utility, you can edit information about individual points in the Points to Map Summarypanel. You can also un-map individual points by double-clicking the point in the middle panel or clickingthe Unmap All button. Selecting a folder in the middle panel displays the points mapped from that folderin the Points to Map Summary panel, whereas selecting the field device in the middle panel displays asummary of all points mapped to that device in the Points to Map Summary panel.

4. Click Next when you have mapped all desired points. The Insert Point Wizard Summary screen appears (Figure22).

27N2 Integration with the NAE Technical Bulletin

Figure 23: Insert Point Wizard Summary Screen

5. If you are satisfied with the Summary, click Finish (otherwise, click the Back button and edit as needed.).

Adding Field Points Using Manual Mode Definition1. On the Insert Point Wizard Select Definition Mode screen (Figure 24), select the Manual radio button. The Insert

Point Wizard switches to Manual mode (Figure 24).

28N2 Integration with the NAE Technical Bulletin

Figure 24: Insert Point Wizard Manual Definition Mode

2. Select the type of point that you want to add and click Next. The point information on the Select Data Sourcescreen is pre-configured, based on the object type selected in the Select Definition Mode screen; however, onthe Select Data Source screen you can edit some properties of the point that cannot be edited in the Configurescreen. Depending on how many points of each type were added to a controller, the values available in thedrop-down boxes change so your available selections are valid. The Insert Point Wizard Select Data Sourcescreen appears (Figure 25).

29N2 Integration with the NAE Technical Bulletin

Figure 25: Insert Point Wizard Select Data Source Screen

3. Edit the point properties as necessary and click Next. The Insert Point Wizard Identifier screen appears (Figure26).

30N2 Integration with the NAE Technical Bulletin

Figure 26: Insert Point Wizard Identifier Screen

4. Enter a unique name for the new field point. The default name is based on the object type of the new field point.5. Click Next. The Insert Point Wizard Configure screen appears (Figure 27).

31N2 Integration with the NAE Technical Bulletin

Figure 27: Insert Point Wizard Configure Screen

6. Review the Configuration and Hardware tabs. Edit if necessary and click Next. The Insert Point Wizard Summaryscreen appears (Figure 28). Properties edited in the Manual Point Data Source page are not editable in thenormal Configuration view of the object.

Note: The object type and naming parameters of the new point appear in the Insert Point Wizard Summaryscreen. When you click Finish, the object is created and you are prompted to add extensions to the newpoint object through the Extension Wizard.

32N2 Integration with the NAE Technical Bulletin

Figure 28: Insert Point Wizard Summary Screen

7. Click Finish. Otherwise, click the Back button and edit as needed.

N2 FEC, FAC, and VMA Point LimitsAt CCT 10.1, FECs, FACs, and VMAs can be defined as certain N2 devices. These devices include AHUs, UNTs,VAVs, and vendor devices. The following tables define the point limits of the new devices. To determine the appropriatepoint limits, use these tables and the tables for the devices which you are defining them as. In all cases, use thelower of the point limits of the N2 FEC and of the device it is defined as. For example, if you are defining an FEC1611as an AHU, your point limit for AIs is 8, as defined in the AHU Point Mapping to NAEs table, rather than the potentialof 12 shown in Table 6.

Table 5: Point Limitations of FAC2611, FAC2612, and FAC3611Network Point AddressNetwork Point Type1-50AI

1-50BI

1-50AO

1-50BO

1-256ADF

1-256ADI

1-256BD

Table 6: Point Limitations of FEC1611 and FEC2611Network Point AddressNetwork Point Type1-12AI

1-12BI

33N2 Integration with the NAE Technical Bulletin

Table 6: Point Limitations of FEC1611 and FEC2611Network Point AddressNetwork Point Type1-10AO

1-15BO

1-256ADF

1-256ADI

1-256BD

Table 7: Point Limitations of VMA1615, VMA1617, VMA1630, VMA1632, and VMA1832Network Point AddressNetwork Point Type1-8AI

1-8BI

1-8AO

1-8BO

1-256ADF

1-256ADI

1-256BD

N2 Device Point Mapping TablesThe N2 device point mapping tables allow you to manually map points into the NAE using the SCT. These tableslist the devices and points that you can manually map into the NAE.

AHUTable 8 describes AHU to NAE object mapping.

Table 8: AHU Point Mapping to NAEsCan Map to NAE Objects:Command AllowedNetwork Point AddressNetwork Point Type1

AI, AO, MSI, MSOYes1-8AI

AO, MSOYes1-8AO

BI, BO

BI 7-8 can be mapped to PC

Yes1-8BI

BOYes1-10BO

AI, MSI1-64ADF

AI, AO, MSI, MSOYesADF

65-256

AI, MSI1-64ADI

AI, AO, MSI, MSOYes65-256

AI, BI, MSI1-64BD

AI, AO, BI, BO, MSI, MSOYes65-2562

1 When configuring an FEC or FAC as an N2 AHU, UNT or VAV type device, the limitations of the new controller must beconsidered in addition to those in this table. See N2 FEC, FAC, and VMA Point Limits.

2 BD245 through BD248 are reserved for user-defined data storage points.

34N2 Integration with the NAE Technical Bulletin

Unitary (UNT)Table 9 describes UNT to NAE object mapping.

Table 9: UNT Point Mapping to the NAECan Map to NAE ObjectsCommand AllowedNetwork Point AddressNetwork Point Type 1

AI, AO, MSI, MSOYes1-40AI

AOYes1-8AO

BI, BO

BI 4 can be mapped to PC.

Yes1-37BI

BOYes1-14BO

AI, MSI1-64ADF

AI, AO, MSI, MSOYes65-256

AI, MSI1-64ADI

AI, AO, MSI, MSOYes65-256

AI, BI, MSI1-64

65-2562BD

AI, AO, BI, BO, MSI, MSOYes

1 When configuring an FEC or FAC as an N2 AHU, UNT or VAV type device, the limitations of the new controller must beconsidered in addition to those in this table. See N2 FEC, FAC, and VMA Point Limits.

2 BD245 through BD248 are reserved for user-defined data storage points.

VAV ControllerTable 10 describes VAV to NAE object mapping.

Table 10: VAV Point Mapping to NAECan Map to NAE Objects:Command AllowedNetwork Point AddressNetwork Point Type 1

AI, AO, MSI, MSOYes1-6AI

AO, MSOYes1-8AO

BI, BO

BI 4 can be mapped to PC.

Yes1-5BI

BOYes1-8BO

AI, MSI1-64ADF

AI, AO, MSI, MSOYes65-256

AI, MSI1-64ADI

AI, AO, MSI, MSOYes65-256

AI, BI, MSI1-64BD

AI, AO, BI, BO, MSI, MSOYes65-2562

1 When. configuring an FEC or FAC as an N2 AHU, UNT or VAV type device, the limitations of the new controller must beconsidered in addition to those in this table. See N2 FEC, FAC, and VMA Point Limits.

2 BD245 through BD248 are reserved for user-defined data storage points.

VMA 1400 SeriesTable 11 describes VMA1400 to NAE object mapping.

35N2 Integration with the NAE Technical Bulletin

Only points defined in the HVAC PRO software configuration can be mapped to the NAE. VMA format errors aregenerated if this rule is not followed.

Table 11: VMA Point Mapping to NAECan Map to NAE ObjectsCommand AllowedNetwork Point AddressNetwork Point Type1

AI, AO, MSI, MSOYes1-6AI

AO, MSOYes1-8AO

BI, BOYes1-5BI

BOYes1-8BO

AI, MSI1-64ADF

AI, AO, MSI, MSOYes65-256

AI, MSI1-64ADI

AI, AO, MSI, MSOYes65-256

AI, BI, MSI1-64BD

AI, AO, BI, BO, MSI, MSOYes65-256

1 When configuring an FEC or FAC as an N2 AHU, UNT or VAV type device, the limitations of the new controller must beconsidered in addition to those in this table. See N2 FEC, FAC, and VMA Point Limits.

Phoenix Fume Hood (PHX)Table 12 describes PHX to NAE object mapping.

Table 12: PHX Point Mapping to NAEsCan Map to NAE Objects:Command AllowedNetwork Point AddressNetwork Point TypeAI, AO, MSI, MSOYes1-40AI

AO, MSOYes1-8AO

BI, BO

BI 4 can be mapped to PC.

Yes1-37BI

BOYes1-14BO

AI, MSI1-64ADF

AI, AO, MSI, MSOYes65-256

AI, MSI1-64ADI

AI, AO, MSI, MSOYes65-256

AI, BI, MSI1-64BD

AI, AO, BI, BO, MSI, MSOYes65-2561

1 BD245 through BD248 are reserved for user-defined data storage points.

Metasys Integrator UnitTable 13 describes the Metasys Integrator unit to NAE object mapping.

Table 13: Metasys Integrator Unit Point Mapping to an NAECan Map to NAE Objects:Command AllowedNetwork Point AddressNetwork Point TypeAI, MSI, MSOYes1-256AI

AO, MSOYes1-256AO

36N2 Integration with the NAE Technical Bulletin

Table 13: Metasys Integrator Unit Point Mapping to an NAECan Map to NAE Objects:Command AllowedNetwork Point AddressNetwork Point TypeBI, BO, PCYes1-256BI

BOYes1-256BO

AI, AO, MSI, MSOYes1-256ADF

AI, AO, MSI, MSO, PCYes1-256ADI

AI, AO, BI, BO, MSI, MSOYes1-256BD

Vendor Device (VND)Table 14 describes VND to NAE object mapping.

Table 14: VND Point Mapping to an NAECan Map to NAE Objects:Command AllowedNetwork Point AddressNetwork Point TypeAI, MSI, MSOYes1-256AI

AO, MSOYes1-256AO

BI, BOYes1-256BI

BOYes1-256BO

AI, AO, MSI, MSOYes1-256ADF

AI, AO, MSI, MSO, PCYes1-256ADI

AI, AO, BI, BO, MSI, MSOYes1-256BD

ILCBefore you map ILC points to NAE objects, the ILC must be programmed. The point mapping table for ILCs is notvalid for MicroLite lighting controllers; instead, use the VND table. Table 15 describes ILC to NAE object mapping.

Table 15: ILC Point Mapping to an NAEDescriptionCan Map to NAE

Objects:OverrideStatus

CommandAllowed

Network PointAddress

Network PointType

Current month runtimelighting

Groups 1-32 (hours)

AI AONoYes1-32ADI

Previous month runtimelighting

Groups 1-32 (hours)

AI AONoYes33-64ADI

Lighting groups (manualoverride)

BOYesYes1-32BO

Intelligent Fire Controller (IFC)Before you map IFC points to NAE objects, the IFC must be programmed.

All points are mapped to NAE BI (Binary Input) points. All points are read-only (no commands allowed). It is theuser’s option to map either a general trouble status point or a trouble status point for each zone.

The fire alarm panel only reports exceptions. Newly added fire points must wait for an exception report beforereporting online. An offline/online transition for the whole controller also generates exception reports. Table 16describes IFC to NAE object mapping.

37N2 Integration with the NAE Technical Bulletin

Table 16: IFC Point Mapping to an NAENotesNAE Object

Description andUnits

Can Map to NAEObjects:

Network PointAddress

Network Point Type

Zone displays troublestatus (T).Overridestatus (O) = zonedisabled at fire panel.

Zone State (Nor/Alm)BI1-240BI

No trouble status (T)Zone Trouble (Nor/Tbl)BI1-240BD

UPS Battery Low(Ok/Alm)

BI241BD

AC Power Fail (Ok/Alm)BI242BD

Database Fault (Ok/Alm)BI243BD

General system alarmpoint

System Alarm (Nor/Alm)BI244BD

General system troublepoint

System Trouble(Nor/Tbl)

BI245BD

Alarm Silenced (No/Yes)BI246BD

TC-9100 Terminal Unit ControllerTable 17 shows how TC-9100 points can map to NAE objects. Table 18 provides more detail about the points (forexample, tag names, item descriptions, and which points are commandable). Use the .PRN file generated by HVACPRO software to determine which points are applicable to the specific TC-9100 controller you are mapping (forexample, TC-9102).Note: If BD-2 is mapped into NAE as a BO, commands to this BO switch the controller mode between Night/Comfort.

This scenario allows NAE to schedule the controller mode weekly. If BD-2 is mapped into NAE as an AO/MSO,a manual command can command this AO/MSO to any of the four controller modes. Only one of thesemethods (BO or AO/MSO) may be used. The override status flag for BD-2 is SUPC (BO-11). A command toBD-2 sets SUPC, and a release or auto command clears it.

Table 17: TC-9100 Point Mapping to an NAENAE Object TypeTC-9100 Network Point TypeAI1 to 10AI

1 to 2BD

1 to 421PMK

BI1 to 14BI

AO1 to 18AO

1 to 2BD

1 to 421PMK

BO1 to 13BO

1 to 2BD

1 All but PMK1 stored in EEPROM (maximum 10,000 write commands).

38N2 Integration with the NAE Technical Bulletin

Table 18: TC-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Process TemperatureAI11AI

Remote Temperature Setpoint BiasAI22AI

PressureAI33AI

Override InputAI44AI

DR-9100 onlyAI55AI

DR-9100 onlyAI66AI

SPARE7AI

SPARE8AI

Winter Authority CorrectionWAC9AI

Summer Authority CorrectionSAC10AI

Window SenseWIN1BI

Occupancy SenseOCC2BI

Air Quality SenseAIRQ3BI

Temporary ModeMODT4BI

Alternate ModeALT5BI

Supervisory Mode StatusSUPS6BI

SPARE7BI

SPARE8BI

Reverse Action LocalREVL9BI

Loop 1 ActiveL1A10BI

General AlarmALM11BI

Low Limit Mode ActiveAFM12BI

Three Speed Fan OverrideFOV13BI

Loop 3 ActiveL3A14BI

Output Programmable Module 1OCM1YesYes1AO

Output Programmable Module 2OCM2YesYes2AO

Output Programmable Module 3OCM3YesYes3AO

Output Programmable Module 4OCM4YesYes4AO

Output Programmable Module 5OCM5YesYes5AO

Output Programmable Module 6OCM6YesYes6AO

Working Set Point Loop 1WSP 1YesYes7AO

Working Set Point Loop 2WSP 2YesYes8AO

Working Set Point Loop 3WSP 3YesYes9AO

Working Set Point Loop 4WSP 4YesYes10AO

Working Set Point Loop 5WSP 5YesYes11AO

Working Set Point Loop 6WSP 6YesYes12AO

External Input 1XAI1Yes13AO

39N2 Integration with the NAE Technical Bulletin

Table 18: TC-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

External Input 2XAI2Yes14AO

External Input 3XAI3Yes15AO

External Input 4XAI4Yes16AO

Analog Constant 5AC05Yes17AO

Analog Constant 6AC06Yes18AO

TRIAC 1D01YesYes1BO

TRIAC 2D02YesYes2BO

TRIAC 3D03YesYes3BO

TRIAC 4D04YesYes4BO

TRIAC 5D05YesYes5BO

TRIAC 6D06YesYes6BO

Shutoff ModeSOFFYes8BO

Startup ModeSTUPYes9BO

DR-9100 OnlyDAYYes10BO

Supervisory Mode Control (SeeBD-2 and Note)

SUPCYes11BO

Manual Operation ModeMANYes12BO

Reverse Action CommandREVCYes13BO

Mode Status: Night, Standby,Comfort, Off

MODSYes1BD

Mode Command: Night, Standby,Comfort, Off (See Note)

MODCYesYes2BD

K1Module 1Constant:

PM1K1Yes1PMK

K2PM1K2Yes12PMK

K3PM1K3Yes13PMK

K4PM1K4Yes14PMK

K5PM1K5Yes15PMK

K6PM1K6Yes16PMK

K7PM1K7Yes17PMK

K1Module 2Constant:

PM2K1Yes8PMK

K2PM2K2Yes19PMK

K3PM2K3Yes110PMK

K4PM2K4Yes111PMK

K5PM2K5Yes112PMK

K6PM2K6Yes113PMK

K7PM2K7Yes114PMK

40N2 Integration with the NAE Technical Bulletin

Table 18: TC-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 3Constant:

PM3K1Yes15PMK

K2PM3K2Yes116PMK

K3PM3K3Yes117PMK

K4PM3K4Yes118PMK

K5PM3K5Yes119PMK

K6PM3K6Yes120PMK

K7PM3K7Yes121PMK

K1Module 4Constant:

PM4K1Yes22PMK

K2PM4K2Yes123PMK

K3PM4K3Yes124PMK

K4PM4K4Yes125PMK

K5PM4K5Yes126PMK

K6PM4K6Yes127PMK

K7PM4K7Yes128PMK

K1Module 5Constant:

PM5K1Yes29PMK

K2PM5K2Yes130PMK

K3PM5K3Yes131PMK

K4PM5K4Yes132PMK

K5PM5K5Yes133PMK

K6PM5K6Yes134PMK

K7PM5K7Yes135PMK

K1Module 6Constant:

PM6K1Yes36PMK

K2PM6K2Yes137PMK

K3PM6K3Yes138PMK

K4PM6K4Yes139PMK

K5PM6K5Yes140PMK

K6PM6K6Yes141PMK

K7PM6K7Yes142PMK

1 Item stored in EEPROM (maximum 10,000 write commands).

Lab and Central Plant Controller/Digital Controller (LCP/DC9100)Table 19 and Table 20 show LCP/DC9100 point mapping. Table 19 shows how LCP/DC9100 points can map toNAE objects. Table 20 provides more detail about the LCP/DC9100 points (for example, tag names and which pointsare commandable).

41N2 Integration with the NAE Technical Bulletin

Table 19: LCP/DC9100 Point Mapping to NAENAE Object TypeLCP/DC9100 Network Point TypeAIAI, ADF

AOADF

BIBI, BD

BOBO, BD

42N2 Integration with the NAE Technical Bulletin

Table 20: LCP/DC9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Analog Input 1AI11AI

Analog Input 2AI22AI

Analog Input 3AI33AI

Analog Input 4AI44AI

Analog Input 5AI55AI

Analog Input 6AI66AI

Analog Input 7AI77AI

Analog Input 8AI88AI

Digital Input 1DI11BI

Digital Input 2DI22BI

Digital Input 3DI33BI

Digital Input 4DI44BI

Digital Input 5DI55BI

Digital Input 6DI66BI

Digital Input 7DI77BI

Digital Input 8DI88BI

Digital Output 3DO3YesYes1BO

Digital Output 4DO4YesYes2BO

Digital Output 5DO5YesYes3BO

Digital Output 6DO6YesYes4BO

Digital Output 7DO7YesYes5BO

Digital Output 8DO8YesYes6BO

Shut Off ModeSOFFYes7BO

Start Up ModeSTUPYes8BO

Output Numeric Module 1NCM11ADF

Output Numeric Module 2NCM22ADF

Output Numeric Module 3NCM33ADF

Output Numeric Module 4NCM44ADF

Analog Constant 1ACO1Yes5ADF

Analog Constant 2ACO2Yes6ADF

Analog Constant 3ACO3Yes7ADF

Analog Constant 4ACO4Yes8ADF

Output Control Module 1OCM1YesYes9ADF

Output Control Module 2OCM2YesYes10ADF

Output Control Module 3OCM3YesYes11ADF

Output Control Module 4OCM4YesYes12ADF

Output Control Module 5OCM5YesYes13ADF

Output Control Module 6OCM6YesYes14ADF

43N2 Integration with the NAE Technical Bulletin

Table 20: LCP/DC9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Output Control Module 7OCM7YesYes15ADF

Output Control Module 8OCM8YesYes16ADF

Working Setpoint Control Module 1WSP1YesYes17ADF

Working Setpoint Control Module 2WSP2YesYes18ADF

Working Setpoint Control Module 3WSP3YesYes19ADF

Working Setpoint Control Module 4WSP4YesYes20ADF

Working Setpoint Control Module 5WSP5YesYes21ADF

Working Setpoint Control Module 6WSP6YesYes22ADF

Working Setpoint Control Module 7WSP7YesYes23ADF

Working Setpoint Control Module 8WSP8YesYes24ADF

Local SetpointControl Module 1:LSP1Yes25ADF

Proportional BandPB1Yes26ADF

Reset ActionTI1Yes27ADF

Rate ActionTD1Yes28ADF

Output High LimitHIL1Yes29ADF

Output Low LimitLOL1Yes30ADF

Standby STPChange

BSB1Yes31ADF

Off Mode STPChange

BOF1Yes32ADF

Deviation AlarmLimit

DA1Yes33ADF

Local SetpointControl Module 2:LSP2Yes34ADF

Proportional BandPB2Yes35ADF

Reset ActionTI2Yes36ADF

Rate ActionTD2Yes37ADF

Output High LimitHIL2Yes38ADF

Output Low LimitLOL2Yes39ADF

Standby STPChange

BSB2Yes40ADF

Off Mode STPChange

BOF2Yes41ADF

Deviation AlarmLimit

DA2Yes42ADF

44N2 Integration with the NAE Technical Bulletin

Table 20: LCP/DC9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Local SetpointControl Module 3:LSP3Yes43ADF

Proportional BandPB3Yes44ADF

Reset ActionTI3Yes45ADF

Rate ActionTD3Yes46ADF

Output High LimitHIL3Yes47ADF

Output Low LimitLOL3Yes48ADF

Standby STPChange

BSB3Yes49ADF

Off Mode STPChange

BOF3Yes50ADF

Deviation AlarmLimit

DA3Yes51ADF

Local SetpointControl Module 4:LSP4Yes52ADF

Proportional BandPB4Yes53ADF

Reset ActionTI4Yes54ADF

Rate ActionTD4Yes55ADF

Output High LimitHIL4Yes56ADF

Output Low LimitLOL4Yes57ADF

Standby STPChange

BSB4Yes58ADF

Off Mode STPChange

BOF4Yes59ADF

Deviation AlarmLimit

DA4Yes60ADF

Local SetpointControl Module 5:LSP5Yes61ADF

Proportional BandPB5Yes62ADF

Reset ActionTI5Yes63ADF

Rate ActionTD5Yes64ADF

Output High LimitHIL5Yes65ADF

Output Low LimitLOL5Yes66ADF

Standby STPChange

BSB5Yes67ADF

Off Mode STPChange

BOF5Yes68ADF

Deviation AlarmLimit

DA5Yes69ADF

45N2 Integration with the NAE Technical Bulletin

Table 20: LCP/DC9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Local SetpointControl Module 6:LSP6Yes70ADF

Proportional BandPB6Yes71ADF

Reset ActionTI6Yes72ADF

Rate ActionTD6Yes73ADF

Output High LimitHIL6Yes74ADF

Output Low LimitLOL6Yes75ADF

Standby STPChange

BSB6Yes76ADF

Off Mode STPChange

BOF6Yes77ADF

Deviation AlarmLimit

DA6Yes78ADF

Local SetpointControl Module 7:LSP7Yes79ADF

Proportional BandPB7Yes80ADF

Reset ActionTI7Yes81ADF

Rate ActionTD7Yes82ADF

Output High LimitHIL7Yes83ADF

Output Low LimitLOL7Yes84ADF

Standby STPChange

BSB7Yes85ADF

Off Mode STPChange

BOF7Yes86ADF

Deviation AlarmLimit

DA7Yes87ADF

Local SetpointControl Module 8:LSP8Yes88ADF

Proportional BandPB8Yes89ADF

Reset ActionTI8Yes90ADF

Rate ActionTD8Yes91ADF

Output High LimitHIL8Yes92ADF

Output Low LimitLOL8Yes93ADF

Standby STPChange

BSB8Yes94ADF

Off Mode STPChange

BOF8Yes95ADF

Deviation AlarmLimit

DA8Yes96ADF

Output Logic Module 1LCM11BD

Output Logic Module 2LCM22BD

Output Logic Module 3LCM33BD

Output Logic Module 4LCM44BD

Digital Constant 1DCO1Yes5BD

46N2 Integration with the NAE Technical Bulletin

Table 20: LCP/DC9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Digital Constant 2DCO2Yes6BD

Digital Constant 3DCO3Yes7BD

Digital Constant 4DCO4Yes8BD

DX-9100 Extended Digital ControllerTable 21 and Table 22 show DX-9100 point mapping. Table 21 shows how DX-9100 points can map to NAE objects.Table 22 provides details about DX-9100 points (for example, tag names, item descriptions, and which points arecommandable).

Note: For XPs, the actual AO range is AO7 and AO8 and the actual AI range is AI1 through AI8.

Note: EEPROM Items can only be written approximately 10,000 times.

Table 21: DX-9100 Point Mapping to NAENAE Object TypeDX-9100 Network Point Type

AI1 to 72AI

1 to 8ADF

1 to 72ADI

1 to 240PMK

1 to 96PMO

1 to 96PMA

AO1 to 72AO

1 to 8ADF

1 to 72ADI

1 to 240PMK

1 to 96PMO

BI1 to 72BI

1 to 32BD

1 to 64LRS

1 to 96PML

BO1 to 72BO

1 to 32BD

1 to 96PML

PC1 to 72ADI

1 to 96PMA

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Analog Input 1AI11AI

Analog Input 2AI22AI

Analog Input 3AI33AI

47N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Analog Input 4AI44AI

Analog Input 5AI55AI

Analog Input 6AI66AI

Analog Input 7AI77AI

Analog Input 8AI88AI

Analog Input 1Expander 1:XT1AI19AI

Analog Input 2XT1AI210AI

Analog Input 3XT1AI311AI

Analog Input 4XT1AI412AI

Analog Input 5XT1AI513AI

Analog Input 6XT1AI614AI

Analog Input 7XT1AI715AI1

Analog Input 8XT1AI816AI1

Analog Input 1Expander 2:XT2AI117AI

Analog Input 2XT2AI218AI

Analog Input 3XT2AI319AI

Analog Input 4XT2AI420AI

Analog Input 5XT2AI521AI

Analog Input 6XT2AI622AI

Analog Input 7XT1AI723AI1

Analog Input 8XT1AI824AI1

Analog Input 1Expander 3:XT3AI125AI

Analog Input 2XT3AI226AI

Analog Input 3XT3AI327AI

Analog Input 4XT3AI428AI

Analog Input 5XT3AI529AI

Analog Input 6XT3AI630AI

Analog Input 7XT3AI731AI1

Analog Input 8XT3AI832AI1

Analog Input 1Expander 4:XT4AI133AI

Analog Input 2XT4AI234AI

Analog Input 3XT4AI335AI

Analog Input 4XT4AI436AI

Analog Input 5XT4AI537AI

Analog Input 6XT4AI638AI

Analog Input 7XT4AI739AI1

Analog Input 8XT4AI840AI1

48N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Analog Input 1Expander 5:XT5AI141AI

Analog Input 2XT5AI242AI

Analog Input 3XT5AI343AI

Analog Input 4XT5AI444AI

Analog Input 5XT5AI545AI

Analog Input 6XT5AI646AI

Analog Input 7XT5AI747AI 1

Analog Input 8XT5AI848AI1

Analog Input 1Expander 6:XT6AI149AI

Analog Input 2XT6AI250AI

Analog Input 3XT6AI351AI

Analog Input 4XT6AI452AI

Analog Input 5XT6AI553AI

Analog Input 6XT6AI654AI

Analog Input 7XT6AI755AI

Analog Input 8XT6AI856AI

Analog Input 1Expander 7:XT7AI157AI

Analog Input 2XT7AI258AI

Analog Input 3XT7AI359AI

Analog Input 4XT7AI460AI

Analog Input 5XT7AI561AI

Analog Input 6XT7AI662AI

Analog Input 7XT7AI763AI

Analog Input 8XT7AI864AI

Analog Input 1Expander 8:XT8AI165AI

Analog Input 2XT8AI266AI

Analog Input 3XT8AI367AI

Analog Input 4XT8AI468AI

Analog Input 5XT8AI569AI

Analog Input 6XT8AI670AI

Analog Input 7XT8AI771AI

Analog Input 8XT8AI872AI

Digital Input 1DI11BI

Digital Input 2DI22BI

Digital Input 3DI33BI

Digital Input 4DI44BI

Digital Input 5DI55BI

Digital Input 6DI66BI

49N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Digital Input 7DI77BI

Digital Input 8DI88BI

Digital Input 1Expander 1:XT1DI19BI

Digital Input 2XT1DI210BI

Digital Input 3XT1DI311BI

Digital Input 4XT1DI412BI

Digital Input 5XT1DI513BI

Digital Input 6XT1DI614BI

Digital Input 7XT1DI715BI

Digital Input 8XT1DI816BI

Digital Input 1Expander 2:XT2DI117BI

Digital Input 2XT2DI218BI

Digital Input 3XT2DI319BI

Digital Input 4XT2DI420BI

Digital Input 5XT2DI521BI

Digital Input 6XT2DI622BI

Digital Input 7XT2DI723BI

Digital Input 8XT2DI824BI

Digital Input 1Expander 3:XT3DI125BI

Digital Input 2XT3DI226BI

Digital Input 3XT3DI327BI

Digital Input 4XT3DI428BI

Digital Input 5XT3DI529BI

Digital Input 6XT3DI630BI

Digital Input 7XT3DI731BI

Digital Input 8XT3DI832BI

Digital Input 1Expander 4:XT4DI133BI

Digital Input 2XT4DI234BI

Digital Input 3XT4DI335BI

Digital Input 4XT4DI436BI

Digital Input 5XT4DI537BI

Digital Input 6XT4DI638BI

Digital Input 7XT4DI739BI

Digital Input 8XT4DI840BI

50N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Digital Input 1Expander 5:XT5DI141BI

Digital Input 2XT5DI242BI

Digital Input 3XT5DI343BI

Digital Input 4XT5DI444BI

Digital Input 5XT5DI545BI

Digital Input 6XT5DI646BI

Digital Input 7XT5DI747BI

Digital Input 8XT5DI848BI

Digital Input 1Expander 6:XT6DI149BI

Digital Input 2XT6DI250BI

Digital Input 3XT6DI351BI

Digital Input 4XT6DI452BI

Digital Input 5XT6DI553BI

Digital Input 6XT6DI654BI

Digital Input 7XT6DI755BI

Digital Input 8XT6DI856BI

Digital Input 1Expander 7:XT7DI157BI

Digital Input 2XT7DI258BI

Digital Input 3XT7DI359BI

Digital Input 4XT7DI460BI

Digital Input 5XT7DI561BI

Digital Input 6XT7DI662BI

Digital Input 7XT7DI763BI

Digital Input 8XT7DI864BI

Digital Input 1Expander 8:XT8DI165BI

Digital Input 2XT8DI266BI

Digital Input 3XT8DI367BI

Digital Input 4XT8DI468BI

Digital Input 5XT8DI569BI

Digital Input 6XT8DI670BI

Digital Input 7XT8DI771BI

Digital Input 8XT8DI872BI

Analog Output 1AO1YesYes1AO

Analog Output 2AO2YesYes2AO

Analog Output 9AO9YesYes3AO

Analog Output 10AO10YesYes4AO

Analog Output 11AO11YesYes5AO

Analog Output 12AO12YesYes6AO

51N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Analog Output 13AO13YesYes7AO

Analog Output 14AO14YesYes8AO

Analog Output 1Expander 1:XT1AO1YesYes9AO

Analog Output 2XT1AO2YesYes10AO

Analog Output 3XT1AO3YesYes11AO

Analog Output 4XT1AO4YesYes12AO

Analog Output 5XT1AO5YesYes13AO

Analog Output 6XT1AO6YesYes14AO

Analog Output 7XT1AO7YesYes15AO

Analog Output 8XT1AO8YesYes16AO

Analog Output 1Expander 2:XT2AO1YesYes17AO

Analog Output 2XT2AO2YesYes18AO

Analog Output 3XT2AO3YesYes19AO

Analog Output 4XT2AO4YesYes20AO

Analog Output 5XT2AO5YesYes21AO

Analog Output 6XT2AO6YesYes22AO

Analog Output 7XT2AO7YesYes23AO

Analog Output 8XT2AO8YesYes24AO

Analog Output 1Expander 3:XT2AO1YesYes25AO

Analog Output 2XT3AO2YesYes26AO

Analog Output 3XT3AO3YesYes27AO

Analog Output 4XT3AO4YesYes28AO

Analog Output 5XT3AO5YesYes29AO

Analog Output 6XT3AO6YesYes30AO1

Analog Output 7XT3AO7YesYes31AO

Analog Output 8XT3AO8YesYes32AO

Analog Output 1Expander 4:XT4AO1YesYes33AO1

Analog Output 2XT4AO2YesYes34AO1

Analog Output 3XT4AO3YesYes35AO1

Analog Output 4XT4AO4YesYes36AO1

Analog Output 5XT4AO5YesYes37AO1

Analog Output 6XT4AO6YesYes38AO1

Analog Output 7XT4AO7YesYes39AO

Analog Output 8XT4AO8YesYes40AO

52N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Analog Output 1Expander 5:XT5AO1YesYes41AO1

Analog Output 2XT5AO2YesYes42AO1

Analog Output 3XT5AO3YesYes43AO1

Analog Output 4XT5AO4YesYes44AO1

Analog Output 5XT5AO5YesYes45AO1

Analog Output 6XT5AO6YesYes46AO1

Analog Output 7XT5AO7YesYes47AO

Analog Output 8XT5AO8YesYes48AO

Analog Output 1Expander 6:XT6AO1YesYes49AO1

Analog Output 2XT6AO2YesYes50AO1

Analog Output 3XT6AO3YesYes51AO1

Analog Output 4XT6AO4YesYes52AO1

Analog Output 5XT6AO5YesYes53AO1

Analog Output 6XT6AO6YesYes54AO1

Analog Output 7XT6AO7YesYes55AO

Analog Output 8XT6AO8YesYes56AO

Analog Output 1Expander 7:XT7AO1YesYes57AO1

Analog Output 2XT7AO2YesYes58AO1

Analog Output 3XT7AO3YesYes59AO1

Analog Output 4XT7AO4YesYes60AO1

Analog Output 5XT7AO5YesYes61AO1

Analog Output 6XT7AO6YesYes62AO1

Analog Output 7XT7AO7YesYes63AO

Analog Output 8XT7AO8YesYes64AO

Analog Output 1Expander 8:XT8AO1YesYes65AO1

Analog Output 2XT8AO2YesYes66AO1

Analog Output 3XT8AO3YesYes67AO1

Analog Output 4XT8AO4YesYes68AO1

Analog Output 5XT8AO5YesYes69AO1

Analog Output 6XT8AO6YesYes70AO1

Analog Output 7XT8AO7YesYes71AO

Analog Output 8XT8AO8YesYes72AO

Shut Off ModeSOFFYes1BO

Start Up ModeSTUPYes2BO

53N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Digital Output 3DO3YesYes3BO

Digital Output 4DO4YesYes4BO

Digital Output 5DO5YesYes5BO

Digital Output 6DO6YesYes6BO

Digital Output 7DO7YesYes7BO

Digital Output 8DO8YesYes8BO

Digital Output 1Expander 1:XT1DO1YesYes9BO

Digital Output 2XT1DO2YesYes10BO

Digital Output 3XT1DO3YesYes11BO

Digital Output 4XT1DO4YesYes12BO

Digital Output 5XT1DO5YesYes13BO

Digital Output 6XT1DO6YesYes14BO

Digital Output 7XT1DO7YesYes15BO

Digital Output 8XT1DO8YesYes16BO

Digital Output 1Expander 2:XT2DO1YesYes17BO

Digital Output 2XT2DO2YesYes18BO

Digital Output 3XT2DO3YesYes19BO

Digital Output 4XT2DO4YesYes20BO

Digital Output 5XT2DO5YesYes21BO

Digital Output 6XT2DO6YesYes22BO

Digital Output 7XT2DO7YesYes23BO

Digital Output 8XT2DO8YesYes24BO

Digital Output 1Expander 3:XT3DO1YesYes25BO

Digital Output 2XT3DO2YesYes26BO

Digital Output 3XT3DO3YesYes27BO

Digital Output 4XT3DO4YesYes28BO

Digital Output 5XT3DO5YesYes29BO

Digital Output 6XT3DO6YesYes30BO

Digital Output 7XT3DO7YesYes31BO

Digital Output 8XT3DO8YesYes32BO

Digital Output 1Expander 4:XT4DO1YesYes33BO

Digital Output 2XT4DO2YesYes34BO

Digital Output 3XT4DO3YesYes35BO

Digital Output 4XT4DO4YesYes36BO

Digital Output 5XT4DO5YesYes37BO

Digital Output 6XT4DO6YesYes38BO

Digital Output 7XT4DO7YesYes39BO

Digital Output 8XT4DO8YesYes40BO

54N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Digital Output 1Expander 5:XT5DO1YesYes41BO

Digital Output 2XT5DO2YesYes42BO

Digital Output 3XT5DO3YesYes43BO

Digital Output 4XT5DO4YesYes44BO

Digital Output 5XT5DO5YesYes45BO

Digital Output 6XT5DO6YesYes46BO

Digital Output 7XT5DO7YesYes47BO

Digital Output 8XT5DO8YesYes48BO

Digital Output 1Expander 6:XT6DO1YesYes49BO

Digital Output 2XT6DO2YesYes50BO

Digital Output 3XT6DO3YesYes51BO

Digital Output 4XT6DO4YesYes52BO

Digital Output 5XT6DO5YesYes53BO

Digital Output 6XT6DO6YesYes54BO

Digital Output 7XT6DO7YesYes55BO

Digital Output 8XT6DO8YesYes56BO

Digital Output 1Expander 7:XT7DO1YesYes57BO

Digital Output 2XT7DO2YesYes58BO

Digital Output 3XT7DO3YesYes59BO

Digital Output 4XT7DO4YesYes60BO

Digital Output 5XT7DO5YesYes61BO

Digital Output 6XT7DO6YesYes62BO

Digital Output 7XT7DO7YesYes63BO

Digital Output 8XT7DO8YesYes64BO

Digital Output 1Expander 8:XT8DO1YesYes65BO

Digital Output 2XT8DO2YesYes66BO

Digital Output 3XT8DO3YesYes67BO

Digital Output 4XT8DO4YesYes68BO

Digital Output 5XT8DO5YesYes69BO

Digital Output 6XT8DO6YesYes70BO

Digital Output 7XT8DO7YesYes71BO

Digital Output 8XT8DO8YesYes72BO

Analog Constant 1ACO1Yes1ADF

Analog Constant 2ACO2Yes2ADF

Analog Constant 3ACO3Yes3ADF

Analog Constant 4ACO4Yes4ADF

Analog Constant 5ACO5Yes5ADF

Analog Constant 6ACO6Yes6ADF

55N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Analog Constant 7ACO7Yes7ADF

Analog Constant 8ACO8Yes8ADF

DI1 Pulse CountCNT1Yes1ADI

DI2 Pulse CountCNT2Yes2ADI

DI3 Pulse CountCNT3Yes3ADI

DI4 Pulse CountCNT4Yes4ADI

DI5 Pulse CountCNT5Yes5ADI

DI6 Pulse CountCNT6Yes6ADI

DI7 Pulse CountCNT7Yes7ADI

DI8 Pulse CountCNT8Yes8ADI

DI1 Pulse CountExpander 1:XT1CNT1Yes9ADI

DI2 Pulse CountXT1CNT2Yes10ADI

DI3 Pulse CountXT1CNT3Yes11ADI

DI4 Pulse CountXT1CNT4Yes12ADI

DI5 Pulse CountXT1CNT5Yes13ADI

DI6 Pulse CountXT1CNT6Yes14ADI

DI7 Pulse CountXT1CNT7Yes15ADI

DI8 Pulse CountXT1CNT8Yes16ADI

DI1 Pulse CountExpander 2:XT2CNT1Yes17ADI

DI2 Pulse CountXT2CNT2Yes18ADI

DI3 Pulse CountXT2CNT3Yes19ADI

DI4 Pulse CountXT2CNT4Yes20ADI

DI5 Pulse CountXT2CNT5Yes21ADI

DI6 Pulse CountXT2CNT6Yes22ADI

DI7 Pulse CountXT2CNT7Yes23ADI

DI8 Pulse CountXT2CNT8Yes24ADI

DI1 Pulse CountExpander 3:XT3CNT1Yes25ADI

DI2 Pulse CountXT3CNT2Yes26ADI

DI3 Pulse CountXT3CNT3Yes27ADI

DI4 Pulse CountXT3CNT4Yes28ADI

DI5 Pulse CountXT3CNT5Yes29ADI

DI6 Pulse CountXT3CNT6Yes30ADI

DI7 Pulse CountXT3CNT7Yes31ADI

DI8 Pulse CountXT3CNT8Yes32ADI

56N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

DI1 Pulse CountExpander 4:XT4CNT1Yes33ADI

DI2 Pulse CountXT4CNT2Yes34ADI

DI3 Pulse CountXT4CNT3Yes35ADI

DI4 Pulse CountXT4CNT4Yes36ADI

DI5 Pulse CountXT4CNT5Yes37ADI

DI6 Pulse CountXT4CNT6Yes38ADI

DI7 Pulse CountXT4CNT7Yes39ADI

DI8 Pulse CountXT4CNT8Yes40ADI

DI1 Pulse CountExpander 5:XT5CNT1Yes41ADI

DI2 Pulse CountXT5CNT2Yes42ADI

DI3 Pulse CountXT5CNT3Yes43ADI

DI4 Pulse CountXT5CNT4Yes44ADI

DI5 Pulse CountXT5CNT5Yes45ADI

DI6 Pulse CountXT5CNT6Yes46ADI

DI7 Pulse CountXT5CNT7Yes47ADI

DI8 Pulse CountXT5CNT8Yes48ADI

DI1 Pulse CountExpander 6:XT6CNT1Yes49ADI

DI2 Pulse CountXT6CNT2Yes50ADI

DI3 Pulse CountXT6CNT3Yes51ADI

DI4 Pulse CountXT6CNT4Yes52ADI

DI5 Pulse CountXT6CNT5Yes53ADI

DI6 Pulse CountXT6CNT6Yes54ADI

DI7 Pulse CountXT6CNT7Yes55ADI

DI8 Pulse CountXT6CNT8Yes56ADI

DI1 Pulse CountExpander 7:XT7CNT1Yes57ADI

DI2 Pulse CountXT7CNT2Yes58ADI

DI3 Pulse CountXT7CNT3Yes59ADI

DI4 Pulse CountXT7CNT4Yes60ADI

DI5 Pulse CountXT7CNT5Yes61ADI

DI6 Pulse CountXT7CNT6Yes62ADI

DI7 Pulse CountXT7CNT7Yes63ADI

DI8 Pulse CountXT7CNT8Yes64ADI

57N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

DI1 Pulse CountExpander 8:XT8CNT1Yes65ADI

DI2 Pulse CountXT8CNT2Yes66ADI

DI3 Pulse CountXT8CNT3Yes67ADI

DI4 Pulse CountXT8CNT4Yes68ADI

DI5 Pulse CountXT8CNT5Yes69ADI

DI6 Pulse CountXT8CNT6Yes70ADI

DI7 Pulse CountXT8CNT7Yes71ADI

DI8 Pulse CountXT8CNT8Yes72ADI

Logic Constant 1DCO1Yes1BD

Logic Constant 2DCO2Yes2BD

Logic Constant 3DCO3Yes3BD

Logic Constant 4DCO4Yes4BD

Logic Constant 5DCO5Yes5BD

Logic Constant 6DCO6Yes6BD

Logic Constant 7DCO7Yes7BD

Logic Constant 8DCO8Yes8BD

Logic Constant 9DCO9Yes9BD

Logic Constant 10DCO10Yes10BD

Logic Constant 11DCO11Yes11BD

Logic Constant 12DCO12Yes12BD

Logic Constant 13DCO13Yes13BD

Logic Constant 14DCO14Yes14BD

Logic Constant 15DCO15Yes15BD

Logic Constant 16DCO16Yes16BD

Logic Constant 17DCO17Yes17BD

Logic Constant 18DCO18Yes18BD

Logic Constant 19DCO19Yes19BD

Logic Constant 20DCO20Yes20BD

Logic Constant 21DCO21Yes21BD

Logic Constant 22DCO22Yes22BD

Logic Constant 23DCO23Yes23BD

Logic Constant 24DCO24Yes24BD

Logic Constant 25DCO25Yes25BD

Logic Constant 26DCO26Yes26BD

Logic Constant 27DCO27Yes27BD

Logic Constant 28DCO28Yes28BD

Logic Constant 29DCO29Yes29BD

Logic Constant 30DCO30Yes30BD

58N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Logic Constant 31DCO31Yes31BD

Logic Constant 32DCO32Yes32BD

Logic Result 1LRS11LRS

Logic Result 2LRS22LRS

Logic Result 3LRS33LRS

Logic Result 4LRS44LRS

Logic Result 5LRS55LRS

Logic Result 6LRS66LRS

Logic Result 7LRS77LRS

Logic Result 8LRS88LRS

Logic Result 9LRS99LRS

Logic Result 10LRS1010LRS

Logic Result 11LRS1111LRS

Logic Result 12LRS1212LRS

Logic Result 13LRS1313LRS

Logic Result 14LRS1414LRS

Logic Result 15LRS1515LRS

Logic Result 16LRS1616LRS

Logic Result 17LRS1717LRS

Logic Result 18LRS1818LRS

Logic Result 19LRS1919LRS

Logic Result 20LRS2020LRS

Logic Result 21LRS2121LRS

Logic Result 22LRS2222LRS

Logic Result 23LRS2323LRS

Logic Result 24LRS2424LRS

Logic Result 25LRS2525LRS

Logic Result 26LRS2626LRS

Logic Result 27LRS2727LRS

Logic Result 28LRS2828LRS

Logic Result 29LRS2929LRS

Logic Result 30LRS3030LRS

Logic Result 31LRS3131LRS

Logic Result 32LRS3232LRS

Logic Result 33LRS3333LRS

Logic Result 34LRS3434LRS

Logic Result 35LRS3535LRS

Logic Result 36LRS3636LRS

59N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Logic Result 37LRS3737LRS

Logic Result 38LRS3838LRS

Logic Result 39LRS3939LRS

Logic Result 40LRS4040LRS

Logic Result 41LRS4141LRS

Logic Result 42LRS4242LRS

Logic Result 43LRS4343LRS

Logic Result 44LRS4444LRS

Logic Result 45LRS4545LRS

Logic Result 46LRS4646LRS

Logic Result 47LRS4747LRS

Logic Result 48LRS4848LRS

Logic Result 49LRS4949LRS

Logic Result 50LRS5050LRS

Logic Result 51LRS5151LRS

Logic Result 52LRS5252LRS

Logic Result 53LRS5353LRS

Logic Result 54LRS5454LRS

Logic Result 55LRS5555LRS

Logic Result 56LRS5656LRS

Logic Result 57LRS5757LRS

Logic Result 58LRS5858LRS

Logic Result 59LRS5959LRS

Logic Result 60LRS6060LRS

Logic Result 61LRS6161LRS

Logic Result 62LRS6262LRS

Logic Result 63LRS6363LRS

Logic Result 64LRS6464LRS

60N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 1Constant:

PM1K1Yes1PMK

K2PM1K2Yes2PMK

K3PM1K3Yes3PMK

K4PM1K4Yes4PMK

K5PM1K5Yes5PMK

K6PM1K6Yes6PMK

K7PM1K7Yes7PMK

K8PM1K8Yes8PMK

K9PM1K9Yes9PMK

K10PM1K10Yes10PMK

K11PM1K11Yes11PMK

K12PM1K12Yes12PMK

K13PM1K13Yes13PMK

K14PM1K14Yes14PMK

K15PM1K15Yes15PMK

K16PM1K16Yes16PMK

K17PM1K17Yes17PMK

K18PM1K18Yes18PMK

K19PM1K19Yes19PMK

K20PM1K20Yes20PMK

K1Module 2Constant:

PM2K1Yes21PMK

K2PM2K2Yes22PMK

K3PM2K3Yes23PMK

K4PM2K4Yes24PMK

K5PM2K5Yes25PMK

K6PM2K6Yes26PMK

K7PM2K7Yes27PMK

K8PM2K8Yes28PMK

K9PM2K9Yes29PMK

K10PM2K10Yes30PMK

K11PM2K11Yes31PMK

K12PM2K12Yes32PMK

K13PM2K13Yes33PMK

K14PM2K14Yes34PMK

K15PM2K15Yes35PMK

K16PM2K16Yes36PMK

61N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K17Module 2Constant:

PM2K17Yes37PMK

K18PM2K18Yes38PMK

K19PM2K19Yes39PMK

K20PM2K20Yes40PMK

K1Module 3Constant:

PM3K1Yes41PMK

K2PM3K2Yes42PMK

K3PM3K3Yes43PMK

K4PM3K4Yes44PMK

K5PM3K5Yes45PMK

K6PM3K6Yes46PMK

K7PM3K7Yes47PMK

K8PM3K8Yes48PMK

K9PM3K9Yes49PMK

K10PM3K10Yes50PMK

K11PM3K11Yes51PMK

K12PM3K12Yes52PMK

K13PM3K13Yes53PMK

K14PM3K14Yes54PMK

K15PM3K15Yes55PMK

K16PM3K16Yes56PMK

K17PM3K17Yes57PMK

K18PM3K18Yes58PMK

K19PM3K19Yes59PMK

K20PM3K20Yes60PMK

62N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 4Constant:

PM4K1Yes61PMK

K2PM4K2Yes62PMK

K3PM4K3Yes63PMK

K4PM4K4Yes64PMK

K5PM4K5Yes65PMK

K6PM4K6Yes66PMK

K7PM4K7Yes67PMK

K8PM4K8Yes68PMK

K9PM4K9Yes69PMK

K10PM4K10Yes70PMK

K11PM4K11Yes71PMK

K12PM4K12Yes72PMK

K13PM4K13Yes73PMK

K14PM4K14Yes74PMK

K15PM4K15Yes75PMK

K16PM4K16Yes76PMK

K17PM4K17Yes77PMK

K18Module 4Constant:

PM4K18Yes78PMK

K19PM4K19Yes79PMK

K20PM4K20Yes80PMK

63N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 5Constant:

PM5K1Yes81PMK

K2PM5K2Yes82PMK

K3PM5K3Yes83PMK

K4PM5K4Yes84PMK

K5PM5K5Yes85PMK

K6PM5K6Yes86PMK

K7PM5K7Yes87PMK

K8PM5K8Yes88PMK

K9PM5K9Yes89PMK

K10PM5K10Yes90PMK

K11PM5K11Yes91PMK

K12PM5K12Yes92PMK

K13PM5K13Yes93PMK

K14PM5K14Yes94PMK

K15PM5K15Yes95PMK

K16PM5K16Yes96PMK

K17PM5K17Yes97PMK

K18PM5K18Yes98PMK

K19PM5K19Yes99PMK

K20PM5K20Yes100PMK

K1Module 6Constant:

PM6K1Yes101PMK

K2PM6K2Yes102PMK

K3PM6K3Yes103PMK

K4PM6K4Yes104PMK

K5PM6K5Yes105PMK

K6PM6K6Yes106PMK

K7PM6K7Yes107PMK

K8PM6K8Yes108PMK

K9PM6K9Yes109PMK

K10PM6K10Yes110PMK

K11PM6K11Yes111PMK

K12PM6K12Yes112PMK

K13PM6K13Yes113PMK

K14PM6K14Yes114PMK

K15PM6K15Yes115PMK

K16PM6K16Yes116PMK

K17PM6K17Yes117PMK

64N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K18Module 6Constant:

PM6K18Yes118PMK

K19PM6K19Yes119PMK

K20PM6K20Yes120PMK

K1Module 7Constant:

PM7K1Yes121PMK

K2PM7K2Yes122PMK

K3PM7K3Yes123PMK

K4PM7K4Yes124PMK

K5PM7K5Yes125PMK

K6PM7K6Yes126PMK

K7PM7K7Yes127PMK

K8PM7K8Yes128PMK

K9PM7K9Yes129PMK

K10PM7K10Yes130PMK

K11PM7K11Yes131PMK

K12PM7K12Yes132PMK

K13PM7K13Yes133PMK

K14PM7K14Yes113PMK

K15PM7K15Yes135PMK

K16PM7K16Yes136PMK

K17PM7K17Yes137PMK

K18PM7K18Yes138PMK

K19PM7K19Yes139PMK

K20PM7K20Yes140PMK

65N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 8Constant:

PM8K1Yes141PMK

K2PM8K2Yes142PMK

K3PM8K3Yes143PMK

K4PM8K4Yes144PMK

K5PM8K5Yes145PMK

K6PM8K6Yes146PMK

K7PM8K7Yes147PMK

K8PM8K8Yes148PMK

K9PM8K9Yes149PMK

K10PM8K10Yes150PMK

K11PM8K11Yes151PMK

K12PM8K12Yes152PMK

K13PM8K13Yes153PMK

K14PM8K14Yes154PMK

K15PM8K15Yes155PMK

K16PM8K16Yes156PMK

K17PM8K17Yes157PMK

K18PM8K18Yes158PMK

K19Module 8Constant:

PM8K19Yes159PMK

K20PM8K20Yes160PMK

66N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 9Constant:

PM9K1Yes161PMK

K2PM9K2Yes162PMK

K3PM9K3Yes163PMK

K4PM9K4Yes164PMK

K5PM9K5Yes165PMK

K6PM9K6Yes166PMK

K7PM9K7Yes167PMK

K8PM9K8Yes168PMK

K9PM9K9Yes169PMK

K10PM9K10Yes170PMK

K11PM9K11Yes171PMK

K12PM9K12Yes172PMK

K13PM9K13Yes173PMK

K14PM9K14Yes174PMK

K15PM9K15Yes175PMK

K16PM9K16Yes176PMK

K17PM9K17Yes177PMK

K18PM9K18Yes178PMK

K19PM9K19Yes179PMK

K20PM9K20Yes180PMK

67N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 10Constant:

PM10K1Yes181PMK

K2PM10K2Yes182PMK

K3PM10K3Yes183PMK

K4PM10K4Yes184PMK

K5PM10K5Yes185PMK

K6PM10K6Yes186PMK

K7PM10K7Yes187PMK

K8PM10K8Yes188PMK

K9PM10K9Yes189PMK

K10PM10K10Yes190PMK

K11PM10K11Yes191PMK

K12PM10K12Yes192PMK

K13PM10K13Yes193PMK

K14PM10K14Yes194PMK

K15PM10K15Yes195PMK

K16PM10K16Yes196PMK

K17PM10K17Yes197PMK

K18PM10K18Yes198PMK

K19PM10K19Yes199PMK

K20PM10K20Yes200PMK

68N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 11Constant:

PM11K1Yes201PMK

K2PM11K2Yes202PMK

K3PM11K3Yes203PMK

K4PM11K4Yes204PMK

K5PM11K5Yes205PMK

K6PM11K6Yes206PMK

K7PM11K7Yes207PMK

K8PM11K8Yes208PMK

K9PM11K9Yes209PMK

K10PM11K10Yes210PMK

K11PM11K11Yes211PMK

K12PM11K12Yes212PMK

K13PM11K13Yes213PMK

K14PM11K14Yes214PMK

K15PM11K15Yes215PMK

K16PM11K16Yes216PMK

K17PM11K17Yes217PMK

K18PM11K18Yes218PMK

K19PM11K19Yes219PMK

K20PM11K20Yes220PMK

69N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

K1Module 12Constant:

PM12K1Yes221PMK

K2PM12K2Yes222PMK

K3PM12K3Yes223PMK

K4PM12K4Yes224PMK

K5PM12K5Yes225PMK

K6PM12K6Yes226PMK

K7PM12K7Yes227PMK

K8PM12K8Yes228PMK

K9PM12K9Yes229PMK

K10PM12K10Yes230PMK

K11PM12K11Yes231PMK

K12PM12K12Yes232PMK

K13PM12K13Yes233PMK

K14PM12K14Yes234PMK

K15PM12K15Yes235PMK

K16PM12K16Yes236PMK

K17PM12K17Yes237PMK

K18PM12K18Yes238PMK

K19PM12K19Yes239PMK

K20PM12K20Yes240PMK

Channel 1Module 1 Output:PM1OU1YesYes1PMO

Channel 2PM1OU2YesYes2PMO

Channel 3PM1OU3YesYes3PMO

Channel 4PM1OU4YesYes4PMO

Channel 5PM1OU5YesYes5PMO

Channel 6PM1OU6YesYes6PMO

Channel 7PM1OU7YesYes7PMO

Channel 8PM1OU8YesYes8PMO

Channel 1Module 2 Output:PM2OU1YesYes9PMO

Channel 2PM2OU2YesYes10PMO

Channel 3PM2OU3YesYes11PMO

Channel 4PM2OU4YesYes12PMO

Channel 5PM2OU5YesYes13PMO

Channel 6PM2OU6YesYes14PMO

Channel 7PM2OU7YesYes15PMO

Channel 8PM2OU8YesYes16PMO

70N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 3 Output:PM3OU1YesYes17PMO

Channel 2PM3OU2YesYes18PMO

Channel 3PM3OU3YesYes19PMO

Channel 4PM3OU4YesYes20PMO

Channel 5PM3OU5YesYes21PMO

Channel 6PM3OU6YesYes22PMO

Channel 7PM3OU7YesYes23PMO

Channel 8PM3OU8YesYes24PMO

Channel 1Module 4 Output:PM4OU1YesYes25PMO

Channel 2PM4OU2YesYes26PMO

Channel 3PM4OU3YesYes27PMO

Channel 4PM4OU4YesYes28PMO

Channel 5PM4OU5YesYes29PMO

Channel 6PM4OU6YesYes30PMO

Channel 7PM4OU7YesYes31PMO

Channel 8PM4OU8YesYes32PMO

Channel 1Module 5 Output:PM5OU1YesYes33PMO

Channel 2PM5OU2YesYes34PMO

Channel 3PM5OU3YesYes35PMO

Channel 4PM5OU4YesYes36PMO

Channel 5PM5OU5YesYes37PMO

Channel 6PM5OU6YesYes38PMO

Channel 7PM5OU7YesYes39PMO

Channel 8PM5OU8YesYes40PMO

Channel 1Module 6 Output:PM6OU1YesYes41PMO

Channel 2PM6OU2YesYes42PMO

Channel 3PM6OU3YesYes43PMO

Channel 4PM6OU4YesYes44PMO

Channel 5PM6OU5YesYes45PMO

Channel 6PM6OU6YesYes46PMO

Channel 7PM6OU7YesYes47PMO

Channel 8PM6OU8YesYes48PMO

71N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 7 Output:PM7OU1YesYes49PMO

Channel 2PM7OU2YesYes50PMO

Channel 3PM7OU3YesYes51PMO

Channel 4PM7OU4YesYes52PMO

Channel 5PM7OU5YesYes53PMO

Channel 6PM7OU6YesYes54PMO

Channel 7PM7OU7YesYes55PMO

Channel 8PM7OU8YesYes56PMO

Channel 1Module 8 Output:PM8OU1YesYes57PMO

Channel 2PM8OU2YesYes58PMO

Channel 3PM8OU3YesYes59PMO

Channel 4PM8OU4YesYes60PMO

Channel 5PM8OU5YesYes61PMO

Channel 6PM8OU6YesYes62PMO

Channel 7PM8OU7YesYes63PMO

Channel 8PM8OU8YesYes64PMO

Channel 1Module 9 Output:PM9OU1YesYes65PMO

Channel 2PM9OU2YesYes66PMO

Channel 3PM9OU3YesYes67PMO

Channel 4PM9OU4YesYes68PMO

Channel 5PM9OU5YesYes69PMO

Channel 6PM9OU6YesYes70PMO

Channel 7PM9OU7YesYes71PMO

Channel 8PM9OU8YesYes72PMO

Channel 1Module 10Output:

PM10OU1YesYes73PMO

Channel 2PM10OU2YesYes74PMO

Channel 3PM10OU3YesYes75PMO

Channel 4PM10OU4YesYes76PMO

Channel 5PM10OU5YesYes77PMO

Channel 6PM10OU6YesYes78PMO

Channel 7PM10OU7YesYes79PMO

Channel 8PM10OU8YesYes80PMO

72N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 11Output:

PM11OU1YesYes81PMO

Channel 2PM11OU2YesYes82PMO

Channel 3PM11OU3YesYes83PMO

Channel 4PM11OU4YesYes84PMO

Channel 5PM11OU5YesYes85PMO

Channel 6PM11OU6YesYes86PMO

Channel 7PM11OU7YesYes87PMO

Channel 8PM11OU8YesYes88PMO

Channel 1Module 12Output:

PM12OU1YesYes89PMO

Channel 2PM12OU2YesYes90PMO

Channel 3PM12OU3YesYes91PMO

Channel 4PM12OU4YesYes92PMO

Channel 5PM12OU5YesYes93PMO

Channel 6PM12OU6YesYes94PMO

Channel 7PM12OU7YesYes95PMO

Channel 8PM12OU8YesYes96PMO

Channel 1Module 1 LogicOutput:

PM1DO1YesYes1PML

Channel 2PM1DO2YesYes2PML

Channel 3PM1DO3YesYes3PML

Channel 4PM1DO4YesYes4PML

Channel 5PM1DO5YesYes5PML

Channel 6PM1DO6YesYes6PML

Channel 7PM1DO7YesYes7PML

Channel 8PM1DO8YesYes8PML

Channel 1PM2DO1YesYes9PML

Channel 2Module 2 LogicOutput:

PM2DO2YesYes10PML

Channel 3PM2DO3YesYes11PML

Channel 4PM2DO4YesYes12PML

Channel 5PM2DO5YesYes13PML

Channel 6PM2DO6YesYes14PML

Channel 7PM2DO7YesYes15PML

Channel 8PM2DO8YesYes16PML

73N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 3 LogicOutput:

PM3DO1YesYes17PML

Channel 2PM3DO2YesYes18PML

Channel 3PM3DO3YesYes19PML

Channel 4PM3DO4YesYes20PML

Channel 5PM3DO5YesYes21PML

Channel 6PM3DO6YesYes22PML

Channel 7PM3DO7YesYes23PML

Channel 8PM3DO8YesYes24PML

Channel 1Module 4 LogicOutput:

PM4DO1YesYes25PML

Channel 2PM4DO2YesYes26PML

Channel 3PM4DO3YesYes27PML

Channel 4PM4DO4YesYes28PML

Channel 5PM4DO5YesYes29PML

Channel 6PM4DO6YesYes30PML

Channel 7PM4DO7YesYes31PML

Channel 8PM4DO8YesYes32PML

Channel 1Module 5 LogicOutput:

PM5DO1YesYes33PML

Channel 2PM5DO2YesYes34PML

Channel 3PM5DO3YesYes35PML

Channel 4PM5DO4YesYes36PML

Channel 5PM5DO5YesYes37PML

Channel 6PM5DO6YesYes38PML

Channel 7PM5DO7YesYes39PML

Channel 8PM5DO8YesYes40PML

Channel 1Module 6 LogicOutput:

PM6DO1YesYes41PML

Channel 2PM6DO2YesYes42PML

Channel 3PM6DO3YesYes43PML

Channel 4PM6DO4YesYes44PML

Channel 5PM6DO5YesYes45PML

Channel 6PM6DO6YesYes46PML

Channel 7PM6DO7YesYes47PML

Channel 8PM6DO8YesYes48PML

74N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 7 LogicOutput:

PM7DO1YesYes49PML

Channel 2PM7DO2YesYes50PML

Channel 3PM7DO3YesYes51PML

Channel 4PM7DO4YesYes52PML

Channel 5PM7DO5YesYes53PML

Channel 6PM7DO6YesYes54PML

Channel 7PM7DO7YesYes55PML

Channel 8PM7DO8YesYes56PML

Channel 1Module 8 LogicOutput:

PM8DO1YesYes57PML

Channel 2PM8DO2YesYes58PML

Channel 3PM8DO3YesYes59PML

Channel 4PM8DO4YesYes60PML

Channel 5PM8DO5YesYes61PML

Channel 6PM8DO6YesYes62PML

Channel 7PM8DO7YesYes63PML

Channel 8PM8DO8YesYes64PML

Channel 1Module 9 LogicOutput:

PM9DO1YesYes65PML

Channel 2PM9DO2YesYes66PML

Channel 3PM9DO3YesYes67PML

Channel 4PM9DO4YesYes68PML

Channel 5PM9DO5YesYes69PML

Channel 6PM9DO6YesYes70PML

Channel 7PM9DO7YesYes71PML

Channel 8PM9DO8YesYes72PML

Channel 1Module 10 LogicOutput:

PM10DO1YesYes73PML

Channel 2PM10DO2YesYes74PML

Channel 3PM10DO3YesYes75PML

Channel 4PM10DO4YesYes76PML

Channel 5PM10DO5YesYes77PML

Channel 6PM10DO6YesYes78PML

Channel 7PM10DO7YesYes79PML

Channel 8PM10DO8YesYes80PML

75N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 11 LogicOutput:

PM11DO1YesYes81PML

Channel 2PM11DO2YesYes82PML

Channel 3PM11DO3YesYes83PML

Channel 4PM11DO4YesYes84PML

Channel 5PM11DO5YesYes85PML

Channel 6PM11DO6YesYes86PML

Channel 7PM11DO7YesYes87PML

Channel 8PM11DO8YesYes88PML

Channel 1Module 12 LogicOutput

PM12DO1YesYes89PML

Channel 2PM12DO2YesYes90PML

Channel 3PM12DO3YesYes91PML

Channel 4PM12DO4YesYes92PML

Channel 5PM12DO5YesYes93PML

Channel 6PM12DO6YesYes94PML

Channel 7PM12DO7YesYes95PML

Channel 8PM12DO8YesYes96PML

Channel 1Module 1Accumulator:

PM1AC1Yes1PMA

Channel 2PM1AC2Yes2PMA

Channel 3PM1AC3Yes3PMA

Channel 4PM1AC4Yes4PMA

Channel 5PM1AC5Yes5PMA

Channel 6PM1AC6Yes6PMA

Channel 7PM1AC7Yes7PMA

Channel 8PM1AC8Yes8PMA

Channel 1Module 2Accumulator:

PM2AC1Yes9PMA

Channel 2PM2AC2Yes10PMA

Channel 3PM2AC3Yes11PMA

Channel 4PM2AC4Yes12PMA

Channel 5PM2AC5Yes13PMA

Channel 6PM2AC6Yes14PMA

Channel 7PM2AC7Yes15PMA

Channel 8PM2AC8Yes16PMA

76N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 3Accumulator:

PM3AC1Yes17PMA

Channel 2PM3AC2Yes18PMA

Channel 3PM3AC3Yes19PMA

Channel 4PM3AC4Yes20PMA

Channel 5PM3AC5Yes21PMA

Channel 6PM3AC6Yes22PMA

Channel 7PM3AC7Yes23PMA

Channel 8PM3AC8Yes24PMA

Channel 1Module 4Accumulator:

PM4AC1Yes25PMA

Channel 2PM4AC2Yes26PMA

Channel 3PM4AC3Yes27PMA

Channel 4PM4AC4Yes28PMA

Channel 5PM4AC5Yes29PMA

Channel 6PM4AC6Yes30PMA

Channel 7PM4AC7Yes31PMA

Channel 8PM4AC8Yes32PMA

Channel 1Module 5Accumulator:

PM5AC1Yes33PMA

Channel 2PM5AC2Yes34PMA

Channel 3PM5AC3Yes35PMA

Channel 4PM5AC4Yes36PMA

Channel 5PM5AC5Yes37PMA

Channel 6PM5AC6Yes38PMA

Channel 7PM5AC7Yes39PMA

Channel 8PM5AC8Yes40PMA

Channel 1Module 6Accumulator:

PM6AC1Yes41PMA

Channel 2PM6AC2Yes42PMA

Channel 3PM6AC3Yes43PMA

Channel 4PM6AC4Yes44PMA

Channel 5PM6AC5Yes45PMA

Channel 6PM6AC6Yes46PMA

Channel 7PM6AC7Yes47PMA

Channel 8PM6AC8Yes48PMA

77N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 7Accumulator:

PM7AC1Yes49PMA

Channel 2PM7AC2Yes50PMA

Channel 3PM7AC3Yes51PMA

Channel 4PM7AC4Yes52PMA

Channel 5PM7AC5Yes53PMA

Channel 6PM7AC6Yes54PMA

Channel 7PM7AC7Yes55PMA

Channel 8PM7AC8Yes56PMA

Channel 1Module 8Accumulator:

PM8AC1Yes57PMA

Channel 2PM8AC2Yes58PMA

Channel 3PM8AC3Yes59PMA

Channel 4PM8AC4Yes60PMA

Channel 5PM8AC5Yes61PMA

Channel 6PM8AC6Yes62PMA

Channel 7PM8AC7Yes63PMA

Channel 8PM8AC8Yes64PMA

Channel 1Module 9Accumulator:

PM9AC1Yes65PMA

Channel 2PM9AC2Yes66PMA

Channel 3PM9AC3Yes67PMA

Channel 4PM9AC4Yes68PMA

Channel 5PM9AC5Yes69PMA

Channel 6PM9AC6Yes70PMA

Channel 7PM9AC7Yes71PMA

Channel 8PM9AC8Yes72PMA

Channel 1Module 10Accumulator:

PM10AC1Yes73PMA

Channel 2PM10AC2Yes74PMA

Channel 3PM10AC3Yes75PMA

Channel 4PM10AC4Yes76PMA

Channel 5PM10AC5Yes77PMA

Channel 6PM10AC6Yes78PMA

Channel 7PM10AC7Yes79PMA

Channel 8PM10AC8Yes80PMA

78N2 Integration with the NAE Technical Bulletin

Table 22: DX-9100 Point Mapping (Detail)Item DescriptionTag NameOverride

StatusCommandAllowed

Network PointAddress

Network PointType

Channel 1Module 11Accumulator:

PM11AC1Yes81PMA

Channel 2PM11AC2Yes82PMA

Channel 3PM11AC3Yes83PMA

Channel 4PM11AC4Yes84PMA

Channel 5PM11AC5Yes85PMA

Channel 6PM11AC6Yes86PMA

Channel 7PM11AC7Yes87PMA

Channel 8PM11AC8Yes88PMA

Channel 1Module 12Accumulator:

PM12AC1Yes89PMA

Channel 2PM12AC2Yes90PMA

Channel 3PM12AC3Yes91PMA

Channel 4PM12AC4Yes92PMA

Channel 5PM12AC5Yes93PMA

Channel 6PM12AC6Yes94PMA

Channel 7PM12AC7Yes95PMA

Channel 8PM12AC8Yes96PMA

1 Applies to European installations only.

Extension Module (XTM and XT)Table 23 and Table 24 show point mapping for the XTM or XT. Table 23 shows how XTM or XT points can map toNAE objects. Table 24 provides more detail about the XTM and XT points (for example, tag names, item descriptions,and which points are commandable).

Override Status is not supported for any points in the XTM or XT, and the Manual Status of Outputs is available onlyfrom the XTM.

These tables are used for XTM-105 or XT-9100 modules on the N2 Bus. For XTM-905 or XT-9100 modules on aDX-9100 XT Bus, see the two DX-9100 tables, Table 21 and Table 22.

Table 23: XTM (or XT) Point Mapping to the NAEDescriptionCan Map to NAE

ObjectsOverrideStatus

CommandAllowed

Network PointAddress

Network PointType

AINo1-8AI

BINo1-16BI

AONoYes1-8AO

BONoYes1-16BO

Writes restricted to0-32767. Only AO pointsare commandable in theNAE.

AI, PC, AONoYes1-8ADI

Auto/Manual Flags forOutputs.

BINo1-24BD

79N2 Integration with the NAE Technical Bulletin

Table 24: XTM (or XT) Point Mapping (Detail)Item DescriptionTag NameCommand

AllowedNetwork PointAddress

Network PointType

Analog Input 1XP0:AI11AI

Analog Input 2AI22AI

Analog Input 3AI33AI

Analog Input 4AI44AI

Analog Input 5AI55AI

Analog Input 6AI66AI

Analog Input 7AI77AI

Analog Input 8AI88AI

Binary Input 1XP1:1DI11BI

Binary Input 21DI22BI

Binary Input 31DI33BI

Binary Input 41DI44BI

Binary Input 51DI55BI

Binary Input 61DI66BI

Binary Input 71DI77BI

Binary Input 81DI88BI

Binary Input 81DI88BI

Binary Input 1XP2:2DI19BI

Binary Input 22DI210BI

Binary Input 32DI311BI

Binary Input 42DI412BI

Binary Input 52DI513BI

Binary Input 62DI614BI

Binary Input 72DI715BI

Binary Input 82DI816BI

Analog Output 1XP0:AO1Yes1AO

Analog Output 2AO2Yes2AO

Analog Output 3AO3Yes3AO

Analog Output 4AO4Yes4AO

Analog Output 5AO5Yes5AO

Analog Output 6AO6Yes6AO

Analog Output 7AO7Yes7AO

Analog Output 8AO8Yes8AO

80N2 Integration with the NAE Technical Bulletin

Table 24: XTM (or XT) Point Mapping (Detail)Item DescriptionTag NameCommand

AllowedNetwork PointAddress

Network PointType

Binary Output 1XP1:1DO1Yes1BO

Binary Output 21DO2Yes2BO

Binary Output 31DO3Yes3BO

Binary Output 41DO4Yes4BO

Binary Output 51DO5Yes5BO

Binary Output 61DO6Yes6BO

Binary Output 71DO7Yes7BO

Binary Output 81DO8Yes8BO

Binary Output 1XP2:2DO1Yes9BO

Binary Output 22DO2Yes10BO

Binary Output 32DO3Yes11BO

Binary Output 42DO4Yes12BO

Binary Output 52DO5Yes13BO

Binary Output 62DO6Yes14BO

Binary Output 72DO7Yes15BO

Binary Output 82DO8Yes16BO

DI1 Pulse CountXTS:CNT1Yes1ADI

DI2 Pulse CountCNT2Yes2ADI

DI3 Pulse CountCNT3Yes3ADI

DI4 Pulse CountCNT4Yes4ADI

DI5 Pulse CountCNT5Yes5ADI

DI6 Pulse CountCNT6Yes6ADI

DI7 Pulse CountCNT7Yes7ADI

DI8 Pulse CountCNT8Yes8ADI

The following Tag Names are available only in the XTM:

Binary Output 1Manual Status

XP1:1DOM11BD

Binary Output 2Manual Status

1DOM22BD

Binary Output 3Manual Status

1DOM33BD

Binary Output 4Manual Status

1DOM44BD

Binary Output 5Manual Status

1DOM55BD

Binary Output 6Manual Status

1DOM66BD

Binary Output 7Manual Status

1DOM77BD

Binary Output 8Manual Status

1DOM88BD

81N2 Integration with the NAE Technical Bulletin

Table 24: XTM (or XT) Point Mapping (Detail)Item DescriptionTag NameCommand

AllowedNetwork PointAddress

Network PointType

Binary Output 1Manual Status

XP2:2DOM19BD

Binary Output 2Manual Status

2DOM210BD

Binary Output 3Manual Status

2DOM311BD

Binary Output 4Manual Status

2DOM412BD

Binary Output 5Manual Status

2DOM513BD

Binary Output 6Manual Status

2DOM614BD

Binary Output 7Manual Status

2DOM715BD

Binary Output 8Manual Status

2DOM816BD

Analog Output 1Manual Status

XP0:AOM117BD

Analog Output 2Manual Status

AOM218BD

Analog Output 3Manual Status

AOM319BD

Analog Output 4Manual Status

AOM420BD

Analog Output 5Manual Status

AOM521BD

Analog Output 6Manual Status

AOM622BD

Analog Output 7Manual Status

AOM723BD

Analog Output 8Manual Status

AOM824BD

TEC1100When adding the TEC1100 to an NAE, define the TEC1100 as controller type VND. Table 25 describes TEC to NAEobject mapping.

Table 25: VND Point Mapping to an NAE (TEC-1100 Thermostat)Override RangeNAEObjectCommandAllowedNetwork Point

Type/AddressPoint Name

0 to 48°C (28 to 124°F)N2 AIADI-1Room Temp

-48 to 48°C (-54 to 124°F)N2 AIYesADI-2Outdoor Temp

0 to 48°C (28 to 100°F)N2 AOYesADI-3Heating SP

0 to 48 °C (28 to 100°F)N2 AOYesADI-4Cooling SP

82N2 Integration with the NAE Technical Bulletin

Table 25: VND Point Mapping to an NAE (TEC-1100 Thermostat)Override RangeNAEObjectCommandAllowedNetwork Point

Type/AddressPoint Name

0 to 48°C (28 to 100°F)N2 AOYesADI-5Setback Heating SP

0 to 48°C (28 to 100°F)N2 AOYesADI-6Setback Cooling SP

0 to 48° C (28 to 100°F)N2 AOYesADI-7Minimum Heat SP

0 to 48° C (28 to 100°F)N2 AOYesADI-8Maximum Heat SP

0 to 48° C (28 to 100°F)N2 AOYesADI-9Minimum Cool SP

0 to 48° C (28 to 100°F)N2 AOYesADI-10Maximum Cool SP

0 = Off/Auto, 1 = On/MANN2 BOYesBD-1Fan

0 = Off, 1 = Cool, 2 = Heat, 3 =Auto, 4 = E Ht Pump ‘O’

N2 MSOYesBD-2Mode

0 = Unoccupied, 1 = OccupiedN2 BOYesBD-3Occupancy

0 = Off, 1 = OnN2 BIBD-4W1 State-Heating

0 = Off, 1 = OnN2 BIBD-5W2 State-Heat

0 = Off, 1 = OnN2 BIBD-6Y1 State-Cooling

0 = Off, 1 = OnN2 BIBD-7Y2 State-Cooling

0 = Off, 1 = OnN2 BIBD-8G State-Fan

0 = °C, 1 = °FN2 BOYesBD-9Temp Units

0 = Normal, 1 = AlarmN2 BIBI-1Wrench BI

0 = Normal, 1 = AlarmN2 BIBI-2Temp Alarm

0 = Normal, 1 = AlarmN2 BIBI-3Filter BI

TEC210xWhen adding the TEC210x to an NAE, define the TEC210x as controller type VND. Table 26 describes TEC210xto NAE object mapping.

Table 26: VND Point Mapping to an NAE (TEC-210x Thermostat)Override RangeNAEObjectCommandAllowedNetwork Point

Type/AddressPoint Name

0 to 50°C (32 to 122°F)N2 AIYesADI-1Room Temp

-40 to 50°C (-40 to 122°F)N2 AIYesADI-2Aux Temp/Outdoor Temp

4.5 to 32°C (40 to 90°F)N2 AOYesADI-3Heating SP

12 to 37°C (54 to 100°F)N2 AOYesADI-4Cooling SP

4.5 to 32°C (40 to 90°F)N2 AOYesADI-5Setback Heating SP

12 to 37.5°C (54 to 100°F)N2 AOYesADI-6Setback Cooling SP

4.5° C (40°F)N2 AIADI-7Minimum Heat SP

4.5 to 32° C (40 to 90°F)N2 AOYesADI-8Maximum Heat SP

12 to 37.5° C (54 to 100°F)N2 AOYesADI-9Minimum Cool SP

37.5° C (100°F)N2 AIADI-10Maximum Cool SP

0 = Auto, 1 = On/MANN2 BOYesBD-1Fan

0 = Off, 1 = Cool, 2 = Heat, 3 =Auto, 4 = E Ht (Auxiliary Heat)

N2 MSOYesBD-2Mode

83N2 Integration with the NAE Technical Bulletin

Table 26: VND Point Mapping to an NAE (TEC-210x Thermostat)Override RangeNAEObjectCommandAllowedNetwork Point

Type/AddressPoint Name

0 = Unoccupied, 1 = OccupiedN2 BOYesBD-3Occupancy

0 = Off, 1 = OnN2 BIBD-4W1 State

0 = Off, 1 = OnN2 BIBD-5W2 State

0 = Off, 1 = OnN2 BIBD-6Y1 State

0 = Off, 1 = OnN2 BIBD-7Y2 State

0 = Off, 1 = OnN2 BIBD-8G State-Fan

0 = °C, 1 = °FN2 BOYesBD-9Temp Units

0 = No Override, 1 = OverrideN2 BIBD-10Occupancy Override

0 = Off, 1 = OnN2 BIBI-1DI1

0 = Normal, 1 = AlarmN2 BIBI-2Temp Alarm

0 = Off, 1 = OnN2 BIBI-3DI2