Page 1: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone ControllerPackage Technical Guide

www.orioncontrols.com

Page 2: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

www.orioncontrols.com

WattMaster Controls Inc.8500 NW River Park Drive · Parkville, MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] our web site at www.orioncontrols.comWindows® is a registered trademark of Microsoft Corporation.

WattMaster Form: OR-VAVZP-TGD-01BAll rights reserved.© October 2017 WattMaster Controls, Inc. WattMaster Controls, Inc. assumes no responsibility for errors or omissions in this document.This document is subject to change without notice.

Page 3: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

OVERVIEW ....................................................................................................................................... 4Features and Applications ........................................................................................................................................ 4Parts and Descriptions ............................................................................................................................................. 6VAV/Zone Controller, Actuator, and Expansion Module Dimensions ..................................................................... 10Slaved Zone Damper Kit Dimensions .................................................................................................................... 11Rectangular Damper Kit Dimensions ..................................................................................................................... 11Round Damper Kit Dimensions .............................................................................................................................. 12

INSTALLATION AND WIRING ........................................................................................................ 13Mounting and Installation ....................................................................................................................................... 13Important Wiring Considerations ............................................................................................................................ 14Device Transformer Sizing ..................................................................................................................................... 16VAV/Zone Communications Wiring ........................................................................................................................ 17VAV/Zone Controller Inputs and Outputs ............................................................................................................... 18Expansion Module Outputs .................................................................................................................................... 19 VAV/Zone Controller Package Wiring .................................................................................................................... 20Expansion Module Wiring ...................................................................................................................................... 21Slaved Zone Wiring ................................................................................................................................................ 24

START-UP AND COMMISSIONING ................................................................................................. 25Addressing and Baud Rate .................................................................................................................................... 25Initialization and Operator Interfaces ..................................................................................................................... 26Confi guring the VAV/Zone Controller ..................................................................................................................... 27

SEQUENCE OF OPERATION .......................................................................................................... 29Scheduling, Operation Modes, and Damper Positions .......................................................................................... 29Occupied Mode ...................................................................................................................................................... 30Unoccupied Mode .................................................................................................................................................. 32Damper Control ...................................................................................................................................................... 34Zoning .................................................................................................................................................................... 35Alarms .................................................................................................................................................................... 36 Tenant Override Logs ............................................................................................................................................. 36Trend Logs ........................................................................................................................................................... 37Force Modes or Overrides ..................................................................................................................................... 37

TROUBLESHOOTING ..................................................................................................................... 38LED Troubleshooting ............................................................................................................................................. 38Other Checks ......................................................................................................................................................... 39Temperature Sensor Testing .................................................................................................................................. 41

APPENDIX - VAV/ZONE CONTROLLER SYSTEM ARCHITECTURE................................................ 43Single Loop VAV/Zoning ........................................................................................................................................ 43Multiple Loop VAV/Zoning ...................................................................................................................................... 43Networked Single Loop System with MLPD5 ........................................................................................................ 44Networked Single Loop System with MLPD5 and CommLink 5 ............................................................................ 45Networked Multiple Loop System .......................................................................................................................... 46

INDEX ............................................................................................................................................ 47

TABLE OF CONTENTS

Page 4: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Controller Overview

The OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral Airfl ow Sensor and is mounted in a plastic enclosure.

The OE326-23D-OR VAV/Zone Controller is designed for pres-sure dependent VAV Box and Zone Damper applications and is mounted in a plastic enclosure.

The OE326-23I-OR and OE326-23D-OR VAV/Zone Controllers utilize terminal block connections for wiring. The 24 VAC power is supplied from a transformer (by others) wired to the VAV/Zone Controller using standard stranded wire and 2 position terminal blocks. The communications wiring is connected between the other VAV/Zone Controllers, CommLink 5, MiniLink PD5, HVAC unit controller or other controllers on the local loop by using 2 conductor 18 gauge twisted pair with shield wire which is connected to the VAV/Zone Controllers via a standard 3 posi-tion terminal block.

Both VAV/Zone Controllers are designed for use with an OE282-01 Zone Damper Actuator. The VAV/Zone Controller connects to the actuator via the modular cable that is included with the actuator.

The VAV/Zone Controller can use a Standard Room Temperature Sensor wired to the provided 3 position terminal block or an E-BUS Digital Room Sensor connected via the integral E-BUS cable connector or to the provided 4 position terminal block. The VAV/Zone Controller also has a 2 position terminal block for wiring a Discharge Temperature Sensor, if desired.

A relay output on the VAV/Zone Controller provides for one stage of electric heat or an On/Off Hot Water Valve if the controlled terminal unit is not a fan terminal unit.

An optional Expansion Module is available for applications us-ing fan terminals and/or more than 1 stage of electric heat, SCR electric heat, or modulating HW heat. The Expansion Module connects to the VAV/Zone Controller by means of a prefabricated E-BUS cable.

VAV/Zone Controller Package Features

VAV/Zone Controller PackagesThe OE744-03-OR Pressure Independent VAV/Zone Controller Package includes the OE326-23I-OR VAV/Zone Controller, the OE282-01 Zone Damper Actuator with cable, and an Airfl ow Sensor.

The OE742-03-OR Pressure Dependent VAV/Zone Controller Package includes the OE326-23D-OR VAV/Zone Controller and the OE282-01 Zone Damper Actuator with cable.

The VAV/Zone Controller packages are factory mounted on WattMaster Controls Zone Dampers. Detailed mounting and installation instructions are provided with each VAV/Zone Con-troller package.

4 VAV/Zone Controller Package

OVERVIEW

Page 5: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Parts and Descriptions

PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.

OE742-03-OR Pressure Dependent VAV/Zone Controller Package with Terminal Blocks

Includes: OE326-23D-OR Pressure Dependent. VAV/Zone Controller with terminal blocks and OE282-01 Zone Damper Actuator with 3 foot phone jack cable.

The Pressure Dependent VAV/Zone Controller with terminal blocks is designed for pressure dependent VAV Box and Zone Damper applications and is mounted in a plastic enclosure. One stage of Auxiliary Heat is provided on the controller

The OE325-03 VAV/Zone Controller Expansion Module (sold separately) is also available for applications using fan terminals and/or more than 1 stage of electric heat, SCR electric heat, or modulating HW heat.

Pages 10, 17, 20

OE744-03-OR Pressure Independent VAV/Zone Controller Package with Terminal Blocks

Includes: OE326-23I-OR Pressure Independent. VAV/Zone Controller with terminal blocks and airfl ow sensor and OE282-01 Zone Damper Actuator with 3 foot phone jack cable.

The Pressure Independent VAV/Zone Controller with terminal blocks is designed for pressure independent VAV Box and Zone Damper applications. It is supplied with an integral Airfl ow Sensor and is mounted in a plastic enclosure. One stage of Auxiliary Heat is provided on the controller.

The OE325-03 VAV/Zone Controller Expansion Module (sold separately) is also available for applications using fan terminals and/or more than 1 stage of electric heat, SCR electric heat, or modulating HW heat.

Pages 10, 17, 20

OE326-23D-OR

Pressure Dependent VAV/Zone Controller with Terminal Blocks

Includes: OE326-23D-OR Pressure Dependent. VAV/Zone Controller with terminal blocks mounted in a plastic enclosure. Pages

10, 17, 20

OE326-23I-OR Pressure Independent VAV/Zone Controller with Terminal Blocks

Includes: OE326-23I-OR Pressure Independent. VAV/Zone Controller with terminal blocks and airfl ow sensor mounted in a plastic enclosure. Pages

10, 17, 20

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

RE

V1

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

CU

S

R

WattM

aste

r Label

#L102318

Rev.

: 01A

B

RE

LA

YC

ON

TA

CT

RA

TIN

G IS

1A

MP

MA

X @

24 V

AC

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

E S

EN

SO

R

GN

D

GN

D

+12 V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23D-ORP.D. VAV CONTROLLER/ZONE

www.orioncontrols.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

10

25

88

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

RE

LA

YC

ON

TA

CT

RA

TIN

G I

S 1

AM

PM

AX

@2

4 V

AC

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

E S

EN

SO

R

GN

D

GN

D

+12 V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

Wa

ttM

aste

r L

ab

el

#L

10

23

17

Re

v.:

01

AB

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

RE

V1

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

CU

S

R

Wa

ttM

aste

r L

ab

el

#L

10

23

18

Re

v.:

01

AB

RE

LA

YC

ON

TA

CT

RA

TIN

G I

S 1

AM

PM

AX

@2

4 V

AC

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

E S

EN

SO

R

GN

D

GN

D

+12 V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23D-ORP.D. VAV CONTROLLER/ZONE

www.orioncontrols.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

RE

LA

YC

ON

TA

CT

RA

TIN

G I

S 1

AM

PM

AX

@2

4 V

AC

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

E S

EN

SO

R

GN

D

GN

D

+12 V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

Wa

ttM

aste

r L

ab

el

#L

10

23

17

Re

v.:

01

AB

CU

S

R

5VAV/Zone Controller Package

OVERVIEW

Page 6: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Parts and Descriptions

PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.

OE325-03 VAV/Zone Controller Expansion Module

Includes: Expansion Module and 3 foot E-BUS modular cable. The Expansion Module is used in conjunction with the OE326-23I-OR and OE326-23D-OR VAV/Zone Controller and the OE742-03-OR and OE744-03-OR VAV/Zone Controller Packages and allows Fan & Heat control of terminal units, including series and parallel fan terminal units with up to 3 stages of electric heat, SCR electric heat, or modulating hot water heat. Provides 4 relay outputs for pilot duty switching control (1 fan, 2 heat, and 1 auxiliary heat), and 1 Analog output for control of a 0-10V modulating hot water valve or SCR controlled electric heating coil.

Pages 10, 20-23

OE282-01 Zone Damper Actuator

Includes: OE282 Zone Damper Actuator & 3 foot phone jack cable only. The OE282-01 Zone Damper Actuator is used to provide control of air volume dampers in a VAV or Zoning system. The Actuator is a shaft mounted, fl oating point control actuator with an included phone jack cable. Actuators are 24VAC/24VDC with a 10K ohm feedback signal for position monitoring. Wiring connection to the actuator is by means of a modular phone cable connector located on the actuator cover.

Pages10, 20

OE282-03 Slaved Zone Damper Kit

Includes: OE282 Zone Damper Actuator, (2) PL101824 Slave Wiring Interface Boards & modular cables for controller to actuator connection. Used when a terminal unit is to be slaved with another VAV/Zone Damper. Pages

11, 24

OE736-03-PT Pressure Dependent Rectangular Damper Kit with Terminal BlocksThe Rectangular Damper Kit comes packaged with the OE742-03-OR Pressure Dependent VAV/Zone Controller Package already mounted in a metal enclosure.

The Rectangular Damper Kit is used in conjunction with rectangular dampers for applications where rectangular dampers are specifi ed or required because of space limitations or job requirements. The rect-angular dampers may be purchased from WattMaster or you may get them from the supplier of your choice. For proper control, WattMaster recommends the use of low leakage opposed blade dampers.

Page 11

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9

R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3

C2

C1

BIN1

C11 D13

R18

R19

R20

TB

3

U7

U8

YS

102532

RE

V R

1W

AT

TM

AS

TE

RC

ON

TR

OL

S,

INC

MA

DE

IN

US

A

R4

R3

2015

SERIAL #

C

D14

C13

CU

S

R

PL101824 Slave WiringInterface Board

PL101824 Slave WiringInterface Board

OE282 Damper Actuator

0.38”

5.70”

4.15”

3.00”

0.75”

(2) Modular Cables

18.0

6 VAV/Zone Controller Package

OVERVIEW

Page 7: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.

OE520-06-PTOE520-08-PTOE520-10-PTOE520-12-PTOE520-14-PTOE520-16-PT

Pressure Dependent Round Damper with Terminal Blocks

The OE520-XX-PT Round Pressure Dependent Zone Damper Assembly with terminal block connectors consists of a round air damper and the OE742-03-OR VAV/Zone Controller Package with terminal block wiring connectors. An optional Expansion Module (OE325-03) is available for control of reheat, auxiliary heat and/or control of series or parallel fl ow fan terminal units.

Page 12

OE521-06-PTOE521-08-PTOE521-10-PTOE521-12-PTOE521-14-PTOE521-16-PT

Pressure Independent Round Damper with Terminal Blocks

The OE521-XX-PT Round Pressure Independent Zone Damper Assembly with terminal block connectors consists of a round air damper with air fl ow pickup cross and the OE744-03-OR VAV/Zone Controller Package (including air fl ow sensor) with terminal block connectors. An optional Expansion Module (OE325-03) is available for control of reheat, auxiliary heat and/or control of series or parallel fl ow fan terminal units.

Page 12

OE217-02 E-BUS Digital Room Sensor LCD Display and keypad allow for setpoint adjustment, override, and display of certain status and setpoints. The OE217-02 is used with the VAV/Zone Controller for room air temperature sensing applications. Typically hard wired to the VAV/Zone Controller or can use the optional EBC E-BUS cables.

Page 20

EBC-1.5-FEBC-3-FEBC-10-FEBC-25-FEBC-37-FEBC-50-FEBC-75-FEBC-100-FEBC-150-FEBC-250-F

EBC E-BUS Cable Assembly (Optional)Includes: EBC E-BUS Cable Assembly. The EBC E-BUS Cables can be used to connect the OE217-02 E-BUS Digital Room Sensor to the VAV/Zone Controller if desired. Otherwise, the sensor can be hard-wired to the VAV/Zone Controller. Different lengths can be joined together using an E-BUS adapter hub. The EBC E-BUS Cables are available in 1.5, 3, 10, 15, 25, 50, 75, 100, 150 & 250 foot lengths.

Page 20

OE230 OE231

Duct Temperature Sensor - 6” Probe Duct Temperature Sensor - 12" ProbeOE230 = 6″ probe length. OE231 = 12″ probe length. Used for return or supply air temperature sensing applications. Includes: 10k Ohm Duct Temperature Sensor, 2 wire only.

Page 20

OE210 OE211 OE212 OE213

Standard Room Sensor - Plain, w/Override, w/Slide Adjust, w/Override & Slide AdjustFor wall mounting. Connects to the VAV/Zone Controller using wiring terminals.

TMP

GNDAUXOUT

Page 20

Parts and Descriptions

Display Override

OVERRIDE ALARM

7VAV/Zone Controller Package

OVERVIEW

Page 8: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Parts and Descriptions

PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.

PL102681 VAV/Zone Controller Power/Comm Cable (PCC) Modular Adapter

Includes: Modular Adapter. The PCC modular cabling is not included. The PL102681 VAV/Zone Controller Modular Adapter is used to provide two Modular PCC connections to the OE326-23I-OR and OE326-23D-OR VAV/Zone Controllers and the OE742-03-OR and OE744-03-OR VAV/Zone Controller Packages so that these controllers can be used with PCC cables.

The VAV/Zone Controller Modular Adapter is only available as a fi eld-installable kit. It plugs into the 3 pin Comm connector, and the 2 pin 24VAC power connector that is on the VAV/Zone Controller.

N/A

OE392-11 System Manager Touch Screen - Limited AccessThe System Manager Touch Screen - Limited Access ( SMTS-L) provides a direct, graphic-enhanced, menu-driven link. The SMTS-L is an end-user interface only and allows the end user to view status points, change Space Setpoints, and view certain alarms of most controllers on the Orion Controls System. The SMTS-L is equipped with a 4.3” 480 x 272 WQVGA RGB TFT LCD Touch Screen Display. The System Manager TS-L is furnished with hardware for fl ush mounting into hollow drywall or surface mounting on concrete brick or plaster surfaces. Includes: SMTS-L with 12 ft. long pigtail cable assembly.

See the SMTS-L Technical Guide

OE391-12 Modular Service Tool SDIncludes: Modular Service Tool, power supply, communication cables, 4 Gigabyte SD card, and (4) AA batteries. Used to program and monitor all Orion controllers.

See the Unit Controller Operator Interfaces SD Technical Guide

OE392-12 Modular System Manager SD Includes: Modular System Manager SD with 4 Gigabyte SD card and 12 ft. long pigtail cable assembly. Used to program and monitor all Orion controllers. Designed for hollow core wall mounting. When System Manager is to be mounted on a solid wall (concrete), you will also need to order the solid wall mounting bracket below.

See the Unit Controller Operator Interfaces SD Technical Guide

EB101505 Solid Wall Mounting Bracket for Modular System Manager SDIncludes: 22 gauge galvanized sheet metal mounting bracket with mounting holes and wire routing opening. Dimensions are 9.25″W x 8.00″H x 0.50″DP. The Wall Mounting Bracket provides wiring clearance between the System Manager and the wall mounting surface when the System Manager is to be mounted on a concrete or other solid wall surface. Not for use with the System Manager TS-L.

N/A

8 VAV/Zone Controller Package

OVERVIEW

Page 9: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Parts and Descriptions

PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.

OE361-13 CommLink 5 Communications InterfaceThe CommLink 5 connects to your control system using a USB computer connection to provide direct on-site communications with the control system from a computer with the Prism 2 software installed. For remote communications, see the OE415-02 IP Module Kit.

Includes: CommLink 5, 6 ft. long USB cable, and 120/24 VAC power sup-ply. Required on all networked systems or if direct computer or remote computer connection is required. Connects to your computer’s USB 1.1 or 2.1 port. Prism 2 computer software must be installed on the direct con-nected or remote connected computer in order to communicate with your system.

STATUS

See theCommLink 5 Technical Guide

OE415-02 IP Module Kit - Internet/LAN ConnectionUsed for Internet or Local Area Network communications with the control system. Field installs by plugging into the CommLink 5 circuit board and provides an addressable Ethernet connection to the controls system from any computer connected to your building’s LAN. It can also be confi gured to allow access to the control system from the Internet through your LAN if your Ethernet fi rewall is confi gured for this option.

Includes: IP Link module, 10 ft. long Ethernet cable, and installation instructions. Prism 2 computer software must be installed on the remote computer in order to dial-up and communicate with the controls system.

See the IP Module Technical Guide

OE364-23-OR MiniLink PD 5 Used with all Orion controllers to provide network communications, zone voting, alarming, and tenant logging capabilities. A MiniLink Polling Device is required on each loop of a Networked system. Includes: MiniLink Polling Device.

PD

DR

V

LO

OP

DR

V

NET DRV

PIC32 MLPDYS102398 REV 3

NETWORK

LOCAL

PD COMM

POWER

1

2

4

8

16

32

COMM

ADDRESS

ML

PD

MADE IN USA

SE

RIA

L#

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4 R20

R21

R22

R23R24

R25

R26

R27

R31

PDSTAT1

PDSTAT2SW2

TB1

TB2

U8

U10

U12

D4

J6

J7

J8

R43

R44

R46

C33

OF

F

T

SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.1uF

.1uF

.1uF

1002

1002

T

SH

R

C24

COMM

www.orioncontrols.com

WattMaster Label#LB102091-00

Rev. 01B

OE364-23-ORMINILINK PD 5

TT

T

LOCAL NETWORK

SH

24 V

AC

GN

D

SH

R

R

LO

CA

LL

OO

PW

IRE

TE

RM

INA

LS

NE

TW

OR

K L

OO

PW

IRE

TE

RM

INA

LS

NE

TW

OR

K L

OO

PC

OM

M C

ON

NE

CT

OR

S

AD

DR

ES

S D

IPS

WIT

CH

POWERTERMINALS

LO

CA

LL

OO

PC

OM

MC

ON

NE

CT

OR

24 VAC POWER ONLYWARNING! POLARITY MUST

BE OBSERVED OR THE

BOARD WILL BE DAMAGED

See the OrionMiniLink PD 5 Technical Guide

OE366 USB-Link 2 KitThe USB-Link 2 is a pocket-sized communications interface used to connect a laptop computer to your controls system for programming and monitoring purposes, utilizing a modular cable to allow connection to the service port connector on the controllers and a USB cable to connect to a laptop computer.

Includes: USB-Link 2 for multiple or single loop systems, USB cable, modular connection cable, two mini-DIN to terminal adapters, and Prism 2 software.

STAND ALONE

NETWORK

See the USB-Link 2 Technical Guide

OE508 Prism 2 Graphical Computer SoftwarePrism 2 provides standard, easy to understand status screens for each type of Orion controllers installed. Prism 2 software has provisions for custom screens which allow fl oor plans, equipment photos, or user-defi ned summary screens to be implemented to meet their own individual needs. All controlling setpoints, trend logs, and alarm conditions are accessed in the Prism environment. Prism 2 can be confi gured for direct on-site installation, remote modem connection, or TCP/IP Internetconnection to several installations.

Page 26

9VAV/Zone Controller Package

OVERVIEW

Page 10: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Controller, Actuator & Expansion Module Dimensions

5.82 .02

5.64

5.05

2.62

2.05

4.10

1.49

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

0.29

RE

LA

YC

ON

TA

CT

RA

TIN

G I

S 1

AM

PM

AX

@2

4 V

AC

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

E S

EN

SO

R

GN

D

GN

D

+1

2 V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

Wa

ttM

aste

r L

ab

el

#L

10

23

17

Re

v.:

01

AB

2.05

CU

S

R

Figure 1: VAV/Zone Controller Dimensions - OE326-23I-OR Shown

Figure 3: OE325-03 VAV/Zone Controller Expansion Module Dimensions

1.35"

4

4

3

3

22

1

1

18.00"

E-BUS CABLE

SNAP TRACKCHANNEL

PL102532 EXPANSION BOARD

GN

D

AO

UT

CO

MM

ST

AT

AL

RM

PW

R

CO

M

R2

R1

GN

D

P1

R17

R16

R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB

2

TB

1

R9

R8

R7

R6

R5

R4

R3

R2

R1

Q4Q3Q2Q1

J1

D4D3D2D1

C10

C9

C8

C7

C6

C5

C4

C3

C2

C1

BIN

1

C11

D13

R18

R19

R20

TB3

U7

U8

YS102532REV R1

WATTMASTER CONTROLS, INC

MADE IN USA

R4

R3

2015

SE

RIA

L#

C

D14

C13

C US

R

4.18"

4.34"

3.10"

Modular Cable

OE282 Damper Actuator

5.7

0”

0.7

5”

0.38”

Modular JackConnection

18.0

Figure 2: OE282-01 Zone Damper Actuator Dimensions

10 VAV/Zone Controller Package

OVERVIEW

Page 11: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Figure 4: OE282-03 Slaved Zone Damper Kit

PL101824 Slave WiringInterface Board

PL101824 Slave WiringInterface Board

OE282 Damper Actuator

0.38”

5.70”

4.15”

3.00”

0.75”

(2) Modular Cables

18.0

Figure 5: OE736-03-PT P.D. Rectangular Damper Kit with Terminal Blocks

15.50

14.15

Dimensional InfoComponent View

DamperActuator

EnclosureBase

EnclosureCover

P.D. ZoneController

Slaved Zone Damper Kit & Rectangular Damper Kit Dimensions

11VAV/Zone Controller Package

OVERVIEW

Page 12: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Round Damper Kit Dimensions

Figure 6: OE520-XX-PT P.D. Round Damper Kit with Terminal Blocks

11.5”

12.0”

P.D. ZoneController

Damper Actua

Control Base Cover

1/2” Foil FaceInsulation

Damper Housing

Damper BladeAnd Shaft

11.5”

12.0”

1/2” Foil FaceInsulation

Damper Housing

Damper BladeAnd Shaft

Air FlowPickup Cross

Control Base Cover

P.I. ZoneController

Damper Actuato

Figure 7: OE521-XX-PT P.I. Round Damper Kit with Terminal Blocks

12 VAV/Zone Controller Package

OVERVIEW

Page 13: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Mounting and Installation

Mounting & Installation

If you purchased the Round Zone Damper or Rectangular Zone Damper Kits from WattMaster, the controller and actuator are factory mounted and wired in the damper control enclosure. If your VAV/Zone Controllers are pressure independent, an airfl ow probe and pressure sensor will also be factory mounted and wired.

Most terminal unit manufacturers will offer the option of fac-tory mounting the Orion controls in their terminal units for an additional charge. An installation worksheet and instructions are available for the Orion VAV/Zone Controller package which can be shipped with the VAV/Zone control(s) to the terminal unit manufacturer to simplify factory mounting and wiring of the controller.

VAV/Zone Controller Package

NOTE: The VAV/Zone Controller defaults to Direct Acting, which means that when looking at the damper shaft, the damper rotates clockwise to open. If the damper on the terminal unit is not installed for clockwise to open operation, the WattMaster Zone Controller can be confi gured for counterclockwise to open opera-tion via the operator interface or through the Prism software. It must be changed prior to system start-up for the designated units for the zone damper to func-tion properly. See your operator interface or Prism manual for further information on reconfi guring for reverse acting operation. Installation is the same as for clockwise-to-open units except all references to clockwise will now be counter-clockwise direction.

1. The terminal unit damper (by others) should be installed so the damper shaft turns in a clockwise direction to open the damper. This is the software default for the VAV/Zone Controller Pack-age. If this is not possible, the Controller can be re-confi gured for counter-clockwise-to-open operation using the Prism software. See the note above for details. All installation instructions are based on the clockwise-to-open default. Check the damper for proper rotation and mark the end of the damper shaft to indicate open and closed positions.

2. Loosen the (2) shaft mounting bracket nuts on the ends of the damper actuator’s shaft mounting U-bolt and slide damper actua-tor assembly over the terminal unit damper shaft. The actuator may have to be rotated from position shown depending on the terminal unit’s available mounting area and damper shaft loca-tion and whether this is a left or right hand installation. Hand tighten the U-bolt nuts until the damper shaft is loosely secured to the shaft.

Space Temperature SensorsThe Space Temperature Sensors should be mounted in the space served by the equipment the sensor is connected or hard wired to. All Space Sensors should be mounted approximately 5 feet above the fl oor and in an area that does not experience direct sunlight or drafts in order to get accurate readings. Cabling or wiring should be routed so the wire or cable is protected from being pinched or punctured by building fasteners or materials.

Discharge Temperature SensorsThese sensors should be mounted in the supply air duct of the equipment. The Discharge Temperature Sensor should be mount-ed at least 10 feet away from any Heating or Cooling source and be mounted 3 duct diameters from any elbow.

Cabling or wiring should be routed so the wire or cable is pro-tected from being pinched or punctured by building fasteners or materials.

NOTE: If this is a stand-alone damper, this sensor would be mounted upstream of the damper to act as a Supply Air Sensor.

3. After positioning the damper actuator over the damper shaft, secure the damper actuator to the controller enclosure base using the supplied L-bracket and 2 screws.

4 Turn the damper blade to its fully closed position. With the manual override clutch button depressed, rotate the actuator clamp to within approximately 1/16 inch to ⅛ inch distance be-tween the actuator stop and the clamp, depending on the damper seal design. Tighten the (2) shaft mounting bracket nuts on the ends of the damper actuator’s shaft mounting U-bolt with an 8 mm wrench to 3-5 ft-lb of torque. On dampers with edge seals, the actuator will compress the damper blade seal when reaching the end position. Adjust the end stops, if required. Attach the actuator cable between the actuator and controller.

13VAV/Zone Controller Package

INSTALLATION & WIRING

Page 14: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Important Wiring Considerations

General

Correct wiring of the VAV/Zone Controller is the most important factor in the overall success of the controller installation process. The VAV/Zone Controller wiring has been simplifi ed by the use of modular connectors and prefabricated modular cables.

Voltage and Environment Requirements

The VAV/Zone Controller and expansion modules must be connected to a 24 VAC power source of the proper size for the calculated VA load requirements. All transformer sizing should be based on the VA rating listed in Table 1.

Con

trol

D

evic

e

Vol

tage

VA

Loa

d

Tem

pera

ture

Hum

idit

y(N

on-

Con

dens

ing)

OE336-23I-OR & OE336-23D-OR

VAV/Zone Controller24VAC 6 -30°F to

150°F0-90%

RH

OE282-01Zone Damper Actuator 24VAC 3 -22°F to

122°F5-95%

RH

OE325-03VAV/Zone Controller Expansion Module

24VAC 5 10°F to 149°F

0-90% RH

OE282-03Slaved Zone Damper Kit 24VAC 3 -22°F to

122°F5-95%

RH

Table 1: Voltage and Environment Requirements

WARNING: When using a single transformer to power more than one controller or expansion module, the correct polarity must always be maintained be- tween the boards. Failure to observe correct polarity will result in damage to the VAV/Zone Controller, actuator, and expansion module.

Important Wiring Considerations

Please carefully read and apply the following information when wiring the VAV/Zone Controller Package. See Figure 10, page 20 for VAV/Zone Controller Package wiring and connections. See Figure 9, page 17 for connecting and wiring multiple VAV/Zone Controller Packages in a system.

1. Size and wire the transformer to be used for powering the Non-Modular VAV/Zone Controller Package(s) per the instructions. Failure to size the transformer and/or wire the Non-Modular VAV/Zone Controller Package(s) correctly may cause the VAV/Zone Controller Package to operate erratically or not at all. See Figure 8, page 16 for wiring and transformer sizing information.

2. All wiring is to be in accordance with local and nationalelectrical codes and specifi cations.

3. All 24 VAC wiring must be connected so that all ground wires remain common. Failure to follow this procedure can result in damage to the controller and connected devices.

4. Minimum wire size for 24 VAC wiring should be18-gauge.

5. Minimum wire size for all sensors should be 24-gauge. Some sensors require 2-conductor wire and some require3-or 4-conductor wire.

6. Minimum wire size for 24 VAC thermostat wiring should be 22 gauge.

7. Be sure that all wiring connections are properly insertedand tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals which could potentially cause a short circuit.

8. Do not pry on the connectors when connecting ordisconnecting the modular cables. Be sure to push in on the connector release clip and then pull straight up.

9. When communication wiring is to be used to intercon-nect VAV/Zone Controllers together or to connect to othercommunication devices, all wiring must be plenum-rated, minimum 18-gauge, 2-conductor, twisted pair withshield. WattMaster can supply communication wire that meets this specifi cation and is color coded for the network or local loop. Please consult your WattMaster distributor for information. If desired, Belden #82760 or equivalent wire may also be used.

10. Before applying power to the VAV/Zone Controller, be sure to recheck all wiring connections and terminations thoroughly.

14 VAV/Zone Controller Package

INSTALLATION & WIRING

Page 15: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Wiring Checks

One of the most important checks to make before powering up the system for the fi rst time is to confi rm proper voltage and transformer sizing. Each VAV/Zone Controller Package requires 6 VA of power delivered to it at 24 VAC. See pages 20-21 of this manual for complete wiring and transformer sizing information for the VAV/Zone Controller.

Check all modular connectors to be sure they are completely pushed and locked into their mating connectors. Confi rm that all sensors required for your system are mounted in the appropriate location and that the modular cables are plugged into the correct connectors on the VAV/Zone Controller. Check the actuator cable and be sure it is plugged in and secured to the modular connec-tor on the actuator and the VAV/Zone Controller circuit board modular connector. If using a Standard Room Sensor or terminal connection for an E-BUS Digital Room Sensor, check to make sure the wiring is correct. See Figure 10, page 20 in this manual for wiring details. If attaching an E-BUS Sensor with an E-BUS cable, make sure the E-BUS connector is connected to one end of the E-BUS sensor cable and the other end is connected to the E-BUS sensor connector on the VAV/Zone Controller. Be sure any VAV/Zone Controller Expansion Modules connected to the VAV/Zone Controller are also correctly wired per the VAV/Zone Controller Expansion Module wiring instructions on pages 20 through 23 of this manual.

After all the above wiring checks are complete, apply power to the transformer(s) that is connected to the VAV/Zone Controller.

Powering Up

When the Controller and Modules are fi rst powered up, the POWER LED should light up and stay on continuously. If it does not light up, check to be sure that you have 24 VAC connected to the controller, that the wiring connections are tight, and that they are wired for the correct polarity. The 24 VAC power must be connected so that all ground wires remain common. If after mak-ing all these checks, the POWER LED does not light up, please contact WattMaster Controls Technical Support for assistance.

Power Wiring

One of the most important checks to make before powering up the system for the fi rst time is to confi rm proper voltage and transformer sizing for each controller. Each VAV/Zone Control-ler requires 6 VA of power delivered to it at 24 VAC. You may use separate transformers for each device (preferred) or power several devices from a common transformer. If several devices are to be powered from a single transformer, correct polarity must be followed.

WARNING: Observe Polarity! All boards must be wired with GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity will result in damage to one or more of the boards.

Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confi rm that all sensors required for your system are mounted in the appropriate location and wired into the correct terminals on the VAV/Zone Controller.

After all the above wiring checks are complete, apply power to the VAV/Zone Controller.

Important Wiring Considerations

15VAV/Zone Controller Package

INSTALLATION & WIRING

Page 16: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Device Transformer Sizing

24 VAC Power - Transformer & Wire Sizing Considerations for Devices Without Modular Connectors

120 / 24VAC

120 / 24VAC

Distance A to B cannot exceed 57.80 Ft. Distance from A to B cannot exceed 115.60 Ft.Distance from A to C cannot exceed 115.60 Ft.

Distance from A to B cannot exceed 230.40 Ft.Distance from A to C cannot exceed Ft.Distance from A to D cannot exceed Ft.Distance from A to E cannot exceed Ft.

230.40230.40230.40

120 / 24VAC

Some installers like to use one large 24 VAC transformer to power several devices. This is allowable as long as polarity is maintained to each deviceon the transformer circuit.

Usingseparate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioningtransformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several devices, the followingtransformer and wire sizing information is presented to help the installer correctly supply 24 VAC power to the devices.

Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.

Each GPC-XP Controller requires 8 VA @ 24VAC power. In the examples below we have a total of 8 GPC-XP Controllers.

8 GPC-XP Controllers @ 8 VA each................ 8 x 8 VA = 64 VA.

The above calculation determines that our transformer will need to be sized for a minimum of 64 VA if we are to use one transformer to power all thecontrollers.

Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has avoltage drop per foot value we use to calculate total voltage drop.

18ga wire.................................0.00054 = voltage drop per 1’ length of wire16ga wire.................................0.00034 = voltage drop per 1’ length of wire14ga wire.................................0.00021 = voltage drop per 1’ length of wire

For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.

Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 8 controllers to be installed.

0.00054 (Voltage drop per foot for 18 gauge wire) x 64VA controller load = Volts/Ft.

WattMaster controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts by thenumber you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 75 VA transformer with no more than a2 Volt drop at the farthest controller from the transformer..

2 (Volts total allowable voltage drop)= 57.80

0.0346 (Voltage drop per 1 ft. @ 64VA load)

Parallel circuiting of the wiring instead of wiring all 8 controllers in series allows for longer wire runs to be used with the same size wire (as shown inour examples below).

Warning: If polarity is not maintained, severe damage to the devices may result. WattMaster Controls recommendsusing a separate transformer for each device in order to eliminate the potential for damaging controllers due to incorrect polarity.

0.0346

feet

It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size,transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatorythat the farthest controller on the circuit is supplied with a minimum of 22 Volts.

A

A

A

B C D EBB C

Figure 8: VAV/Zone Controller Package With Terminal Blocks Transformer Sizing

16 VAV/Zone Controller Package

INSTALLATION & WIRING

Page 17: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Communications Wiring

Wire To The Next ZoneController On The LocalCommunications Loop.

All Wiring To Be ConnectedAs Shown Below

Line VoltageGND

24 VAC

R

SH

T

R

SH

T

R

SH

T

R

SH

T

Local Loop

Local Loop

Local Loop

Local Loop

VAV/Zone Controller

VAV/Zone Controller

VAV/Zone Controller

VAV/Zone Controller

VAV/Zone Controller

VAV/Zone Controller

VAV/Zone Controller

VAV/Zone Controller

Damper Actuator

Damper Actuator

Damper Actuator

Damper Actuator

Damper Actuator

Damper Actuator

Damper Actuator

Damper Actuator

Local Loop

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

CU

S

R

CU

S

R

CU

S

R

CU

S

R

CU

S

R

CU

S

R

CU

S

R

Use WattMaster 2Conductor Twisted PairWith Shield Cable OrBelden 82760 OrEquivalent To ConnectBetween Each VAV/ZoneController ActuatorPackage And From TheUnit Controller, MiniLinkPD Or CommLink To TheFirst VAV/Zone ControllerActuator Package AsRequired By YourApplication.

24VAC Transformer (By Others)See Zone Controller TransformerSizing Information For CalculatingVA Requirements.

WARNING: If Multiple Controllers Are Wired To ASingle Transformer As Shown, Polarity Must BeObserved On All 24 VAC Wiring Or Damage To TheControllers Will Result.

CAUTION: Size PowerWiring Per Wire SizingInformation In This Manual.Be Sure Wiring Is Sized ForMinimum Voltage Drop ForYour Length Of Wiring Run.

NOTE: A Single Transformer Supplying Each VAV/Zone ControllerIndividually Can Be Used Or A Transformer Supplying Several VAV/ZoneControllers Can Be Used. Each Controller Requires 6 VA Minimum Power.Do Not Exceed 16 Controllers Attached To One Transformer (96 VA). AlsoSee Warning Note Regarding Polarity.

Figure 9: VAV/Zone Controllers Communication & Power Wiring Diagram

17VAV/Zone Controller Package

INSTALLATION & WIRING

Page 18: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

18 VAV/Zone Controller Package

INSTALLATION & WIRING

VAV/Zone Controller Inputs

Analog Space Sensor or Digital Space SensorA Standard Room Temperature Sensor that hard wires to the Space Sensor wiring terminals on the VAV/Zone Controller is used when an analog sensor is desired. When an E-BUS Digital Room Temperature Sensor is desired, it can connect to the Digital Space Sensor wire terminals on the VAV/Zone Controller or it can be connected to the E-BUS connector on the VAV/Zone Control-ler using an E-BUS pre-fabricated cable of the desired length. Discharge Temperature SensorThis sensor can be used for monitoring the discharge air tempera-ture of the terminal unit, round damper or rectangular damper used with the VAV/Zone Controller. The sensor is typically used when the terminal unit has reheat installed so the true temperature of the air being supplied to the space can be monitored. It should be mounted in the discharge duct downstream of the terminal unit where the VAV/Zone Controller is installed.

NOTE: If this is a stand-alone damper, this sensor would be mounted upstream of the damper to act as a Supply Air Sensor.

Occupied SwitchThis input is used when you have a motion switch or window switch to determine room occupancy and allows for setback of the heating or cooling during occupied periods.

Window Open Detection ModeIf the “Window Open Detection” button is checked, and the “Oc-cupied Switch” contacts (located on the VAV/Zone Controller) are open, the VAV/Zone controller will control to the Unoccupied Cooling and Heating Setpoints and the Damper will completely close. When the contacts are shorted, the unit will control to the Occupied Cooling and Heating Setpoints. If the “Reverse Contact Polarity” button is checked, then the unit controls to the Unoc-cupied Cooling and Heating setpoints when the Occupied Switch contacts are shorted, and control to the Occupied Cooling and Heating Setpoints when the contacts are open.

Motion Sensor Occupancy DetectionThis operation only occurs in the scheduled Occupied Mode. If the Motion Sensor Occupancy Detection button is checked, then the Occupancy Detection Time and Occupancy Duration Timeout setpoints are used to determine the cooling and heating setpoints of the VAV/Zone controller. A motion sensor is con-nected to the Occupied Switch contacts (located on the VAV/Zone Controller) and when motion is detected (contacts shorted together) for the Occupancy Detection Time period, the control-ler will display “Occupied Mode” and control to the Occupied Cooling and Heating setpoints. If no motion is detected for a period longer than the Occupancy Duration Timeout setpoint, (the

contacts will open) the controller will display “Occupied Room Empty” and the controller will go to the Occupancy Cooling and Heating Setback temperatures, until motion is detected again. If the “Reverse Contact Polarity” button is checked, then the unit controls the opposite. When no motion is detected (contacts shorted) the controller will display “Occupied Room Empty” and unit will control to the Occupancy Cooling and Heating Setback temperatures, until motion is detected. When motion is detected (contacts open) for the Occupancy Detection Time period, the controller will display “Occupied Mode” and control to the Oc-cupied Cooling and Heating setpoints.

Airfl ow SensorIf the OE326-23I-OR Pressure Independent VAV/Zone Control-ler is being used, the terminal unit’s pressure pick-up tube must be connected with FRP tubing to the barb fi ttings on the side of the VAV/Zone Controller. No wiring connections are required as the pressure sensor is integral to the VAV/Zone Controller. This pressure sensor input is used for CFM (airfl ow) calculations.

VAV/Zone Controller Outputs

Auxiliary Reheat RelayThis relay has a dry contact on the VAV/Zone Controller and can be confi gured for Auxiliary Heat or Box Re-heat. Box Re-heat is used when you only need 1 stage of electric heat or On/Off Hot Water Valve. Auxiliary Heat is selected when you are using Baseboard or some other Heating Source. Use this relay if the controlled terminal unit is not a fan terminal unit. When you are using a fan terminal unit or have more than 1 stage of electric heat, SCR electric heat, or modulating HW heat, the OE325-03 VAV/Zone Controller Expansion Module must be used.

Confi gure the relay for Auxiliary Heat if the heat being controlled by the controller is baseboard type heat or any other type heat that does not require airfl ow through box. The relay will be energized whenever the Space Temperature drops 0.5° below the Auxiliary Heat Setpoint and the damper will remain in the position determined by the mode of operation.

If the relay is confi gured for Box Reheat, then the relay will be energized whenever the Space Temperature drops below the Oc-cupied Heating Setpoint and the damper will go to the Minimum Damper During Box Heating Mode Setpoint. The stages of box reheat will need to be set to 1.

VAV/Zone Controller Inputs and Outputs

Page 19: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

19VAV/Zone Controller Package

INSTALLATION & WIRING

VAV/Zone Controller Expansion Module OutputsAs previously stated, when you are using a fan terminal unit or have more than 1 stage of electric heat, have SCR electric heat, or have modulating HW heat, the OE325-03 VAV/Zone Controller Expansion Module is required.

Binary Input - Proof of FlowThis input is for an airfl ow Proving Switch. It is only an option with Stand-Alone damper applications using electric reheat.

Relay #1 - Fan EnableThis relay is used for energizing the Fan on Series or Parallel Fan Terminal units.

Relay #2 - Heating Stage 1If you have at least 1 stage of Heat, this relay is used to energize the 1st stage of terminal unit Heat. This Heating Stage can either be used with Electric Heat or On/Off Hot Water Valve control.

Relay #3 - Heating Stage 2If you have 2 stages of Electric Heat, this relay controls the 2nd

stage of Electric Heat.

Relay #4 - Heating Stage 3If you have 3 stages of Electric Heat, this relay controls the 3rd

stage of Electric Heat.

Analog OutputIf you are using SCR Electric Heat or a modulating Hot Water Valve or modulating Steam Valve for Heating, this output can supply a 0-10 VDC signal for proportional control of the Valve or SCR Electric Heater.

VAV/Zone Controller Expansion Module Inputs and Outputs

Other Connections

E-BUS ConnectorsThe EBC E-BUS modular connectors are used to connect the optional OE325-03 VAV/Zone Controller Expansion Module to the VAV/Zone Controller. The expansion module is only required when staged electric heat (more than 1 stage), SCR electric heat, modulating HW heat, and/or fan terminal control is required.

The E-BUS connector can also be used to connect an E-BUS Digital Room Temperature Sensor to the VAV/Zone Controller if desired. Actuator Modular ConnectorThis modular connector is used to connect a modular cable from the VAV/Zone Controller to a damper actuator.

Communications Terminal BlockThis three position terminal block is used for connecting the communications wiring between each VAV/Zone Controller and/or to the MiniLink, HVAC Unit Controller, or other installed controller on the local communications loop. Communications wiring should be 18 gauge minimum 2 conductor twisted pair with shield Belden #82760 or its equivalent.

24 VAC Power Terminal Block

This two position terminal block is used to wire the 24 Volt power to the VAV/Zone Controller Packages. If desired, a single transformer can be used to power multiple VAV/Zone Control-ler Packages together, or a separate transformer can be used for each controller.

WARNING: If multiple controllers are to be wired to the same transformer, polarity must be observed or damage to the controller will result.

Page 20: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Controller Package Wiring

24 VAC Transformer. Size AsRequired For Number OfControllers Connected. EachVAV/Zone Controller ActuatorPackage Requires 6 VA Minimum.

LineVoltage

GND

R+

TM

P

GN

D

GN

D

BIN

GN

D

-+1

2V

TM

P

AD

J

GN

D

+

SH

T-

24VAC

WARNING:When Multiple VAV/Zone ControllerActuator Packages Are Powered FromA Single Transformer, Polarity Must BeObserved Or Damage To TheControllers Will Result.

OE325-03 Zone Controller Expansion Module(See Expansion Board Wiring For Detailed Wiring Connections)

Connect FRP Tubing (By Others) To TerminalUnit Air Flow Pickup Tube Hi & Lo Ports(P.I. VAV/Zone Controller Packages Only)

Occupied OrWindow Switch

This Expansion Module Is OnlyRequired For Single Duct Terminal

Units With Reheat And All FanTerminal Units

The E-BUS Cable For The Digital RoomTemperature Sensor Can Be ConnectedTo This E-BUS Port Or The E-BUS Port

On The VAV/Zone Controller

Optional - Discharge AirTemperature Sensor. OnlyRequired When The MainController Is Not Installed On TheHVAC Unit Connected To TheTerminal Units. Locate InDuctwork Downstream Of TheTerminal Unit OrUpstreamIf UsingStand-Alone Damper.

Wire To Previous And/Or Next VAV/Zone ControllerActuator Package Or Device On The LocalCommunications Loop. All Communication WiringMust Be Plenum-rated, Minimum 18-gauge, 2-conductor, Twisted Pair With Shield Wire. WattmasterCan Supply Communication Wire That Meets ThisSpecification And Is Color Coded For Local Loop. TheLocal Loop Wire Part Number Is WR-LL-WG-18, IsColor Coded With Green Candy Striping And ComesOn A 1000 Ft. Spool. If Desired, 18 Gauge MinimumBelden #82760 Or Equivalent Communications WireMay Also Be Used For The Local Loop Wiring.

Damper Actuator

Address Switch Shown IsSet For Address 1

Modular ActuatorCable

Electric Heat Contactor(By Others - When Used)

HW Valve(By Others - When Used)

Either A 1 Stage Electric HeaterOr On/Off HW Valve May Be Used

Not Both.

Loop Baud Switch1 Should Be Set To Off

And Loop Baud Switch 2Should Be Set To On

As Shown ForVAV/Zone Controllers

Using High SpeedConnection

Address Switch Shown IsSet For Address 21

NOTE:The Power To The VAV/ZoneController Must Be RemovedAnd Reconnected AfterChanging The Address SwitchSettings In Order For AnyChanges To Take Effect.

CAUTION:Disconnect All CommunicationLoop Wiring From TheVAV/Zone Controller BeforeRemoving Power. ReconnectPower And Then ReconnectCommunication Loop Wiring.

The Address For Each VAV/Zone ControllerMust Be Unique To The Other Zone ControllersOn The Local Loop And Be Between 1 and 58.

TMP

GND

AUX OUT

OE210, OE211,OE212 Or OE213

Wired Room Sensor

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

OFFOFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

A

AA

D

DD

D

DD

R

RR

E

EE

S

SS

S

SS

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1

11

2

22

4

44

8

88

1

116

663

332

22

CW

CC

W

O

O O

N

N N

LOOP

LOOPLOOP

BAUD

BAUDBAUD

1

112

22

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

GN

D

AO

UT

CO

MM

STA

T

AL

RM

PW

R

CO

M

R2

R1

GN

DP1

R1

7R

16

R1

5

R1

4

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB

2

TB

1

R9

R8

R7

R6

R5

R4

R3

R2

R1

Q4Q3Q2Q1

J1

D4D3D2D1

C1

0

C9

C8

C7

C6

C5

C4

C3

C2

C1

BIN

1

C11

D13

R18

R19

R20

TB

3U7

U8

YS102532REV R0A

WATTMASTER CONTROLS, INC

MADE IN USA

R4

R3

LM7805

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF.1uF

.1uF

1002

LM

358

04 04

04

LT1785

10A

250V

AC

~5A

30V

DC

SA

VD

E

G5Q

-1A

4O

MR

ON

DC

12V

CH

INA

10A

250V

AC

~5A

30V

DC

SA

VD

E

G5Q

-1A

4O

MR

ON

DC

12V

CH

INA

10A

250V

AC

~5A

30V

DC

SA

VD

E

G5Q

-1A

4O

MR

ON

DC

12V

CH

INA

10A

250V

AC

~5A

30V

DC

SA

VD

E

G5Q

-1A

4O

MR

ON

DC

12V

CH

INA

-COM

+COM

GND

+12 VDC

Display Override

OVERRIDE ALARM

NOTE: The Optional E-BUSDigital Room Temperature SensorCan Be Connected To TheVAV/Zone Controller With E-BUSCable(s) Of The Required LengthOr They Can Be Hard Wired FromThe Terminals On The VAV/ZoneController To The Terminals OnThe E-BUS Sensor.

HWV

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

NOTE: Mount Both SensorAt Least 5 Feet Above Floor.

P.O.F. AirflowSwitch

(If Required)

Note: ThisAirflow Switch(By Others) IsOptional AndOnly Used ForStand AloneDamperApplications

Figure 10: VAV/Zone Controller Package with Terminal Blocks Wiring

20 VAV/Zone Controller Package

INSTALLATION & WIRING

Page 21: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Controller Expansion Module Wiring

21VAV/Zone Controller Package

INSTALLATION & WIRING

RC

RC

RC

R4

R4

R3

R3

R2

R2

R1

R1

Typical Wiring ForSingle Duct Terminal UnitWith Staged Electric Heat

Typical Wiring ForFan Terminal UnitWithout Heat

Typical Wiring ForFan Terminal UnitWith Staged Electric Heat

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

Connect to VAV/ZoneController E-BUSFemale Connector

Connect to VAV/ZoneController E-BUSFemale Connector

Connect to VAV/ZoneController E-BUSFemale Connector

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3U

2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1Q

4Q

3Q

2Q

1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

E-BUSEBC Cable

E-BUSEBC Cable

E-BUSEBC Cable

WattMaster Part #OE325-03Zone Controller Expansion Module

WattMaster Part #OE325-03Zone Controller Expansion Module

WattMaster Part #OE325-03Zone Controller Expansion Module

24VAC

24VAC

24VAC

COM

COM

COM

C3

C3

C2

C2

C1

C1

R1

R1

24 VAC Transformer Supplied& Wired by Others. Size ForRequired Heat Contactor Load

24 VAC Transformer Supplied& Wired by Others. Size ForRequired Fan Relay & Heat Contactor Load

24 VAC Transformer Supplied& Wired by Others. Size ForRequired Fan Relay & AuxiliaryHot Water Valve Load

24 VAC HeatContactors Supplied& Wired By Others.1 Amp Max. Load.

24 VAC HeatContactors & FanRelay Supplied &Wired By Others.1 Amp Max. Load.

24 VAC Fan RelaySupplied & WiredBy Others. 1 AmpMax. Load.

Figure 11: VAV/Zone Controller Expansion Module Wiring - Fan Terminals And/Or Electric Staged Heat

Page 22: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Controller Expansion Module Wiring

22 VAV/Zone Controller Package

INSTALLATION & WIRING

Typical Wiring ForSingle Duct TerminalWith Modulating HotWater Heat

Typical Wiring ForFan Terminal WithModulating HotWater Heat

0-10 VDC ModulatingHot Water Valve

Supplied & WiredBy Others

0-10 VDC ModulatingHot Water Valve

Supplied & WiredBy Others

0-10 VDC

0-10 VDC

GND

GND

AOUT

AOUT

HWV

HWV

+

+

0-10 VDC

0-10 VDC

_

_

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

E-BUSEBC Cable

E-BUSEBC Cable

WattMaster Part #OE325-03Zone Controller Expansion Module

WattMaster Part #OE325-03Zone Controller Expansion Module

24VAC

24VAC

24VAC

COM

COM

COM

24 VAC Transformer Supplied& Wired by Others. Size ForRequired HW Valve Load.

24 VAC Transformer Supplied& Wired by Others. Size ForRequired HW Valve Load.

24 VAC Transformer Supplied & Wired byOthers. Size For Required Fan Relay Load.

R1

24 VAC FanRelay Supplied& Wired By Others.1 Amp Max. Load.

Connect to VAV/ZoneController E-BUSFemale Connector

Connect to VAV/ZoneController E-BUSFemale Connector

RC

R1

Figure 13: VAV/Zone Controller Expansion Module Wiring - Fan Terminals And/Or On/Off HW Heat

Typical Wiring For SingleDuct Terminal Unit WithOn/Off Hot Water Heat

Typical Wiring For FanTerminal Unit With On/OffHot Water Heat

WattMaster Part #OE325-03Zone Controller Expansion Module

WattMaster Part #OE325-03Zone Controller Expansion Module

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

24VAC

24VAC

COM

COM

R1

24 VAC Transformer Supplied& Wired by Others. Size ForRequired Fan Relay &Hot Water Valve Load

24 VAC Transformer Supplied& Wired by Others. Size ForRequired HW Valve Load.

24 VAC Fan RelaySupplied & WiredBy Others. 1 AmpMax. Load.

HWV

HWV

24 VAC On/OffHW ValveSupplied & WiredBy Others.1 Amp Max. Load

24 VAC On/OffHW ValveSupplied & WiredBy Others. 1 Amp GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

E-BUSEBC Cable

E-BUSEBC Cable

Connect to VAV/ZoneController E-BUSFemale Connector

Connect to VAV/ZoneController E-BUSFemale Connector

RC

RC

R2

R2

R1

Figure 12: VAV/Zone Controller Expansion Module Wiring - Fan Terminals And/Or Modulating HW Heat

Page 23: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Controller Expansion Module Wiring

Typical Wiring ForSingle Duct TerminalWith SCR Electric Heat

Typical Wiring ForFan Terminal WithSCR Electric Heat

0-10 VDC

0-10 VDC

GND

GND

AOUT

AOUT

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

Remove Control Boardfrom Snaptrack & MountSnaptrack on Box

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5

X1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1

C11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

GND

AOUT

COMM

STAT

ALRM

PWR

COM

R2

R1

GND

P1

R17R16R15

R14

R13

R12

R11

R10

D8

D7

D6

D5X

1

U6

U5

U4

U3

U2

U1

TB2

TB1

R9R8

R7 R6

R5

R4

R3

R2 R1

Q4

Q3

Q2

Q1

J1

D4

D3

D2

D1

C10

C9

C8

C7

C6

C5C4

C3 C2

C1

BIN1C

11 D13

R18

R19

R20

TB3

U7

U8

YS

10

25

32

RE

VR

0A

WA

TT

MA

ST

ER

CO

NT

RO

LS

,IN

C

MA

DE

INU

SA

R4

R3

LM

78

05

.1uF

1uF

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002 1002

1002

.1uF

.1uF .1uF

.1uF

.1uF

.1uF .1uF

.1uF

.1uF

1002

LM358

04

04

04

LT

17

85

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

10A250VAC~5A30VDC

SA

VDE

G5Q-1A4OMRON

DC12V

CHINA

E-BUSEBC Cable

E-BUSEBC Cable

WattMaster Part #OE325-03Zone Controller Expansion Module

WattMaster Part #OE325-03Zone Controller Expansion Module

24VAC

COM

24 VAC Transformer Supplied & Wired byOthers. Size For Required Fan Relay Load.

R1

24 VAC FanRelay Supplied& Wired By Others.1 Amp Max. Load.

Connect to VAV/ZoneController E-BUSFemale Connector

Connect to VAV/ZoneController E-BUSFemale Connector

RC

R1

SCR

SCR

0-10 VDC SCRElectric HeatControllerSupplied & WiredBy Others

0-10 VDC SCRElectric HeatControllerSupplied & WiredBy Others

Figure 14: VAV/Zone Controller Expansion Module Wiring - Fan Terminals And/Or SCR Electric Heat

23VAV/Zone Controller Package

INSTALLATION & WIRING

Page 24: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Slaved Zone Damper Wiring

For large zones, it may be necessary to have more than one air damper controlled by a VAV/Zone Controller Package and its associated space sensor. The Orion system allows for connecting up to two additional Slaved Zone Dampers to the master VAV/Zone Controller Package. Slaving is not available for pressure independent damper applications.

NOTE: Each slaved actuator is considered a modular device rated at 6 VA each. This 6 VA load must be included in the transformer sizing. See the previous section regarding transformer sizing for complete information.

Two Slave Wiring Adapters consisting of a slave wiring interface card and modular cable are supplied with the OE523 Round Slaved Zone Damper, OE738 Slaved VAV/Zone Rectangular Damper Kit, and the OE282-03 Slaved VAV/Zone Damper Kit. These are required when attaching slave actuator(s) to the master zone damper. One slave wiring interface card should be mounted near the control enclosure of the master VAV/Zone Controller Package. It is mounted by fastening the plastic snap-track to suit-able sheet metal mounting surface with the sheet metal screws provided. The other card is mounted in the control enclosure of the slaved zone damper. Run 24 AWG minimum wire between the slave wiring interface cards. Connect modular cables to the slave wiring interface cards and to the zone actuators as shown. See Figure 15, below for complete wiring details.

Figure 15: Slaved Zone Damper Wiring & Connection Diagram

Slaved Zone Damper Wiring

SLAVED- ZONE ACTUATOR #2 SLAVED-ZONE ACTUATOR #1

MODULARCABLE

MODULARCABLE

( 101824) BYPASS ANDSLAVE INTERFACE CARDPL

OE326-23D-ORVAV/ZONE CONTROLLER

(PL101824) BYPASS ANDSLAVE INTERFACE CARD

(PL101824) BYPASS ANDSLAVE INTERFACE CARD

HZ000095 MODULAR CABLE

HZ000095 HZ000095

FR

OM

ZO

NE

CO

NT

RO

LLE

R

BY

PA

SS

AN

DS

LAV

E IN

TE

RFA

CE

YS

1018

24

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

FR

OM

ZO

NE

CO

NT

RO

LLE

R

BY

PA

SS

AN

DS

LAV

E IN

TE

RFA

CE

YS

1018

24

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

FR

OM

ZO

NE

CO

NT

RO

LLER

BY

PA

SS

AN

DS

LAV

E IN

TE

RFA

CE

YS

101824

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2 LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

APPLIES TO WIRING THE OE520-XX-PT PRESSURE DEPENDENT ROUND ZONE DAMPER, THE OE736-03-PT PRESSUREDEPENDENT RECTANGULAR ZONE DAMPER AND THE OE742-01P-VAVZ ZONE CONTROLLER ACTUATOR PACKAGE.

VAV/ZONE CONTROLLER & ACTUATOR

SLAVED ZONE DAMPER ASSEMBLY #1

SLAVED ZONE DAMPER ASSEMBLY #2 (IF USED)

OE282 OE282

OE282

(PL101824) BYPASS ANDSLAVE INTERFACE CARD

FR

OM

ZO

NE

CO

NT

RO

LLER

BY

PA

SS

AN

DS

LAV

E IN

TE

RFA

CE

YS

101824

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2 LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

SECOND SLAVE INTERFACECARD NOT USED IN THIS

APPLICATION

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

MOUNT ONE BYPASS & SLAVE INTERFACE CARDWITHIN 1 FOOT OF ZONE CONTROLLER &ACTUATOR. CONNECT TO ZONE CONTROLLER ANDACTUATOR WITH SUPPLIED CABLES. WIRE TOSECOND (AND THIRD WHEN USED) SLAVEINTERFACE CARD WITH 24 GAUGE MINIMUM WIRE.

24 VAV/Zone Controller Package

INSTALLATION & WIRING

Page 25: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Addressing & Baud Rate

Figure 16: Address and Baud Rate Switch Setting

Controller Addressing & Baud Rate Setting

Before applying power for the fi rst time, it is very important to correctly address the controller and run through a few simple checks.

If the VAV/Zone Controller is to operate as a Stand Alone con-troller (not connected to any other HVAC unit or VAV/Zone Controller(s)), the controller address switch should be set for address 1. When the VAV/Zone Controller is to be connected to other VAV/Zone Controllers on a communication loop, each VAV/Zone Controller’s address switch must be set with a unique address between 1 and 58.

Address Switch Shown IsSet For Address 9

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

The Address For Each ControllerMust Be Between 1 And 58 And Be

Unique To The Other ControllersOn The Local Loop

OFFON

ADDRESSOFF

ON

ADDRESS

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

RE

V1

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

10

25

88

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

CU

S

R

Wa

ttM

aste

rLabel

#L102318

Re

v.:

01

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+12

VD

C

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23D-ORP.D. VAV CONTROLLER/ZONE

www.orioncontrols.com

OF

F

ADDRESS

1

2

4

8

16

32

ON

LO

OP

BA

UD

1

2

NOTE:The Power To The Controller Must Be Removed AndReconnected After Changing The Address Switch Settings InOrder For Any Changes To Take Effect.

CAUTION:Disconnect All Communication Loop Wiring From TheController Before Removing Power From The Controller.Reconnect Power And Then Reconnect Communication LoopWiring.

Baud Loop Switch 1 Should BeSet To And Baud Loop Switch2 Should Be Set To As Shown.See Baud Rate Table For Exceptions.

OFFON

BAUD RATE SELECTION

Switch 1 Switch 2

9600

Baud

57600

OFF OFF

ONOFF

CommLink IV

Communication Setting

CommLink 5 Set at High Speed*or VAV/Zone Controller

is Stand Alone

9600 OFF OFF CommLink 5 Set at Low Speed*

* The CommLink 5 must be set to Low Speed if it is being usedon a system that includes the VCM-X Controller or oldergeneration of Orion Controllers.** The CommLink 5 can be set to High Speed if is being usedon a system that only includes VCC-X, VCB-X, or GPC-XPControllers.

When programming the VAV/Zone Controller on a Stand Alone or Interconnected System and you are asked to enter the Unit ID, you would enter the address for the controller you wish to program. When programming the VAV/Zone Controller on a Networked System and you are asked to enter the Unit ID, you would fi rst enter the MiniLink PD loop address for the loop the VAV/Zone Controller Package is connected to and then enter the VAV/Zone Controller’s address. See Figure 16, below for a diagram depicting address switch settings.

Baud Rate Address switches 1 and 2 are used for the baud rate selection. See Figure 16, below for baud rate setting information.

25VAV/Zone Controller Package

START-UP & COMMISSIONING

Page 26: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Initialization and Operator Interfaces

Figure 17: Operator Interfaces

Initialization

On system power-up, the “STAT 1” & “STAT 2” LEDs are ex-tinguished for a few seconds, and then STAT1 fl ashes a set of 3 fl ashes fi ve times. After that, STAT2 fl ashes the number of the address switch setting, so if the address switch is set to 7, STAT2 will fl ash 7 times. If the address is higher than 9, both STAT 1 and 2 will fl ash with STAT1 fl ashing the 10s and STAT2 fl ashing the 1s. For example, if the address is 34, STAT1 will fl ash 3 times and STAT2 will fl ash 4 times. After the address is fl ashed, there is a short delay and then the controller will go into damper calibration and the ACTUATOR LEDs will come on. The CW LED will be on while the actuator is driving clockwise, and the CCW LED will light when the damper is driving counter-clockwise. When the calibration is completed, the normal diagnostic fl ashes of STAT2 will be begin. If everything is operating correctly, STAT2 LED will blink once every 10 seconds. If there is a problem with the controller, STAT2 LED will blink more than once. These diagnostic fl ashes are described in the Troubleshooting section of this manual..

Operator Interfaces

The next step is confi guring the controller for your specifi c re-quirements. In order to confi gure the VAV/Zone Controller, you must use an operator interface. Four different operator interfaces are available for programming and monitoring of the VAV/Zone Controller. See Figure 17. They are as follows:

• Modular Service Tool SD• Modular System Manager SD• Computer with Prism 2 Software & CommLink 5 Installed• System Manager TS-L (Touch Screen - Limited Access)

Any of these devices or a combination of them can be used to access the status, confi guration, and setpoints of any controller on your communications loop.

If using the Modular Service Tool SD or the Modular System Manager SD for programming, refer to your HVAC Unit Control-ler’s Operator Interface SD Technical Guide. If using a computer and the Prism 2 software for programming, refer to the Prism 2 Technical Guide. If using the System Manager TS-L for moni-toring, please see the System Manager TS-L Technical Guide.

No matter which operator interface you use, we recommend that you proceed with the programming and setup of the VAV/Zone Controller in the order that follows:

1. Confi gure the controller for your application. 2. Program the Controller setpoints. 3. Review Controller Status Screens to verify system

operation and correct Controller confi gurations.

26 VAV/Zone Controller Package

START-UP & COMMISSIONING

Page 27: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Configuration & Setup

27VAV/Zone Controller Package

START-UP & COMMISSIONING

VAV/Zone Controller Confi guration & SetupConfi guration can be accomplished by using either the Modular Service Tool SD, Modular System Manager SD, or a computer with Prism 2 software installed. Several options are available to confi gure the VAV/Zone Controller for the appropriate equip-ment it is installed on. All of these options can be set from the Confi guration Menu or Confi guration Screens with the exception of “AHU Heating Call Setpoint” which is set from the Setpoints Menu or Setpoints Screens.

Box Control MethodSet this confi guration item for the type of box the VAV/Zone Controller is used on. All options below are available with and without reheat. The options are:

• Cooling Only Box (VAV)• Heating/Cooling Changeover Box (Zoning)• Series Fan Powered Box (VAV & Zoning)• Parallel Fan Powered Box (VAV & Zoning)

Damper Operating ModeThis option sets the direction of rotation the damper moves when driving towards its full open position. The options available are:

• Direct Acting ( Clockwise-to-Open Damper)• Reverse Acting ( Counterclockwise-to-Open Damper)

NOTE: The Default is Direct Acting, which means that when looking at the damper shaft, the damper rotates clockwise to open. When the operating mode is changed, the damper will re-calibrate.

Voting ZoneWhen the VAV/Zone Controller is being used on a Zoning sys-tem as opposed to a true VAV system, this option must be set to allow the MiniLink to determine if this controller should be included in the zoning system voting process. If this is set to Yes, this controller will be included in the voting process. If this is a zoning system and it is set to No, this controller will not vote in the zoning system voting process. If this is a true VAV system, the option should be set to No. A maximum of 16 voting zones can be confi gured. The options available are:

• Yes• No

Pressure Independent Boxes-Airfl ow @ 1” W.C.If this is a pressure independent box, this option allows you to calibrate the box CFM correctly using the box manufacturer’s “K” factor. Enter the correct “K” ( CFM) factor for the inlet diameter of the box you are confi guring. See the “K” factor table that fol-lows if you are using the Round VAV/Zone Dampers.

Airfl ow @ 1” W.C. Across Airfl ow PickupOn Round Damper

Damper Size K-Factor (CFM) Velocity (FPM)6” Nominal Dia. 448 22828” Nominal Dia. 904 259010” Nominal Dia. 1436 263312” Nominal Dia. 1891 240814” Nominal Dia. 3015 282016” Nominal Dia. 3889 2749

NOTES: K-Factor in the table is corrected to 70 °F @ 1000 ft. elevation. For other elevations add 2% for each additional 1000 ft. of elevation.

Add 1% for each additional 10 degrees of temperature increase.

Expansion Relays - Steps of ReheatIf the box has Reheat supplied by an Electric Coil, this option must be set for the number of Electric Heating stages on the box. If the box has Hot Water Heat with a 2 position Hot Water Valve, set the number of stages to 1. For Hot Water Heat with a proportional Hot Water Valve, this must be set for 0. Options available are:

• No Staging• 1 Stage of Reheat• 2 Stages of Reheat• 3 Stages of Reheat

Proportional Heating SignalIf the box has Hot Water Reheat using a proportional Hot Water Valve, set this option to match the voltage signal required by the Hot Water Valve you are using. Options available are:

• 0-10 VDC Voltage Signal• 2-10 VDC Voltage Signal

Allow Box Heat With AHU HeatIf the box you are using has Reheat or Auxiliary Heat, confi gur-ing this setting to 1=Yes will allow the box Heat to operate at the same time as the HVAC unit Heat. Options available are:

• No• Yes

Multiple Daily Setpoints/SchedulesBy clicking on the “Use Schedule Space Setpoints” box, in the Prism Setpoints/Confi guration screen, you can set up to 5 Tem-perature Setpoint periods in a 24 hour period. You can select a Cooling and Heating Setpoint for the period from Midnight to the fi rst event, then different setpoints from the fi rst event to second event, then the second event to third event, then the third event to fourth event, and fi nally from the fourth event to midnight. Each of the event times and temperatures are confi gurable.

Table 2: Airfl ow K-Factor ( CFM) Requirements

Page 28: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

28 VAV/Zone Controller Package

START-UP & COMMISSIONINGVAV/Zone Controller Configuration & Setup

Main Fan StatusIf the VAV/Zone Controller is installed on a non-fan powered box that has Reheat, set this option to Yes in order to enable box Reheat only when the HVAC unit fan is running. A full description of how this setting affects the various box types in the occupied and unoccupied modes is contained in the Occupied Mode Sequences and Unoccupied Mode Sequences that follow later in this manual. Options available are No - Heat can operate without fan or Yes - Heat cannot operate without fan.

Push-Button Override Group ID#During Unoccupied Mode, all VAV/Zone Controllers with a cor-responding Group ID# will resume Occupied operation whenever any of the VAV/Zone Controllers with the same Group ID # has its push-button depressed to initiate an override condition. This allows you to group zones in various areas of the building. For example, individual tenants with several offi ces could restore occupied mode for just their zones and not affect other zones in the building.

The default group ID number for all VAV/Zone Controllers is set at the factory as 1. If you don’t want a specifi c zone(s) to be part of that group, you must give each one a distinct group number between 2 and 16.

NOTE: WattMaster recommends that your groups consist of at least 3 zones to ensure minimum airfl ow across the HVAC unit coil.

Dump ZoneThe dump zone is a controller without an actuator that is used to control a duct heater or Auxiliary Heat. If this VAV/Zone Controller is to be used as a Dump Zone, set this confi guration to 1=Yes. Options available are Yes or No.

AHU Heating CallThis setting is located under the Setpoints Menu or Setpoints Screens and is used only for the Unoccupied mode. For Non-Fan Powered Terminal units, this temperature setpoint is used to al-low a heating device such as baseboard heaters to be energized in an attempt to satisfy the heating demand prior to initiating the HVAC unit’s Supply Air Heating Mode. For Fan Powered Terminal Units, this setpoint can be used to operate the Series or Parallel box to satisfy the heating demand by using plenum air and reheat prior to initiating the HVAC Supply Air Heating Mode.

During unoccupied mode, when the temperature in the space drops below the AHU Heat Call setpoint, the VAV/Zone Control-ler sends a signal to the Unit Controller to initiate the HVAC unit Supply Air Heating Mode. This setpoint temperature can be set higher or lower than the Space Heating Setpoint.

NOTE: This setpoint follows the Unoccupied Heating Setpoint Setback.

Auxiliary HeatThe Auxiliary Heat option allows for a separate setpoint that is different from the other heating setpoints. The Auxiliary Heat Relay energizes at 0.5ºF below the Auxiliary Heat Setpoint and de-energizes 0.5ºF above the Auxiliary Heat Setpoint. The Auxiliary Heat will continue to function regardless of the HVAC Mode the Unit Controller is in or at any airfl ow condition. This is typically used to control baseboard or other perimeter heat sources. See Table 3, page 31 for a complete layout of the vari-ous fan and heat relay staging points.

Expansion Relays – Steps of ReheatIf only 1 stage of box heat is required and this is not a Fan Termi-nal Unit, use the Auxiliary Heat relay on the VAV/Zone Controller and select “Used for BOX Re-heating” in the Confi guration. Also in “Stages of Box Re-Heat” confi gure for 1 stage.

If the box requires more than 1 stage of reheat, the OE325-03 VAV/Zone Controller Expansion Module must be used and 2 or 3 stages of heat must be selected. If a Fan Terminal Unit is used, use the OE325-03 VAV/Zone Controller Expansion Module for all stages of heat.

Box ReheatThe box heat will be energized whenever the Space Temperature drops below the Occupied Heating Setpoint and the damper will go to the Minimum Damper During Box Heating Mode setpoint.

Window Open DetectionWhen this feature is selected, if the contacts on terminals BIN and GND are open, the controller will control to the Unoccupied Cooling and Heating Setpoints, and when the contacts are closed, it will go control to the Occupied Cooling and Heating Setpoints. Normally closed operation can be selected by confi guring reverse contact polarity. See the VAV/Zone Controller Inputs and Outputs section for more details.

Motion Sensor Occupancy DetectionWhen this feature is selected, if the contacts on terminals BIN and GND are open, the controller will control to the Occupancy Cooling and Heating Setback Setpoints. When the contacts are closed, it will go back to the Occupied Cooling and Heating Set-points. Normally closed operation can be selected by confi guring reverse contact polarity. See the VAV/Zone Controller Inputs and Outputs section for more details.

Type of Space SensorChoose the type of Space Sensor that you are using - Analog or Digital.

Stand Alone Box Running Continuous Occupied ModeChoose if unit is a Stand-Alone Box that operates independently without requiring communication with the HVAC unit controller.

Page 29: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Scheduling & Operation Modes

29VAV/Zone Controller Package

SEQUENCE OF OPERATIONS

HVAC Modes of OperationThere are 7 possible modes of operation for the HVAC Unit and the VAV/Zone Controller. These modes are determined by the Supply Air Temperature (SAT) and/or space demand conditions. They are:

• Supply Air Vent Mode (Based on HVAC Unit SAT) This mode occurs when the Supply Air Temperature is within 2°F of the Space Temperature and stays in this mode until the Supply Air Temperature is above or below the Space Temperature plus or minus the Supply Air HVAC Mode Deadband.

Space Vent Mode (Based on VAV/Zone Controller Space Temp) This mode occurs when the Space Temperature is below the Cooling Setpoint and 1.0°F above the Heating Setpoint.

Scheduling Occupied/ Unoccupied Mode The VAV/Zone Controller monitors the communications loop for its Occupied and Unoccupied mode of operation command. Either the Unit Controller or a GPC-XP Controller can transmit the Oc-cupied command to the VAV/Zone Controller. This requires the VAV/Zone Controller Packages to all be connected to the system communication loop through their RS-485 connector and to be properly addressed for the command to be received.

Push-button Override OperationDuring unoccupied hours, you can force the VAV/Zone Controller and Unit Controller back to occupied operation by pressing the override button on the Modular Room Sensor or Digital Room Sensor. The operation for the push-button override sequence is different depending on which sensor you are using.

Standard Room SensorPushing the override button for less than 3 seconds initiates the override which will continue for a confi gurable duration of time (0-8 hours). If during the override period the button is pressed a second time for less than 3 seconds, an additional confi gurable du-ration of time (0-8 hours) will be added to the remaining override duration that is left at the time of pushing the button. Depressing the button between 3 and 10 seconds will cancel the override.

Digital Room SensorPushing the override button momentarily initiates the override which will continue for a confi gurable duration of time (0-8 hours). If during the override period the button is pressed a second time, it will cancel

Damper PositionsThe actual values for the minimum damper positions that are described in the following paragraphs can be confi gured by changing the values in the setpoint screens for the VAV/Zone Controller. These minimums are expressed in damper open percentages for pressure dependent terminal units or in CFM for pressure independent terminal units.

Cooling MinimumWhen the HVAC unit is in the Supply Air Cooling Mode but the space does not require cooling, the VAV/Zone damper will move to the Cooling Minimum position.

Heating MinimumWhen the HVAC unit is in the Supply Air Heating Mode but the space does not require Heating, the VAV/Zone damper will move to the Heating Minimum position.

Vent MinimumThis is the position the VAV/Zone damper will move to when the HVAC unit is in the Supply Air Vent Mode.

Supply Air Cooling Mode (Based on HVAC Unit SAT) This mode occurs when the Supply Air Temperature falls to less than the Space Temperature minus the Supply Air HVAC Deadband. To cancel the Supply Air Cooling Mode, the Supply Air Temperature must rise to within 2°F of the Space Temperature.

Space Cooling Mode (Based on VAV/Zone Controller Space Temp) This mode occurs when the Space Temperature rises above the Space Cooling Setpoint.

Supply Air Heating Mode (Based on HVAC Unit SAT) This mode occurs when the Supply Air Temperature rises to a temperature that is greater than the Space Temperature plus the Supply Air HVAC Deadband. To cancel the Supply Air Heating Mode, the Supply Air Temperature must fall to within 2°F of the Space Temperature.

Space Heating Mode (Based on VAV/Zone Controller Space Temp) This mode occurs when the Space Temperature falls below the Space Heating Setpoint.

Off Mode - (Not displayed) During Unoccupied Mode, the mode is considered OFF if the Space Temperature does not generate a Heating Mode or Cooling Mode based on the Unoccupied Heating & Cooling Setpoints.

Page 30: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

30 VAV/Zone Controller Package

SEQUENCE OF OPERATIONSVAV/Zone Occupied Mode Sequences

When the HVAC unit is in the Supply Air Cooling Mode, the damper is normally held at the Minimum Cooling Position until the Space Temperature begins to rise above the Occupied Cool-ing Setpoint. As the Space Temperature rises to within 0.5ºF of the Occupied Cooling Setpoint, the Damper/Airfl ow calculation causes the air valve to open proportionally until the Maximum Setpoint is achieved at 1.5ºF above the setpoint. This is a 2ºF Proportional Window starting 0.5ºF below the Occupied Cooling Setpoint to 1.5ºF above the Occupied Cooling Setpoint.

The Damper Position/Airfl ow is never allowed to modulate out-side the user-adjustable Minimum and Maximum setpoints. The Maximum Damper Position/Airfl ow Setpoint applies to Heating and Cooling modes of operation only. All of the modes have their own individual minimum setting.

Series Flow Fan TerminalsIf the VAV/Zone Controller has been confi gured as a Series Fan Powered terminal unit, the series fan relay will activate and run the series box fan continuously anytime the HVAC unit fan is running.

In all cases, before the series box fan can be activated, the air damper is driven fully closed and held that way for 30 seconds to make sure the series box fan hasn’t inadvertently started to spin backwards. Once the series box fan starts, it waits an additional 10 seconds to allow the fan to spin up before it starts to open the damper and introduce airfl ow from the HVAC unit fan.

Parallel Flow Fan TerminalsDuring normal cooling or vent mode and adequate air supply, the parallel fan will be off. During the Occupied Cooling Mode, the fan will only activate if the damper/airfl ow is below a user-defi ned low limit setting. This causes it to be used as a supplemental air source. When the damper/airfl ow rises 15% above the low limit setpoint, the fan will be deactivated.

NOTE: A VAV/Zone Controller Expansion Module is required for each VAV/Zone Controller used when you are using a Fan Terminal even if you do not have any heat requirements. All Single Duct Terminal Units with multiple heat stages or modulating heat also require a VAV/Zone Controller Expansion Module.

Night MinimumThis is the position that the damper moves to during the Unoc-cupied mode. When using non-fan powered terminal units, the VAV/Zone damper will position itself in the Night Minimum position. In order for fan powered terminal units to position the damper to the Night Minimum position, the check for main fan status must be selected, and the HVAC unit fan must be operating.

Box Heating MinimumThis is the position that the damper moves to when Reheat is initiated. If the VAV/Zone Controller is used on a terminal unit that has reheat, the VAV/Zone damper will move to the Reheat position whenever a Space Heating demand occurs and the HVAC unit is in Supply Air Cooling or Vent Mode. When the HVAC unit is in Supply Air Heating Mode, the VAV/Zone damper will modulate as required to maintain the Space Heating Setpoint.

Occupied Mode Sequences

Space Vent ModeThis mode only applies to the Occupied Mode of operation. If the equipment is in the Unoccupied Mode, then a lack of heating or cooling demand would generate the Off Mode.

If the HVAC unit is in Supply Air Vent Mode, you can adjust the damper position on pressure dependent terminal units and the airfl ow on pressure independent terminal units to provide a fi xed amount of ventilation air into the space when there are no heating or cooling demands. During this time, the damper does not modulate on pressure dependent terminal units. On pressure independent terminal units, it only modulates to the extent re-quired to maintain the Vent Minimum Airfl ow setting.

If the VAV/Zone Controller detects that the HVAC unit is in Sup-ply Air Heating Mode, indicating that the air handler has activated its heat, the Heating Airfl ow Minimum will be substituted for the Vent Minimum.

If the VAV/Zone Controller detects that the HVAC unit is in Sup-ply Air Cooling Mode, indicating that the air handler has activated its cooling, the Cooling Airfl ow Minimum will be substituted for the Vent Minimum.

Space Cooling ModeOccupied Space Cooling mode is initiated by the temperature in the space rising to within 0.5ºF of the Occupied Cooling Setpoint.

If the HVAC unit is in the Supply Air Heating Mode and another VAV/Zone Controller has a cooling demand, the Damper Posi-tion/Airfl ow for the VAV/Zone Controller requiring cooling will position itself to provide the Heating Minimum Damper Position/Airfl ow Setpoint amount of air into the space. No modulation open will occur because the space does not want the warm air currently being supplied by the air handler.

Page 31: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Occupied Mode Sequences

31VAV/Zone Controller Package

SEQUENCE OF OPERATIONS

Space Heating ModeOccupied Space Heating mode is initiated by the temperature in the space falling to within 0.5ºF of the Occupied Heating Setpoint.

If the HVAC unit is in the Supply Air Cooling Mode and another VAV/Zone Controller has a heating demand, the damper/airfl ow for the VAV/Zone Controller requiring heating will position itself to provide the Cooling Minimum amount of air into the space. No modulation open will occur because the space does not want the cold air currently being supplied by the air handler.

When the HVAC unit is in the Occupied Supply Air Heating Mode, the damper will be held at the Heating Minimum posi-tion until the space temperature falls to within 0.5ºF of the Oc-cupied Heating Setpoint. As the Space Temperature falls below the Heating Setpoint, the damper/airfl ow calculation causes the air valve to open proportionally until the maximum setpoint is achieved at 1.5ºF below the setpoint. This is a 2ºF proportional window starting 0.5ºF above the Heating Setpoint to 1.5ºF below the Heating Setpoint.

Two different confi gurations are available for the Occupied Space Heating Mode. If the box is confi gured to allow reheat during Supply Air Heating Mode, the reheat relays can be activated even when the HVAC unit is in the Supply Air Heating Mode. If the box is confi gured not to allow reheat when the HVAC unit is in Supply Air Heating Mode, the box heat relays will be de-energized when the HVAC unit is in Supply Air Heating mode. In either confi guration, when the HVAC unit is in the Supply Air Heating Mode, the damper will modulate open proportionally to the space demand. The proportional window for the space temperature is to 1.5ºF below the Heating Setpoint. This allows the space to take advantage of the warm supply air in the duct.

The VAV/Zone Controller can activate auxiliary heating relays. Multiple heat stages or modulating heat can activate if the Ex-pansion Module has been connected and the correct number of additional heating stages (2 or 3) has been confi gured. During demands for Heat, the fi rst stage will activate whenever the space temperature drops below the Heating Setpoint. The second stage will activate if the Space Temperature falls 1.0ºF below the Heat-ing Setpoint. The third stage will activate if the Space Tempera-ture falls 2.0ºF below the Heating Setpoint. There is a two-minute delay between staging. This prevents stages from activating at the same time. Once a Heating Stage has been activated, it must remain on for at least one minute. Once it has been deactivated, it must remain off for at least two minutes. The third stage relay will deactivate when the Space Temperature rises to within 1.0ºF of the Heating Setpoint. The second stage relay will deactivate when the Space Temperature rises to the Heating Setpoint. The fi rst stage relay will deactivate when the Space Temperature rises above the Heating Setpoint by 1.0ºF. See Table 3 for a complete layout of the various Fan & Heat relay staging points.

Modulating ( Proportional) HeatThe VAV/Zone Controller Package with the Zone Controller Expansion Module provides an analog output for control of a Modulating Hot Water Valve or SCR Electric Heater. It provides a 0-10 VDC signal to control the heating device. When the space temperature drops to 0.5ºF above the Heating Setpoint the output starts at 0 VDC and ramps up to 10 VDC at 1.5 below the Heat-ing Setpoint.

Auxiliary HeatThe Auxiliary Heat option allows for a separate setpoint that is different from the other heating setpoints. The Auxiliary Heat Relay energizes at 0.5ºF below the Auxiliary Heat Setpoint and de-energizes 0.5ºF above the Auxiliary Heat Setpoint. The Auxiliary Heat will continue to function regardless of the HVAC Mode the Unit controller is in or at any airfl ow condition. This is typically used to control baseboard heat or an external duct heater. See Table 3 for a complete layout of the various fan and heat relay staging points.

Fan & Reheat Relay Staging

Relays Stage On At

SeriesFan

ParallelFan

Heat Stage

1

Heat Stage

2

Heat Stage

3

Aux.Heat

0.5ºF Above Box Heat Setpoint

ON With HVAC Fan

*See Note 1

X

At Box Heat Setpoint X

1.0ºF Below Box Heat Setpoint X

2.0ºF Below Box Heat Setpoint X

0.5ºF Below Aux. Heat Setpoint

X

Relays Stage Off At

SeriesFan

ParallelFan

Heat Stage

1

Heat Stage

2

Heat Stage

3Aux.Heat

1.0ºF Above Box Heat Setpoint

OFF With HVAC FanSee Note 1

XSee

Note 2

1.0ºF Above Box Heat Setpoint X

At Box Heat Setpoint X

1.0ºF Below Box Heat Setpoint X

0.5ºF Above Aux. Heat Setpoint

X

NOTES:: 1.) If check for main fan status is selected when confi guring the controller, the series fan will energize anytime the HVAC unit’s fan is operating, even in the unoccupied mode.2.) The parallel fan will continue to run for 2 minutes following the relay stag-ing off.

Table 3: Fan & Reheat Relay Staging

Page 32: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Unoccupied Mode Sequences

32 VAV/Zone Controller Package

SEQUENCE OF OPERATIONS

Series Flow Fan TerminalsIf the VAV/Zone Controller has been confi gured as a Series Fan Powered terminal unit, the series fan relay will activate and run the series box fan continuously anytime the HVAC unit fan is running.

In all cases, before the series box fan can be activated, the air damper is driven fully closed and held that way for 30 seconds to make sure the series box fan hasn’t inadvertently started to spin backwards. Once the series box fan starts, it waits an additional 10 seconds to allow the fan to spin up before it starts to open the damper and introduce airfl ow from the HVAC unit fan.

Parallel Flow Fan TerminalsOn parallel fan powered terminal units, the fan will run when-ever Space Heating Mode is active. At all other times, the fan will only activate if the damper/airfl ow is below a user defi ned low limit setting. This causes it to be used as a supplemental air source. When the damper/airfl ow rises 15% above the low limit setpoint, the fan will be deactivated if there are no heating stages active, and no space demand exists.

The check for main fan status setting has no effect on the Parallel Fan box when in the occupied mode. The Parallel Fan will only be energized when in the Space Heating Mode.

Unoccupied Mode Sequences

Space Vent ModeThis mode only applies to the Occupied Mode of operation. If the equipment is in the Unoccupied Mode, then a lack of Heating or Cooling demand would generate “No Space Demand” on the Unit Controller display.

Space Cooling ModeDuring Unoccupied Mode, the HVAC unit is normally off. Unoc-cupied Space Cooling Mode is initiated by the temperature in the space rising to within 0.5ºF of the Unoccupied Cooling Setpoint.

If the HVAC unit is in the Unoccupied Supply Air Heating Mode because one or more of the VAV/Zone Controllers has a Heating demand and another VAV/Zone Controller has a Cooling demand, the damper/airfl ow for the VAV/Zone Controller requiring Cool-ing will position itself to provide the Heating Minimum Setpoint amount of air into the space. No modulation open will occur because the space does not want the warm air currently being supplied by the air handler.

When the HVAC unit is in the Unoccupied Supply Air Cooling Mode, the damper will be held at the Night Minimum Position until the Space Temperature begins to rise above the Cooling Setpoint. As the Space Temperature rises to within 0.5ºF of the Unoccupied Cooling Setpoint, the damper/airfl ow calculation causes the air valve to open proportionally until the maximum setpoint is achieved at 1.5ºF above the setpoint. This is a 2ºF proportional window starting 0.5ºF below the Cooling Setpoint to 1.5ºF above the Cooling Setpoint.

The damper/airfl ow is never allowed to modulate outside the user-adjusted minimum and the maximum setpoints. The Maximum Damper/Airfl ow Setpoint applies to Heating and Cooling Modes of operation only. All of the modes have their own individual minimum setting.

Series Flow Fan TerminalsIf the VAV/Zone Controller has been confi gured as a Series Fan Powered terminal unit and “Check for Main Status” has been selected, the series fan relay will activate and run the series box fan continuously anytime the HVAC unit fan is running. The damper will be held at the Night Minimum Position until the Space Temperature begins to rise above the Cooling Setpoint. If “Check for Main Status” has not been selected, the series fan relay will activate and run the series box fan when in the Space Cooling Mode. The damper will be in the fully closed position until the Space Temperature begins to rise above the Cooling Setpoint.

In all cases, before the series box fan can be activated, the air damper is driven fully closed and held that way for 30 seconds to make sure the series box fan hasn’t inadvertently started to spin backwards. Once the series box fan starts, it waits an additional 10 seconds to allow the fan to spin up before it starts to open the damper and introduce airfl ow from the HVAC unit fan.

Parallel Flow Fan TerminalsIn the Unoccupied Cooling Mode, the parallel fan will be off whether “Check for Main Status” has been selected or not. If “Check for Main Status” has been selected, the damper will be held at the Night Minimum Position until the Space Temperature begins to rise above the Cooling Setpoint. If “Check for Main Status” has not been selected, the damper will be held in the fully closed position until the Space Temperature begins to rise above the Cooling Setpoint.

Page 33: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

33VAV/Zone Controller Package

SEQUENCE OF OPERATIONSVAV/Zone Unoccupied Mode Sequences

Space Heating ModeDuring Unoccupied Mode, the HVAC unit is normally off. Un-occupied Space Heating Mode is initiated by the temperature in the space falling to within 0.5ºF of the Unoccupied Space Heating Setpoint.

If the HVAC unit is in the Unoccupied Supply Air Cooling Mode because one or more of the VAV/Zone Controllers has a cooling demand and another VAV/Zone Controller has a heating demand, the damper/airfl ow for the VAV/Zone Controller requiring heat-ing will position itself to provide the Night Minimum Position Setpoint amount of air into the space. No modulation open will occur because the space does not want the cold air currently being supplied by the air handler.

When the HVAC unit is in the Unoccupied Supply Air Heating Mode, the damper will be held at the Night Minimum Position until the Space Temperature begins to fall below the Unoccupied Heating Setpoint. As the Space Temperature falls to 0.5ºF below the Unoccupied Heating Setpoint, the damper/airfl ow calculation causes the air valve to open proportionally until the maximum setpoint is achieved at 1.5ºF below the setpoint. This is a 2ºF proportional window starting 0.5ºF above the Heating Setpoint to 1.5ºF below the Heating Setpoint.

As with the Occupied Mode of operation, two different confi gura-tions are available for the Unoccupied Space Heating Mode. If the box is confi gured to allow reheat during Supply Air Heating Mode, the reheat relays can be activated even when the HVAC unit is in the Supply Air Heating Mode. If the box is confi gured not to allow reheat when the HVAC unit is in Supply Air Heating Mode, the box heat relays will be de-energized when the HVAC unit is in Supply Air Heating Mode. In either confi guration, when the HVAC unit is in the Supply Air Heating Mode, the damper will modulate open proportionally to the space demand. The proportional window for the space temperature is 0.5ºF above to 1.5ºF below the Heating Setpoint. This allows the space to take advantage of the warm supply air in the duct.

If “Check for Main Status” is not selected and the VAV/Zone terminal unit has auxiliary heat (baseboard heat etc.) that does not require the HVAC unit fan to operate, reheat can be used without the HVAC unit fan operating. If “Check for Main Status” is selected, the reheat will only operate when the HVAC unit fan is operating.

The VAV/Zone Controller can activate auxiliary heating relays. Multiple heat stages or modulating heat can activate if the Ex-pansion Module has been connected and the correct number of additional heating stages (2 or 3) has been confi gured. During demands for Heat, the fi rst stage will activate whenever the Space Temperature drops below the Heating Setpoint. The second stage will activate if the Space Temperature falls 1.0ºF below the Heat-ing Setpoint. The third stage will activate if the Space Tempera-ture falls 2.0ºF below the Heating Setpoint. There is a two-minute

delay between staging. This prevents stages from activating at the same time. Once a heating stage has been activated, it must remain on for at least one minute. Once it has been deactivated, it must remain off for at least two minutes. The third stage relay will deactivate when the Space Temperature rises to within 1.0ºF of the Heating Setpoint. The second stage relay will deactivate when the Space Temperature rises to the Heating Setpoint. The fi rst stage relay will deactivate when the Space Temperature rises above the Heating Setpoint by 1.0ºF. See Table 3, page 31 for a complete layout of the various fan & heat relay staging points.

Modulating ( Proportional) HeatThe VAV/Zone Controller Package also provides an analog output for control of a Modulating Hot Water Valve or SCR Electric Heater. It provides a 0-10 VDC signal to control the heating device. When the Space Temperature drops to 0.5ºF above the Unoccupied Heating Setpoint, the output starts at 0 VDC and ramps up to 10 VDC at 1.5 below the Heating Setpoint.

Auxiliary HeatThe Auxiliary Heat option allows for a separate setpoint that is different from the other heating setpoints. The Auxiliary Heat Relay energizes at 0.5ºF below the Auxiliary Heat Setpoint and de-energizes 0.5ºF above the Auxiliary Heat Setpoint. The night offsets would apply to these values. The Auxiliary Heat will continue to function regardless of the HVAC Mode the Unit Controller is in, or at any airfl ow condition. This is typically used to control baseboard heat or an external duct heater.

Series Flow Fan TerminalsIf the VAV/Zone Controller has been confi gured as a Series Fan Powered terminal unit, the series fan will run continuously when the VAV/Zone Controller is in the Space Heating Mode, no matter whether check for main fan status has been selected or not. If the HVAC unit is in Supply Air Heating Mode, the damper will modulate to maintain the Space Heating Setpoint.

Any series fan terminal unit that has “Check for Main Status” selected will also operate its series box fan anytime the HVAC unit controller is broadcasting that the HVAC unit fan is operating, regardless of whether it is calling for heat or not. The damper will be held at the closed position until the main fan status broadcast is received. Once the broadcast is received, the damper will then move to its Reheat Minimum position. If “Check for Main Status” has not been selected, the series box fan will only activate and run when it is in Space Heating Mode. When in Space Heating Mode, the damper will move to its Reheat Minimum position. When in Supply Air Heating Mode, the damper will modulate to maintain the Unoccupied Heating Setpoint.

In all cases, before the series box fan can be activated, the air damper is driven fully closed and held that way for 30 seconds to make sure the series box fan hasn’t inadvertently started to spin backwards. Once the series box fan starts, it waits an additional 10 seconds to allow the fan to spin up before it starts to open the damper and introduce airfl ow from the HVAC unit fan.

Page 34: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

34 VAV/Zone Controller Package

SEQUENCE OF OPERATIONS VAV/Zone Damper Control

Parallel Flow Fan TerminalsIf the VAV/Zone Controller has been confi gured as a Parallel Fan Powered terminal unit, the Parallel fan will run continuously when the VAV/Zone Controller is in the Space Heating Mode no matter whether “Check for Main Status” has been selected or not. At all other times, the fan will be off.

If “Check for Main Status” is selected, the damper will remain in the closed position until the HVAC unit controller is broadcast-ing that the HVAC unit fan is operating, regardless of whether it is calling for heat or not. The damper will be held at the closed position until the main fan status broadcast is received. Once the broadcast is received, the damper will then move to its Night Minimum position. If “Check for Main Status” has not been selected, the damper will stay in the closed position until Space Heating Mode is initiated. When in Space Heating Mode the damper will move to its Reheat Minimum position. When in Supply Air Heating Mode the damper will modulate to maintain the Unoccupied Heating Setpoint.

Damper ControlThe damper position is calculated by the demand from the space. This calculation can also include an optional Integral function. This prevents the damper/airfl ow from stagnating at a position somewhere above the setpoint because the Supply Air Temperature or Duct Pressure isn’t quite enough to satisfy the space at the currently calculated proportional position. The Integral causes the calculation to keep adding a small amount of the proportional error back into the damper/airfl ow position each time a new position is calculated. The amount the Integral adds back in is user-adjustable. This value is presented as a number between 0.0 and 10.0. That means that if the integral is less than 1.0, you are adding a percentage from 0 to 100% of the error back into the calculation. If you increase the Integral above 1.0, you are adding more than 100% back in.

With just proportional control, a 1ºF error would cause a 50% increase in damper/airfl ow if the Integral is not included. (1°F is half of the 2ºF Proportional Window).

If you had set the Integral to 1.0, the calculation would add 2% to the current damper/airfl ow calculation each time. The calcula-tion occurs once every 10 seconds, so it would take a little over 4 minutes to reach the programmed 100% maximum.

Example:

1. 50% Remaining / 2% Integral = 25 moves to get to a 100% Maximum2. 25 Moves times 10 seconds = 250 seconds or a little over 4 minutes to reach the 100% maximum damper/ airfl ow position.

Of course, different Space Temperature errors and different In-tegral values cause this calculation to operate slower or faster. It is up to the user to determine the optimum setting that provides the tightest temperature control without causing the damper to continue to hunt or modulate which causes premature wear of the actuator gears and motor.

On pressure dependent terminal units, the damper position is maintained to within ± 3% of the calculated position. No attempt is made to position the damper exactly on the calculated posi-tion. This reduces wear and tear on the actuator gears and motors and the amount of airfl ow involved is not affected by that small amount of damper error.

On pressure independent terminal units, the airfl ow is maintained to within roughly 3% of the terminal unit size constant but no tighter than 16 CFM on the smallest terminal units. The actual control window is based on the formula:

Window = Terminal unit size X Square Root (1 / 750)where Terminal unit size refers to the total rated CFM of the terminal unit

This sliding window allows the control to be much tighter on the smaller terminal units than can be achieved on the larger terminal units as far as CFM readings. On a large terminal unit, 25 CFM may not be noticeable, but on a small terminal unit, 25 CFM may be more than the minimum airfl ow setting for the space.

If the pressure sensor is disconnected or fails on a pressure in-dependent terminal unit, the controller automatically reverts to pressure dependent operation and generates an alarm to alert the user that a failure has occurred.

On either type of terminal unit, a space sensor failure will force the damper to position itself to the 50% of the maximum damper position setpoint, and it will not change until the sensor is repaired or replaced.

Page 35: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

35VAV/Zone Controller Package

SEQUENCE OF OPERATIONSZoning

Zoning

The Orion Control System can be confi gured to operate as a true zoning system with the addition of a MiniLink PD 5. The Mini-Link PD 5 acts as a loop manager receiving information from the VAV/Zone Controller Packages, interpreting this information, and then sending a heat, cool, or vent signal to the Unit Control-ler. Only 16 zones can be confi gured as voting zones per loop. Additional zones will be non-voting.

Zone PollingThe MiniLink PD 5 must be confi gured for zoning operation using the Modular Service Tool SD, System Manager SD, or Prism 2 computer software. During the setup and confi guring, the user is required to enter the last Zone address on the loop. Once confi gured, the MiniLink PD 5 begins polling each VAV/Zone Controller for its temperature and setpoint information. A zone poll cycles through all confi gured zones in one pass without interruption.

The following is a list of status information required by the MiniLink PD 5 to correctly perform its HVAC mode calculations.

Zone Temperature Current Cooling Setpoint Current Heating Setpoint Current Zone Operating Mode Status & Alarm Conditions

A zone is considered Missing if it fails to respond to 5 consecu-tive polling requests. A Missing Zone alarm can be generated in less than 2 minutes. This alarm can generate an alarm callout to maintenance or a supervisor if the system has been properly setup. See the “Alarm Detection And Reporting” section for more information.

Zone VotingIf a zone has been confi gured for the Voting mode, the Mini-Link will perform the following tests based on the data received during the zone polling operation. These tests ensure that only properly operating zones can have an effect on the HVAC Mode calculation.

The zone has not been reported as Missing

The zone is not currently undergoing Damper Calibration

The zone damper does not have an alarm condition

The zone temperature readings are between 40°F and 105ºF

The Zone Cooling Setpoint is between 55°F and 105ºF

The Zone Heating Setpoint is between 48°F and 99°F

The zone has not been declared Maverick by the MiniLink

The zone has been confi gured as a Voting zone

If all the above tests are passed, the zone temperature and set-points are then included in the HVAC mode decision; otherwise, this zone is ignored.

Testing for Maverick ZonesDuring the HVAC mode decision process, a zone cannot be in-cluded in the Voting if it has been declared as Maverick. A zone is determined to be a Maverick if it stays 4ºF below the Space Heating Setpoint for 1 hour or 4ºF above the Space Cooling Set-point for 1 hour. During this 1 hour time period, the zone is still included in the voting, but it generates a Priority call for Heating or Cooling to the MiniLink. During this 1 hour time period, if the Space Temperature moves to within 2ºF of its Space Heating or Space Cooling Setpoint, the Priority and Maverick are both canceled. If the zone stays in Priority for greater than 1 hour, it then becomes a Maverick zone. At that point, its Priority is canceled and the zone is ignored in the voting process until the Space Temperature changes to within 2ºF of its Space Heating or Space Cooling Setpoint. If at least 75% of the zones go Maverick simultaneously, the MiniLink assumes an abnormal condition has occurred in the building and resets all the zones back to normal. It then restarts the 1 hour Maverick test over again for all zones. Maverick testing can be disabled if your system is connected to a computer with Prism 2, the Modular System Manager SD, or the Modular Service Tool SD.

Page 36: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

36 VAV/Zone Controller Package

SEQUENCE OF OPERATIONSAlarms & Tenant Override Logs

Alarm Detection and ReportingThe VAV/Zone Controller continuously performs self diagnostics during normal operations to determine if any operating failures have occurred. These failures can be reported to the user in sev-eral ways, depending on the type of system and options installed by the user. If a System Manager TS-L is connected, the alarms will be reported on the Status Screens. If the Prism 2 computer software is installed, the alarms will be reported on the main screen of the program and be logged to disk. If the remote com-munications option is installed, all alarms can initiate an e-mail to alert someone to the alarm condition. See the Prism 2 Technical Guide for further information on this topic.

VAV/Zone Controller Alarms

Space Sensor Failure Alarm If the controller detects an open or short on the Space Sensor input, this alarm will be generated.

CFM Sensor Failure AlarmIf the Airfl ow Constant (K Factor) is set to any value other than zero, and the controller does not detect the Airfl ow Sensor, this alarm will be generated.

Damper Opening AlarmAfter initial calibration, if the damper is called to be fully open and cannot reach that position within approximately 2 minutes, this alarm will be generated.

Damper Closing AlarmAfter initial calibration, if the damper is called to be fully closed and cannot reach that position within approximately 2 minutes, this alarm will be generated.

High Space Temp AlarmIf the zone temperature is above the Cooling Setpoint by the High Zone Alarm Offset (user adjusted) for the Zone Alarm Delay Period (user adjusted), this alarm will be generated.

Low Space Temp AlarmIf the zone temperature is below the Heating Setpoint by the Low Zone Alarm Offset (user adjusted) for the Zone Alarm Delay Period (user adjusted), this alarm will be generated.

Damper Feedback Failure AlarmIf the controller fails to detect the actuator feedback signal, this alarm will be generated.

Tenant Override LogsIf you require tenant billing for push-button override usage, a MiniLink PD 5 must be installed on each local loop. The Mini-Link PD 5 has the ability to track the amount of override time gen-erated by each space sensor equipped with push-button override.

Storing and retrieving these logs requires a dedicated computer running the Prism 2 front-end software program. No other method exists for retrieving these logs. This means that all of your units must be connected together on the communications loop and the loop must be terminated at a CommLink device connected to the on-site computer.

WARNING: The computer must be on 24 hours a day 7 days a week running the Prism 2 software in order for tenant logging to be tracked.

The tenant logs are kept on the dedicated jobsite computer’s hard drive. The only limitation to the number of logs stored is the capacity of the hard drive on the computer to which it is being logged.

NOTE: For proper time and date stamping of the tenant log, you must confi gure the air handler to broadcast the time so that the VAV/Zone Controllers can read it and use it in their tenant and trend logs.

Page 37: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

37VAV/Zone Controller Package

SEQUENCE OF OPERATIONS

Internal Trend LoggingIn order to retrieve and utilize these logs, a computer with Prism 2 computer software installed must be connected to the Orion Controls System. The VAV/Zone Controller continuously main-tains an Internal Trend Log, which records a fi xed set of values at an interval confi gured by the user.

There are 120 log values available. Once all 120 log values have been recorded, the oldest value is replaced by each subsequent new value. This means the user is required to retrieve the logs at an interval that is shorter than the duration of the last 120 logs. Shown below are some log intervals and the duration of 120 logs.

1 minute interval ...................... 2 hour duration15 minute interval .................... 30 hour duration30 minute interval .................... 60 hour duration60 minute interval .................... 120 hour duration

The fi xed items in the log are listed below with the column header in parentheses:

Date (Date)

Time (Time)

Space Temperature (Space)

Active Cooling Setpoint (CoolSP)

Active Heating Setpoint (HeatSP)

Supply Air Temperature (SAT)

Discharge Air Temperature (DAT)

Airfl ow (Airfl ow) [P.I. Units Only]

Damper Position (Damper)

Proportional Heat (Heat)

Current Operating Mode (Mode)

Space Temperature Mode (SPCMode)

SAT Mode (SATMode)

Fan Status (Box)

Box Heat Stages (BoxHt)

Auxiliary Heat Stages (AuxHt)

NOTE: For proper time and date stamping of the tenant log, you must confi gure the Unit Controller to broadcast the time so that the VAV/Zone Controllers can read it and use it in their tenant and trend logs.

CAUTION: These logs are subject to loss if a power outage occurs.

Internal Trend Logs & Force Modes or Overrides

Force Modes or OverridesThe VAV/Zone Controller damper can be forced to one of several positions. These force modes aid the user during troubleshooting or air balancing, etc.

Force Damper Full Open (ignores Airfl ow reading) Force Damper Full Closed (ignores Airfl ow reading) Force to Maximum Airfl ow/Damper Setpoint Force to Minimum Airfl ow/Damper Setpoint Force to Fixed Airfl ow/Damper Setpoint Force Damper to Re-Calibrate

The Force to Fixed Airfl ow/Damper Mode also has a setpoint associated with it. This allows the user to provide a non-changing fi xed amount of air into the space that doesn’t affect the mini-mum or maximum setpoints. This means the user doesn’t have to disturb the real minimum and maximum setpoints to achieve a nonstandard setting during their troubleshooting or air balanc-ing modes.

The Force to Minimum Mode uses the currently active minimum setting based on the Vent, Cooling, or Heating Modes. Whatever mode the VAV/Zone Controller is in determines the minimum used by the force mode.

The damper force modes will remain in effect until cancelled by the user or until the power is removed. Unlike the Unit Control-lers which require the initiating device to be present at all times during a force mode, the damper force modes are more permanent since they are less likely to damage any equipment. There are no force commands available for the auxiliary relays.

Page 38: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

LED Troubleshooting

Using LEDs To Verify Operation

The VAV/Zone Controller is equipped with LEDs that can be used to verify operation and perform troubleshooting. See Figure 18. for the LED locations. The LEDs and their uses are as follows:

Operation LEDs - Factory Troubleshooting

COMM - This orange LED will light up and blink continuously to indicate communications are working properly.

POWER - This green LED will light up to indicate that 24 VAC power has been applied to the controller.

APP HB - This green LED will light up and blink continuously to indicate the application software is working properly.

WDOG - This green LED will light up and stay lit to indicate the operating system is working properly.

OS HB - This green LED will light up and blink continuously to indicate the operating system is working properly. Diagnostic LEDs

STAT 1 - This red LED is a diagnostic blink code LED. It blinks continuously while in TEST MODE at address 63. Under normal operation, it should not be blinking.

STAT 2 - This red LED is a diagnostic blink code LED. It blinks continuously while in TEST MODE at address 63. The status code is repeatedly blinked every 10 seconds to indicate control-ler status. See Table 4, below for STAT 2 LED Blink Codes. The Blink Codes are listed in order of priority with 7 being the highest priority.

Only the highest priority failure code will blink. You must correct the highest priority alarm before other problems will be indicated.

LED Blinks ThisNumber of Times

Blink Code Description

1 Normal Operation.No Alarm Conditions Exist

2 Push-button Override orGroup Override Is Active

3 Communications Failure4 Bad Airfl ow Sensor5 Bad Or Missing Space Sensor6 Damper Open or Close Failure7 Damper Feedback Failure

Table 4: STATUS 2 LED Blink Codes

If the STAT 2 LED does not operate as indicated, fi rst check the address switch setting. See Figure 16, page 25 for correct address switch setting procedures. If the address switch setting is correct and the STAT 2 LED still does not behave as indicated above, contact WattMaster Controls Technical support.

AUX HEAT RELAY LED - This yellow LED will blink to signal the Aux Heat Relay is enabled.

CCW LED & CW LED - These yellow LEDs blink or are on steady depending on the direction the damper is currently being driven.

1002

1002

1002

1002

1002

1002

1002

1002

3650

.001uF

OF

F

3650

3650

3650

3650

3650

POWER

APP HB

WDOG

OS HB

STAT 2

STAT 1

COMM

ADDRESS

1

2

4

8

16

32

ON

LO

OP

BA

UD

1

2

E-BUS

V2

P1

R5

SW1

R5

R5

R4

R4

R4

R4

R4

D7

C29

3650

VAV/Zone Controller

STAT 1 LED

STAT 2 LEDOS HB LEDWDOG LEDAPP HB LED

POWER LED

COMM LED

D1

R40

D2

1002

1002

4751

4751

10uF

VAC~VDC

VDE

ACTUATOR

HEATAUX

CW

CCW

SERIAL #

V4

V3

TB5 R24

R21

P3

C25

R42

D1

3

AUX HEATLED

CW LED

CCW LED

Figure 18: VAV/Zone Controller LED Locations

38 VAV/Zone Controller Package

TROUBLESHOOTING

Page 39: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Other Checks

Analog Space Temperature SensorIf the Space Temperature Sensor is not reading a valid tempera-ture, make sure the wiring terminal connections are tight and that any wiring splices are properly connected. You can check the operation of the Space Temperature Sensor by measuring the resistance or voltage using a digital multimeter. Set the meter to DC Volts. Place the positive probe on the AIN terminal and the negative probe on the GND terminal. Read the DC Volts and fi nd that voltage in Table 5, page 42. Read the temperature corresponding with that voltage and determine if this is close to the actual temperature the sensor is exposed to. If the tempera-ture from the chart is different by more than a few degrees, you probably have a defective or damaged sensor. You can also check the sensor resistance to determine correct operation. To read the resistance, set the meter to Ohms. Unplug the sensor connector from the board and measure the resistance across the discon-nected wires. This resistance should match the corresponding temperature from Table 5, page 42.

E-BUS Digital Room Temperature SensorIf the E-BUS Digital Room Temperature Sensor is not displaying a valid temperature, fi rst make sure that the E-BUS modular cable connector is fi rmly plugged into the E-BUS modular connector on the board and at the Temperature Sensor. If the problem persists, try swapping the sensor with a known good Room Temperature Sensor. If that sensor works when connected to the VAV/Zone Controller, you can assume you have a defective or damaged sen-sor. If you are using a terminal connector to connect the sensor, follow the instructions for the Analog Space Temperature Sensor .

Supply Air Temperature SensorIf you suspect the Supply Air Temperature Sensor is not reading correctly, make sure the wiring terminal connections are tight and that any wiring splices are properly connected. You can check the operation of the Supply Air Temperature Sensor by measuring the resistance or voltage using a digital multimeter. Set the meter to DC Volts. Place the positive probe on the AIN terminal and the negative probe on the GND terminal. Read the DC Volts and fi nd that voltage in Table 5, page 42. Read the temperature corresponding with that voltage and determine if this is close to the actual temperature the sensor is exposed to. If the temperature from the chart is different by more than a few degrees, you probably have a defective or damaged sensor. You can also check the sensor resistance to determine correct opera-tion. To read the resistance, set the meter to Ohms. Unplug the sensor connector from the board and measure the resistance across the disconnected wires. This resistance should match the corresponding temperature from Table 5, page 42.

Airflow SensorIf the Airfl ow Sensor seems to be reading incorrectly, check the Airfl ow Sensor tubing connections at the airfl ow pickup tubes. The high pressure port of the sensor needs to be connected to the upstream pickup tube. The low pressure port of the sensor needs to be connected to the downstream pickup tube.

The “Air Valve Sizing Constant” setting under the confi guration settings for the VAV/Zone Controller must be set to a number other than 0. This number is normally referred to as the “K” factor and is supplied by the terminal unit manufacturer. It represents the airfl ow through the box inlet at 1” W.G. constant static pres-sure. This factor must be entered in the confi guration screen or the airfl ow through the box will be incorrect.

If none of the procedures above solves the problem, remove power from the VAV/Zone Controller. Shut down the HVAC unit supplying the duct that the VAV/Zone damper is located on. Be sure that no airfl ow is present in the duct. Reapply power to the board and wait for the VAV/Zone Controller to run through its calibration sequence. Restart the HVAC unit and check the VAV/Zone Controller CFM readings. If the CFM reading still seems to be in error, you probably have a defective Airfl ow Sensor and will need to replace it.

Diagnostics

39VAV/Zone Controller Package

TROUBLESHOOTING

Page 40: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Zone Damper Actuator

Check the Modular cable between the controller and the actuator. Be sure both ends of the cable are fi rmly connected to the mating connectors on the actuator and the VAV/Zone Controller. Be sure the damper moves freely and is not bound. Do this by pressing the actuator clutch button and rotating the damper shaft in both directions to verify smooth operation. If binding is present, fi x the problem as required. Remove power from the VAV/Zone Controller. Reapply power and observe the damper rotation. If the actuator does not drive the damper in both directions, the actuator is probably defective or damaged. Another test that can be performed is to swap cables with another known operating actuator to determine if the cable could be bad. If the problem goes away, you have a defective cable that must be replaced. You can also try swapping a functioning actuator with the suspected defective actuator. If this solves the problem, the defective actua-tor will need to be replaced.

Diagnostics

VAV/Zone Controller Expansion Module

If the VAV/Zone Controller Expansion Module does not seem to operate correctly, fi rst make sure the E-BUS cable between the Expansion Module and the VAV/Zone Controller is fi rmly con-nected at both ends. Be sure that the Expansion Module has been confi gured correctly. The Expansion Module must be confi gured using the Modular Service Tool SD, Modular System Manager SD, or Prism 2 computer software for your application before it will operate. You must confi gure the number of heat stages, and if it is a fan terminal you must confi gure whether it is a Series Flow or Parallel Flow Fan Terminal unit. On a single duct non-fan terminal unit when a call for heat is initiated, the LED labeled RLY2 should light up. If the Expansion Module is confi gured as a fan terminal, on a call for the fan, the LED labeled RLY1 should light up. If the LEDs do not light up, the Expansion Module is probably defective and must be replaced.

40 VAV/Zone Controller Package

TROUBLESHOOTING

Page 41: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Temperature Sensor Testing

Temperature Sensor Testing

The following sensor voltage and resistance table is provided to aid in checking sensors that appear to be operating incorrectly. Many system operating problems can be traced to incorrect sen-sor wiring. Be sure all sensors are wired per the wiring diagrams in this manual.

If the sensors still do not appear to be operating or reading cor-rectly, check voltage and/or resistance to confi rm that the sensor is operating correctly per the table. Please follow the notes and instructions in Figure 19, below when checking sensors.

Figure 19: Testing Resistance On E-BUS Digital Room Sensors

MA

DE

IN U

SA

YS

102370 R

1

ModB

us L

CD

Space S

ensor

WattM

aste

r Contro

ls, In

c

PR

OG

RA

M

COMM

LED1

EX

TE

RN

TH

ER

M

+12V

dc

GN

D

-CO

M

+C

OM

M

SH

LD

P1

R1

F3

U4

C18

R36C30

D1

L1

C17

R38

R37C19

C31

C21

TB

1

X2

J3

C3

C24

C23

C1

C8

C12

C13 C14

C16

C25

C26

J2

Q2

R3R4

R6

R8

R9

R10

R11

R12

R14

R13

R15

TH1

U3

X1

C27

R18

C20

D4

R17

D6

D7

R32

R33

D5

1

J1

DIS

P1

C15

D2

R2

R5

R7

R16

R19

R20

U6

U2

TB

2

R35

2.2uF

R18

10

02

10

01

13

30

47

51

47

51

1001

1001

.1u

F

9.21Mhz

47

51

47

51

LTC3502

.1u

F

15pF6.8uF

.1uF

10

uF

31621502

6.8

uH

10

02

24F

C1025

6.8

uF

6.8

uF

10

01

47

51

.1u

F

.1uF

1000 1002

47

51

.1u

F

47

51

AD

M3

483

.1uF

.1uF

RS

1G

X05

MICROCHIP

PIC32MX440F

512H-80IPT

.1uF

10

RO

10

RO

47

0p

F

X05

++

-

-T

E-BUS Digital Room SensorBack View

Note: ,For This Test The Sensor Must BeDisconnected From Its E-BUS Cable AsShown Or Disconnected From the VAV/ZoneController If Wired To The Board. The MeterMust Be Set To Measure Resistance inOhms. Use The Table On The Facing PageTo Determine If The Sensor Is Reading TheCorrect Resistance Value For The AmbientTemperature. This Resistance Value ShouldMatch The Temperature Value Listed Next ToThe Resistance Value In The Table. TheTemperature Should Be Measured With ASeparate Accurate Temperature MeasuringDevice Located In The Area Where TheSensor Is Currently Located.

Test Points Labeled“Extern Therm” OnSensor Circuit Board

E-BUS CableDisconnectedFrom Sensor Port

9302

41VAV/Zone Controller Package

TROUBLESHOOTING

Page 42: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Table 5: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors

Temperature/Resistance/Voltage Table

Temperature – Resistance – Voltage forType III 10 K Ohm Thermistor SensorsTemp(ºF)

Resistance(Ohms)

Voltage @ Input (VDC)

-10 93333 4.620-5 80531 4.5500 69822 4.4745 60552 4.390

10 52500 4.29715 45902 4.20020 40147 4.09525 35165 3.98230 30805 3.86235 27140 3.73740 23874 3.60545 21094 3.47050 18655 3.33052 17799 3.27554 16956 3.21756 16164 3.16058 15385 3.10060 14681 3.04262 14014 2.98564 13382 2.92766 12758 2.86768 12191 2.81069 11906 2.78070 11652 2.752

Temperature – Resistance – Voltage forType III 10 K Ohm Thermistor SensorsTemp(ºF)

Resistance(Ohms)

Voltage @ Input (VDC)

71 11379 2.72272 11136 2.69573 10878 2.66574 10625 2.63575 10398 2.60776 10158 2.57778 9711 2.52080 9302 2.46582 8893 2.40784 8514 2.35286 8153 2.29788 7805 2.24290 7472 2.18795 6716 2.055

100 6047 1.927105 5453 1.805110 4923 1.687115 4449 1.575120 4030 1.469125 3656 1.369130 3317 1.274135 3015 1.185140 2743 1.101145 2502 1.024150 2288 0.952

42 VAV/Zone Controller Package

TROUBLESHOOTING

Page 43: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Single Loop VAV/Zoning

If you have a single HVAC unit that will be using VAV terminal units or are using a zoning system and don’t have any CV units you should select the Single Loop Zoning System. On a Variable Volume Variable Temperature Zoning System up to 16 VAV/Zone Controllers can be confi gured as voting zones, and additional zone controllers can be non-voting zones. For VAV systems you can have up to 58 total VAV/Zone Controllers in addition to the HVAC unit controller for the VAV boxes.

The Unit Controller(s) are connected to a MiniLink communi-cations interface which provides communications between all controllers on the local communications loop and the System Manager TS-L end-user interface, Modular System Manager SD operator interface, Prism 2 operator interface, or CommLink communication interface. The MiniLink provides for alarm poll-ing of all VAV/Zone Controllers.

Each of the controllers are connected together and to the MiniLink by means of local loop communications cable. All communication wiring must be plenum-rated, minimum 18 gauge, 2-conductor, twisted pair with shield cable. WattMaster can supply commu-nication wire that meets this specifi cation and is color coded for the network or local loop or if desired, Belden #82760 or its equivalent wire may also be used.

The System Manager TS-L is an operator interface that can be used for monitoring of the system. It has a color touch screen display and intuitive graphical user interface.

In addition or as an alternative a CommLink communication interface can be provided that allows for connection to any computer which has the free Prism 2 software installed to pro-vide for confi guring and monitoring of the system. Prism 2 is a Windows®-based color graphical computer front end software package designed by WattMaster. An optional IP Module is also available to provide Internet connectivity to the control system.

Multiple Loop VAV/Zoning

If you have a multiple HVAC units that will be using VAV Ter-minal Units or will be using a Zoning System and don’t have any CV units you should select the Multiple Loop Zoning System. On a Zoning System each local loop allows up to 16 VAV/Zone Controllers can be confi gured as voting zones, and additional controllers to be non-voting zones. For VAV systems you can have up to 58 total VAV/Zone Controllers in addition to the HVAC unit controller for the VAV boxes.

Each local loop is connected to its own MiniLink communications interface which provides communications between all control-lers on the local communications loop and the System Manager TS-L end-user interface, Modular System Manager SD operator interface, Prism 2 operator interface, and/or the CommLink com-munication interface. The MiniLink provides for alarm polling of all the zone controllers.

On this type of system the CommLink communications interface is required and acts as the main hub for all the local loops on the system and passes communications between and across all the local loops . The wiring between the CommLink and all the MiniLink devices is called the network loop

Each of the controllers on the local loops are connected together and to that loops MiniLink by means of local loop communica-tions cable. Each of the MiniLink devices are connected together and to the CommLink on the network loop using network com-munications cable. All communication wiring must be plenum-rated, minimum 18 gauge, 2 conductor, twisted pair with shield cable. WattMaster can supply communication wire that meets this specifi cation and is color coded for the network loop or local loop, or if desired, Belden #82760 or its equivalent wire may also be used.

The System Manager TS-L is an operator interface that can be used for monitoring of the entire control system. It has a color touch screen display and intuitive graphical user interface. It can be located on any local loop on the system. Multiple System Manager TS-L operator interfaces can also be used if desired.

The CommLink communication interface is standard on this type of system and allows for connection to any personal com-puter which has the free Prism 2 software installed to provide for confi guring and monitoring of the system. Prism 2 is a Windows®-based color graphical computer front end software package designed by WattMaster. An optional IP Module is also available to provide Internet connectivity to the control system.

APPENDIX

43VAV/Zone Controller Package

VAV/Zone Controller System Architecture

Page 44: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

No

te:

Mu

ltip

le V

AV

/Zo

ne

Co

ntr

olle

rs C

an

Be

Co

nn

ecte

dTo

AS

ing

leT

ran

sfo

rme

r If

De

sire

d.

Ho

we

ve

r P

ola

rity

Mu

st

Be

Ob

se

rve

d O

rD

am

ag

eTo

Th

e C

on

tro

ller(

s)

Will

Re

su

lt.

Se

eT

he

Tra

nsfo

rme

r S

izin

g P

ag

e I

nT

his

Ma

nu

al

Fo

rT

ran

sfo

rme

r S

izin

gA

nd

Circu

it D

esig

nIn

form

atio

n.

Co

nn

ectTo

Ne

xt

VA

V/Z

on

e C

on

tro

ller

On

Lo

ca

l L

oo

p

SH

LD

T R

Ty

pic

al

Te

rmin

al

Blo

ck

s.A

llW

irin

g T

o B

e T

To

T,

SH

LD

(G

)To

SH

LD

(G

) &

R T

o R

TG

R

485 LOOP

FIL

EN

AM

E

DE

SC

RIP

TIO

N:

PA

GE

Wirin

g &

Co

nn

ectio

n D

iag

ram

s

JO

B N

AM

E

1 o

f 1

Typ

ical S

ing

le L

oo

p N

etw

ork

ed

Syste

mW

ith

Min

iLin

k P

ollin

g D

evic

e &

VA

V/Z

on

e C

on

tro

llers

Lin

eV

olt

ag

e

Lin

eV

olt

ag

e

Lin

eV

olt

ag

e

VC

CX

2U

nit

Co

ntr

olle

r

24

VA

C(6

VA

)

24

VA

C(6

VA

)

24

VA

C(6

VA

)

VC

CX

2-N

etw

ork

-Sin

gle

-1A

.CD

R

VC

CX

2 N

etw

ork

ed S

yste

m -

Sin

gle

Loop

Lin

eV

olt

ag

e

24

VA

C(6

VA

)

No

te:

Eith

er

AM

od

ula

r S

yste

m M

an

ag

er

SD

,M

od

ula

r S

erv

ice

To

ol S

D,

Or

Co

mp

ute

r W

ith

Prism

2 S

oft

wa

re I

nsta

lled

Ca

n B

e U

se

dTo

Pro

gra

mA

nd

Co

nfig

ure

Th

e O

rio

n S

yste

m.

VA

V/Z

on

eC

on

tro

lle

r(N

on

-Mo

du

lar)

VA

V/Z

on

eC

on

tro

lle

r(N

on

-Mo

du

lar)

VA

V/Z

on

eC

on

tro

lle

r(N

on

-Mo

du

lar)

VA

V/Z

on

eC

on

tro

lle

r(N

on

-Mo

du

lar)

BY

:S

onya O

lson

DA

TE

:

Mo

du

lar

Se

rvic

eTo

ol S

D

10/3

0/1

7

Lo

ca

l

Lo

ca

l

24

VA

C(6

VA

)

Min

iLin

k P

D 5

PD DRV

LOOP DRV

NE

TD

RV

PIC

32 M

LP

DY

S102398 R

EV

3

NE

TW

OR

K

LO

CA

L

PD

CO

MM

PO

WE

R

1 2 4 8 16

32

CO

MM

AD

DR

ES

S

ML

PD

MA

DE

IN

US

A

SERIAL #

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4

R2

0

R2

1

R22R23

R2

4

R25R2

6

R27

R31

PD

STA

T1

PD

STA

T2

SW

2

TB

1

TB

2

U8

U10

U12

D4

J6

J7 J8

R4

3

R44

R4

6

C33

OFF

T SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.1uF

.1uF

.1uF

1002 1002

T

SHR

C24

CO

MM

ww

w.o

rio

nco

ntr

ols

.co

m

Wa

ttM

aste

r L

ab

el

#L

B1

02

09

1-0

0R

ev.

01

B

OE

36

4-2

3-O

RM

INIL

INK

PD

5

TT

T

LO

CA

LN

ET

WO

RK

SH

24 VAC

GND

SH

R

R

LOCALLOOPWIRE TERMINALS

NETWORK LOOPWIRE TERMINALS NETWORK LOOP

COMM CONNECTORS

ADDRESS DIPSWITCH

PO

WE

RT

ER

MIN

AL

S

LOCALLOOPCOMM

CONNECTOR

24

VA

C P

OW

ER

ON

LY

WA

RN

ING

!P

OL

AR

ITY

MU

ST

BE

OB

SE

RV

ED

OR

TH

E

BO

AR

D W

ILL

BE

DA

MA

GE

D

Lin

e V

olt

ag

e

24 V

AC

(15 V

A)

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

Mo

du

lar

Sy

ste

m M

an

ag

er

SD

Sy

ste

m M

an

ag

er

TS

-L

No

te:

The S

MT

S-L

IsA

nE

nd-U

ser

Inte

rface O

nly

.It C

annot B

e U

sed

To

Configure

The C

ontr

olle

rs.

Lin

eV

olt

ag

e

Sy

ste

m M

an

ag

er

TS

-L(B

ac

k V

iew

)

24

VA

C(6

VA

)

RS

T+

BLACK (R)

Co

nn

ec

t To

T,

SH

, R

Te

rmin

als

On

HV

AC

Un

itC

on

tro

lle

r

RED (24 VAC)

BROWN (GND)

WHITE (T)

BARE (S)

.1uF

YS

10

21

78

R4

WQ

VG

AG

rap

hic

al In

terf

ace

Wa

ttM

aste

r C

on

tro

ls,

Inc

C2

4

R9R7

R6

R5

R2

R1

C5

1

C3

9

C2

0

C1

9

C15

C1

4

C13

C12C11

C10

C9

C7

C1

X3

8.0

0M

hz

OF

F

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

10021002

10021002

1002

1002

10021002

1002

1002

10021002

1002

1002

1002

1002 10021002

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

1002

.1uF

1002

1002

.1uF

.1uF

.1uF

.1uF

LTC

3824

1002

1002

1002

1002

1002

1002

66

.00

0M

hz

MA

DE

IN

US

A

33

0u

F 5

0V

33

0u

F

1002

SE

RIA

L#

OPT4

OPT3

OPT2

OPT1

TE

RM

RT

C

YS

10

21

78

R4

WQ

VG

AG

rap

hic

al In

terf

ace

Wa

ttM

aste

r C

on

tro

ls,

Inc

CA

L

5V

3.3

V2

.5V

J3

R34R16

R13 R8

R3

9

X2

R2

6R

17

R1

4

C2

4

U1

3

R49

R48

R47R4

6

R4

5

R44

R4

3R

40

R3

7

R3

5

R32 R31

R2

9

R2

7

R2

4

R2

2

R12

R11

R10

R9R7

R6

R5

R2

R1

L5

L4

D1

2

D11

D1

C5

1C

50

C4

5

C41

C3

9

C36

C2

0

C1

9

C1

8

C17

C1

6

C15

C1

4

C13

C12C11

C10

C9

C8

C7

C6

C5

C4

C1

J1

R41

C2

3

C25

C26

R4

2

X3

R2

0

C27

C3

4C

40

U10

U11

C28

C2

9

R18

C35

D2

L1

R25C31R19

U9

R28C32R30

R33

C30

R1

5Q

2

R2

1

R2

3

SW

1

C2 C3

V1

R3

6

1002

RS

T+

1002

R T

5V

GN

D

TE

RM

Fo

r S

tan

dA

lon

eA

pp

lica

tio

ns

Bo

th J

um

pe

rs M

ust

Be

ON

4GB

Mo

du

lar

Sy

ste

m M

an

ag

er

SD

(Ba

ck

Vie

w)

M

EN

TE

R

UP

DO

WN

AL

AR

M

ME

NU

RE

LA

YC

ON

TA

CT

RA

TIN

G IS

1A

MP

MA

X @

24 V

AC

RS

-485 C

OM

MLO

OP. W

IRE

“R”

TO

“R”,

“T”

TO

“T”

“SH

LD

”T

O“S

HLD

24

VA

C P

OW

ER

ON

LY

WA

RN

ING

!

PO

LA

RIT

Y

MU

ST

BE

OB

SE

RV

ED

OR

TH

E

CO

NT

RO

LL

ER

WIL

LB

E

DA

MA

GE

D

ww

w.a

aon.c

om

ww

w.o

rio

nco

ntr

ols

.co

m

VC

CX

2 C

ON

TR

OL

LE

RO

rio

n N

o.:

OE

33

8-2

6B

-VC

CX

2A

AO

N N

o.:

V8

79

00

BIN

AR

YIN

PU

TS

BI1

= P

RO

OF

OF

AIR

FLO

WB

I2

BI3

BI5

BI6

AI1

AI2

AI3

AI4

AI5

A6

= D

IRT

YF

ILT

ER

= H

OO

D O

N/O

FF

= R

EM

OT

E O

CC

UP

IED

= R

EM

OT

E C

OO

LIN

G=

RE

MO

TE

HE

AT

ING

= R

EM

OT

E D

EH

UM

IDIF

ICA

TIO

N=

EM

ER

GE

NC

YS

HU

TD

OW

N

= S

PA

CE

TE

MP

ER

AT

UR

E=

SP

AC

E S

LID

E O

FF

SE

T=

SU

PP

LY

AIR

TE

MP

ER

AT

UR

E=

RE

TU

RN

AIR

TE

MP

ER

AT

UR

E=

BU

ILD

ING

PR

ES

SU

RE

= S

UP

PLY

AIR

TE

MP

RE

SE

T=

OU

TD

OO

RA

IRT

EM

PE

RA

TU

RE

= N

OT

CO

NN

EC

TE

D U

SE

DU

CT

STA

TIC

CO

NN

EC

TO

R

BI4

BI7

BI8 I

AI7

AI8

AN

AL

OG

IN

PU

TS

WattM

aste

rO

verlay

#S

000079

Rev.

: 1A

W

DU

AL

E-B

US

+24VAC

GND

MA

IN F

AN

RE

LA

Y2

RE

LA

Y3

RE

LA

Y4

RE

LA

Y5

RE

LA

Y6

RE

LA

Y7

RE

LA

Y8

RE

LA

YC

OM

MO

N

MA

IN S

UP

PLY

FA

N V

FD

=E

CO

NO

MIZ

ER

AC

TU

AT

OR

=M

OD

ULA

TIN

G H

EA

TIN

G =

EX

HA

US

TF

AN

VF

D =

AO

1

AO

2

AO

3

AO

4

BA

CN

ET

BA

CN

ET

SH

IELD

BA

CN

ET

+

=T

=S

H

=R

DU

CT

STA

TIC

Figure 20: Networked Single Loop System With MiniLink PD VAV/Zone Controllers Wiring

APPENDIX

44 VAV/Zone Controller Package

VAV/Zone Controller System Architecture

Page 45: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Netw

ork

110 V

AC

To

24 V

AC

Po

wer

Pack

FIL

EN

AM

E

DE

SC

RIP

TIO

N:

PA

GE

Wirin

g &

Connection D

iagra

ms

JO

B N

AM

E

1 o

f 1

Ty

pic

al

Sin

gle

Lo

op

Ne

two

rke

d S

ys

tem

Wit

hM

iniL

ink

Po

llin

g D

ev

ice

, C

om

mL

ink

& V

AV

/Zo

ne

Co

ntr

oll

ers

Net-

CL5-M

LP

D5-S

ingle

-1A

.CD

R

VC

CX

2 N

etw

ork

ed

Syste

m -

Sin

gle

Lo

op

No

te:

Com

mLin

k M

ust B

e S

et

For

Multip

le L

oop O

pera

tion

When U

sed W

ith

AM

iniL

ink

Wheth

er

It Is

AS

ingle

Loop

Syste

m O

r N

ot. If it D

oesn’t

Have

AM

iniL

ink, S

et

Com

mLin

kTo S

ingle

Loop.

SH

LD

T R

Typ

ical Term

inal B

locks.A

llW

irin

g T

o B

e T

To

T, S

HL

D (

G)

To

SH

LD

(G

) &

R T

o R

TG

R

485 LOOP

VC

CX

2U

nit

Co

ntr

oller

VA

V/Z

on

eC

on

tro

ller

(No

n-M

od

ula

r)

VA

V/Z

on

eC

on

tro

ller

(No

n-M

od

ula

r)

VA

V/Z

on

eC

on

tro

ller

(No

n-M

od

ula

r)

Lin

eV

olt

ag

eL

ine

Vo

ltag

e

Lin

eV

olt

ag

e

24 V

AC

(6 V

A)

24 V

AC

(6 V

A)

24 V

AC

(6 V

A)

ConnectTo N

ext

VA

V/Z

one C

ontr

olle

rO

n L

ocal Loop

No

te:

Multip

le V

AV

/Zone C

ontr

olle

rs C

an B

e C

onnecte

dTo

AS

ingle

Tra

nsfo

rmer

If D

esired. H

ow

ever,

Pola

rity

Must B

e O

bserv

ed O

r D

am

age

To

The C

ontr

olle

r(s)

Will

Result. S

ee

The

Tra

nsfo

rmer

Siz

ing P

age In

This

Manual

For

Tra

nsfo

rmer

Siz

ing

And C

ircuit D

esig

n Info

rmation.

BY

:S

on

ya

Ols

on

DA

TE

:1

0/3

0/1

7

Back V

iew

Fro

nt

Vie

w

Co

mm

Lin

k 5

Seri

al #

CO

MP

UT

ER

US

B

10

/10

0E

TH

ER

NE

T

DIA

G

48

5 L

OO

PP

OW

ER

AC

TL

NK

HIGH

LOW

BA

UD

R(+)

24V

GND

SHLD

T(-)

MULTIPLE

SINGLE

LO

OP

No

te:

EitherA

Modula

r S

yste

m M

anager

SD

,M

odula

r S

erv

ice

Tool S

D O

r C

om

pute

r W

ith

Prism

2 S

oftw

are

Insta

lled C

an B

e U

sed

To

Pro

gra

mA

nd C

onfigure

The O

rion S

yste

m.

Mo

du

lar

Serv

ice

To

ol S

D

Lo

ca

l

Lo

ca

l

24

VA

C(6

VA

)

Min

iLin

k P

D 5

Lo

op

1

PD DRV

LOOP DRV

NE

TD

RV

PIC

32 M

LP

DY

S102398 R

EV

3

NE

TW

OR

K

LO

CA

L

PD

CO

MM

PO

WE

R

1 2 4 8 16

32

CO

MM

AD

DR

ES

S

ML

PD

MA

DE

IN

US

A

SERIAL #

C2

2

C2

3

C3

0

C3

7

C4

0

J1

J3

R1

R2

R3

R4

R2

0

R2

1

R22R2

3R

24

R25R2

6

R2

7

R3

1

PD

STA

T1

PD

STA

T2

SW

2

TB

1

TB

2

U8

U1

0

U12

D4

J6

J7 J8

R4

3

R4

4

R4

6

C33

OFF

T SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.1uF

.1uF

.1uF

1002 1002

T

SHR

C2

4

CO

MM

ww

w.o

rio

nc

on

tro

ls.c

om

Wa

ttM

aste

r L

ab

el

#L

B1

02

09

1-0

0R

ev.

01

B

OE

364-2

3-O

RM

INIL

INK

PD

5

TT

T

LO

CA

LN

ET

WO

RK

SH

24 VAC

GND

SH

R

R

LOCALLOOPWIRE TERMINALS

NETWORK LOOPWIRE TERMINALS NETWORK LOOP

COMM CONNECTORS

ADDRESS DIPSWITCH

PO

WE

RT

ER

MIN

AL

S

LOCALLOOPCOMM

CONNECTOR

24

VA

C P

OW

ER

ON

LY

WA

RN

ING

!P

OL

AR

ITY

MU

ST

BE

OB

SE

RV

ED

OR

TH

E

BO

AR

D W

ILL

BE

DA

MA

GE

D

Lin

e V

olt

ag

e

24

VA

C(1

5 V

A)

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

Mo

du

lar

Syste

m M

an

ag

er

SD

Syste

m M

an

ag

er

TS

-L

No

te:

Th

e S

MT

S-L

IsA

nE

nd

-Use

r In

terf

ace

On

ly.

It C

an

no

t B

e U

se

dTo

Co

nfig

ure

Th

e C

on

tro

llers

.

Lin

eV

olt

ag

e

Syste

m M

an

ag

er

TS

-L(B

ack V

iew

)

24 V

AC

(6 V

A)

RS

T+

BLACK (R)

Co

nn

ect

To

T, S

H, R

Term

inals

On

HV

AC

Un

itC

on

tro

ller

RED (24 VAC)

BROWN (GND)

WHITE (T)

BARE (S)

.1uF

YS

102178 R

4

WQ

VG

AG

raphic

al In

terf

ace

WattM

aste

r C

ontr

ols

, In

c

C24

R9R7

R6

R5

R2

R1

C51

C39

C20

C19

C15

C14

C13

C12C11

C10

C9

C7

C1

X3

8.0

0M

hz

OF

F

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

10021002

10021002

1002

1002

10021002

1002

1002

10021002

1002

1002

1002

1002 10021002

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

1002

.1uF

1002

1002

.1uF

.1uF

.1uF

.1uF

LTC

3824

1002

1002

1002

1002

1002

1002

66.0

00M

hz

MA

DE

IN

US

A

330uF

50V

330uF

1002

SE

RIA

L#

OPT4

OPT3

OPT2

OPT1

TE

RM

RT

C

YS

102178 R

4

WQ

VG

AG

raphic

al In

terf

ace

WattM

aste

r C

ontr

ols

, In

c

CA

L

5V

3.3

V2.5

V

J3

R34R16

R13 R8

R39

X2

R26

R17

R14

C24

U13

R49

R48

R47R46

R45

R44

R43

R40

R37

R35

R32 R31

R29

R27

R24

R22

R12

R11

R10

R9R7

R6

R5

R2

R1

L5

L4

D12

D11

D1

C51

C50

C45

C41

C39

C36

C20

C19

C18

C17

C16

C15

C14

C13

C12C11

C10

C9

C8

C7

C6

C5

C4

C1

J1

R41

C23

C25

C26

R42

X3

R20

C27

C34

C40

U10

U11

C28

C29

R18

C35

D2

L1

R25C31R19

U9

R28C32R30

R33

C30

R15

Q2

R21

R23

SW

1

C2 C3

V1

R36

1002

RS

T+

1002

R T

5V

GN

D

TE

RM

For

Sta

nd

Alo

ne

Applic

ations

Both

Jum

pers

Must B

e O

N

4GB

Mo

du

lar

Syste

m M

an

ag

er

SD

(Back V

iew

)

M

EN

TE

R

UP

DO

WN

AL

AR

M

ME

NU

RE

LA

YC

ON

TA

CT

RA

TIN

G I

S 1

AM

PM

AX

@ 2

4 V

AC

RS

-48

5 C

OM

ML

OO

P.

WIR

E“R

”T

O“R

”,“T

”T

O“T

”“S

HLD

”T

O“S

HLD

24

VA

C P

OW

ER

ON

LY

WA

RN

ING

!

PO

LA

RIT

Y

MU

ST

BE

OB

SE

RV

ED

OR

TH

E

CO

NT

RO

LL

ER

WIL

LB

E

DA

MA

GE

D

ww

w.a

aon.c

om

ww

w.o

rio

nco

ntr

ols

.co

m

VC

CX

2 C

ON

TR

OL

LE

RO

rio

n N

o.:

OE

33

8-2

6B

-VC

CX

2A

AO

N N

o.:

V8

79

00

BIN

AR

YIN

PU

TS

BI1

= P

RO

OF

OF

AIR

FL

OW

BI2

BI3

BI5

BI6

AI1

AI2

AI3

AI4

AI5

A6

= D

IRT

YF

ILT

ER

= H

OO

D O

N/O

FF

= R

EM

OT

E O

CC

UP

IED

= R

EM

OT

E C

OO

LIN

G=

RE

MO

TE

HE

AT

ING

= R

EM

OT

E D

EH

UM

IDIF

ICA

TIO

N=

EM

ER

GE

NC

YS

HU

TD

OW

N

= S

PA

CE

TE

MP

ER

AT

UR

E=

SP

AC

E S

LID

E O

FF

SE

T=

SU

PP

LY

AIR

TE

MP

ER

AT

UR

E=

RE

TU

RN

AIR

TE

MP

ER

AT

UR

E=

BU

ILD

ING

PR

ES

SU

RE

= S

UP

PLY

AIR

TE

MP

RE

SE

T=

OU

TD

OO

RA

IRT

EM

PE

RA

TU

RE

= N

OT

CO

NN

EC

TE

D U

SE

DU

CT

STA

TIC

CO

NN

EC

TO

R

BI4

BI7

BI8 I

AI7

AI8

AN

AL

OG

IN

PU

TS

Wa

ttM

aste

rO

ve

rla

y#

S0

00

07

9R

ev.

: 1

AW

DU

AL

E-B

US

+24VAC

GND

MA

IN F

AN

RE

LA

Y2

RE

LA

Y3

RE

LA

Y4

RE

LA

Y5

RE

LA

Y6

RE

LA

Y7

RE

LA

Y8

RE

LA

YC

OM

MO

N

MA

IN S

UP

PLY

FA

N V

FD

=E

CO

NO

MIZ

ER

AC

TU

AT

OR

=M

OD

UL

AT

ING

HE

AT

ING

=E

XH

AU

ST

FA

N V

FD

=

AO

1

AO

2

AO

3

AO

4

BA

CN

ET

BA

CN

ET

SH

IEL

D

BA

CN

ET

+

=T

=S

H

=R

DU

CT

STA

TIC

Figure 21: Networked Single Loop System With CommLink & MLPD VAV/Zone Controller Wiring

APPENDIX

45VAV/Zone Controller Package

VAV/Zone Controller System Architecture

Page 46: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

SH

LD

T

R

Ty

pic

al

Te

rmin

al

Blo

ck

s.A

llW

irin

g T

o B

e T

To

T,

SH

LD

(G

)To

SH

LD

(G

) &

R T

o R

TG

R

485 LOOP

VA

V/Z

on

eC

on

tro

lle

r(N

on

-Mo

du

lar)

VA

V/Z

on

eC

on

tro

lle

r(N

on

-Mo

du

lar)

VA

V/Z

on

eC

on

tro

lle

r(N

on

-Mo

du

lar)

Lin

eV

olt

ag

eL

ine

Vo

lta

ge

Lin

eV

olt

ag

e2

4 V

AC

(6 V

A)

24

VA

C(6

VA

)2

4 V

AC

(6 V

A)

Co

nn

ectTo

Ne

xt

VA

V/Z

on

e C

on

tro

ller

On

Lo

ca

l L

oo

p

Ne

two

rk

FIL

EN

AM

E

DE

SC

RIP

TIO

N:

PA

GE

JO

B N

AM

E

1 o

f 1

Co

nn

ec

t To

Lo

op

2V

CC

-XC

on

tro

lle

r &

VA

V/Z

on

eC

on

tro

lle

rs

Co

nn

ec

t To

Lo

op

3M

iniL

ink

PD

Wirin

g &

Co

nn

ectio

n D

iag

ram

VC

CX

2-N

et-

Mu

ltiL

oo

p-1

A.C

DR

Ne

two

rke

d S

yste

m -

Mu

ltip

le L

oo

p

11

0 V

AC

To

24

VA

CP

ow

er

Pa

ck

No

te:

Com

mLin

k M

ust B

e S

et

For

Multip

le L

oop O

pera

tion

Ty

pic

al

Mu

ltip

le L

oo

p N

etw

ork

ed

Sy

ste

m W

ith

VA

V/Z

on

e C

on

tro

lle

rs

No

te:

Mu

ltip

le V

AV

/Zo

ne

Co

ntr

olle

rs C

an

Be

Co

nn

ecte

dTo

AS

ing

leT

ran

sfo

rme

r If

De

sire

d.

Ho

we

ve

r, P

ola

rity

Mu

st

Be

Ob

se

rve

d O

r D

am

ag

eTo

Th

e C

on

tro

ller(

s)

Will

Re

su

lt.

Se

eT

he

Tra

nsfo

rme

r S

izin

g P

ag

e I

nT

his

Ma

nu

al

Fo

rT

ran

sfo

rme

r S

izin

gA

nd

Circu

it D

esig

n I

nfo

rma

tio

n.

Mo

du

lar

Se

rvic

eTo

ol

SD

VC

CX

2C

on

tro

lle

r

10/3

0/1

7S

onya O

lson

BY

:D

AT

E:

Ba

ck

Vie

w o

f C

om

mL

ink

5

Fro

nt

Vie

w o

f C

om

mL

ink

5

Se

ria

l #

CO

MP

UT

ER

US

B

10

/10

0E

TH

ER

NE

T

DIA

G

48

5 L

OO

PP

OW

ER

AC

TL

NK

HIGH

LOW

BA

UD

R(+)

24V

GND

SHLD

T(-)

MULTIPLE

SINGLE

LO

OP

No

te:

Eith

er

AM

od

ula

r S

yste

m M

an

ag

er

SD

,M

od

ula

r S

erv

ice

To

ol S

D,

Or

Co

mp

ute

r W

ith

Prism

2 S

oft

wa

re I

nsta

lled

Ca

n B

e U

se

dTo

Pro

gra

mA

nd

Co

nfig

ure

Th

e O

rio

n S

yste

m.

Ne

two

rk

Lo

ca

l

Lo

ca

l

24

VA

C(6

VA

)

Min

iLin

k P

D 5

Lo

op

1

PD DRV

LOOP DRV

NE

TD

RV

PIC

32 M

LP

DY

S102398 R

EV

3

NE

TW

OR

K

LO

CA

L

PD

CO

MM

PO

WE

R

1 2 4 8 16

32

CO

MM

AD

DR

ES

S

ML

PD

MA

DE

IN

US

A

SERIAL #

C2

2

C2

3

C3

0

C3

7

C4

0

J1

J3

R1

R2

R3

R4

R2

0

R2

1

R22R2

3R

24

R25R2

6

R2

7

R3

1

PD

STA

T1

PD

STA

T2

SW

2

TB

1

TB

2

U8

U1

0

U12

D4

J6

J7 J8

R4

3

R4

4

R4

6

C33

OFF

T SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.1uF

.1uF

.1uF

1002 1002

T

SHR

C2

4

CO

MM

ww

w.o

rio

nc

on

tro

ls.c

om

Wa

ttM

aste

r L

ab

el

#L

B1

02

09

1-0

0R

ev.

01

B

OE

364-2

3-O

RM

INIL

INK

PD

5

TT

T

LO

CA

LN

ET

WO

RK

SH

24 VAC

GND

SH

R

R

LOCALLOOPWIRE TERMINALS

NETWORK LOOPWIRE TERMINALS NETWORK LOOP

COMM CONNECTORS

ADDRESS DIPSWITCH

PO

WE

RT

ER

MIN

AL

S

LOCALLOOPCOMM

CONNECTOR

24 V

AC

PO

WE

R O

NLY

WA

RN

ING

!P

OLA

RIT

YM

US

T

BE

OB

SE

RV

ED

OR

TH

E

BO

AR

D W

ILL

BE

DA

MA

GE

D

Ne

two

rk

Ne

two

rkL

oc

al

24

VA

C(6

VA

)

Min

iLin

k P

D 5

Lo

op

2

PD DRV

LOOP DRV

NE

TD

RV

PIC

32 M

LP

DY

S102398 R

EV

3

NE

TW

OR

K

LO

CA

L

PD

CO

MM

PO

WE

R

1 2 4 8 16

32

CO

MM

AD

DR

ES

S

ML

PD

MA

DE

IN

US

A

SERIAL #

C2

2

C2

3

C3

0

C3

7

C4

0

J1

J3

R1

R2

R3

R4

R2

0

R2

1

R22R2

3R

24

R25R2

6

R2

7

R3

1

PD

STA

T1

PD

STA

T2

SW

2

TB

1

TB

2

U8

U1

0

U12

D4

J6

J7 J8

R4

3

R4

4

R4

6

C33

OFF

T SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.1uF

.1uF

.1uF

1002 1002

T

SHR

C2

4

CO

MM

ww

w.o

rio

nc

on

tro

ls.c

om

Wa

ttM

aste

r L

ab

el

#L

B1

02

09

1-0

0R

ev.

01

B

OE

364-2

3-O

RM

INIL

INK

PD

5

TT

T

LO

CA

LN

ET

WO

RK

SH

24 VAC

GND

SH

R

R

LOCALLOOPWIRE TERMINALS

NETWORK LOOPWIRE TERMINALS NETWORK LOOP

COMM CONNECTORS

ADDRESS DIPSWITCH

PO

WE

RT

ER

MIN

AL

S

LOCALLOOPCOMM

CONNECTOR

24 V

AC

PO

WE

R O

NLY

WA

RN

ING

!P

OLA

RIT

YM

US

T

BE

OB

SE

RV

ED

OR

TH

E

BO

AR

D W

ILL

BE

DA

MA

GE

D

Lin

e V

olt

ag

e

24 V

AC

(15 V

A)

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

DSH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

GN

D

TM

P

SP

AC

E

+

D1

R40

R37

D2

10

02

10

02

10

02

10

02

10

02

10

02

10

02

10

02

36

50

10

02

10

02

36

50

10

02

10

02

47

51

47

51

1002

10

uF

.00

1uF

10

uF

VA

C~

VD

C

VD

E

OFF

36

50

36

50

36

50

36

50

36

50

LOHI

RE

V1

LO

HI

SW

ITC

HO

CC

.

GN

D

BIN

PO

WE

R

AP

PH

B

WD

OG

OS

HB

ST

AT

2

ST

AT

1

AC

TU

AT

OR

HE

AT

AU

X

CO

MM

AD

DR

ES

S

DU

CT

SE

NS

OR

GN

D

+12V

-DIG

ITA

L

SE

NS

OR

SP

AC

E

GN

D

AD

J

TM

P

1 2 4 8 16

32

CW

CC

W

ON

LOOPBAUD

1 2

3.3

V

5.0

VA

IRF

LO

WT

P

GN

D

YS

102588

SE

RIA

L#

E-B

US

V4

V3

R60

R59

C34

TB

1

R30 R29 R28

V2

TB

6

TB

5

P1

R5

TB

4

TB

3

SW

1

R5

R5

R4

R4

R4

R4

R4

R37

R24

R21

R14

R13

R11

R10

R6R5

R4

P3

D7

C25

C15 C5

C4J1

R42

C29

D13

36

50

D9

Wa

ttM

aste

rLa

be

l#

L1

02

20

2R

ev.

:1

AB

RE

LA

YC

ON

TA

CT

RA

TIN

GIS

1A

MP

MA

X@

24

VA

C

AU

XIL

IAR

YH

EA

T

AC

TU

AT

OR

CO

NN

EC

TO

R

DIG

ITA

LS

PA

CE

SE

NS

OR

AN

AL

OG

SP

AC

ES

EN

SO

R

GN

D

GN

D

+1

2V

DC

AD

J

TM

PH

EA

T

CO

M

24 VAC POWER ONLYWARNING! POLARITY

MUST BE OBSERVED

OR THE CONTROLLER

WILL BE DAMAGED

POWERINPUT

E-BUSCONNECTORS

GN

D

GN

D

SH

GND

BIN

TM

P

R+

T-

24 VAC

DU

CT

TE

MP

SE

NS

OR

OC

CU

PIE

DS

WIT

CHCOMM

+ -

1

1 2

AD

DR

ES

S

ON

2 4 8 16

32

BAUD

ADDRESSSWITCH

www.wattmaster.com

OE326-23I-ORP.I. VAV CONTROLLER/ZONE

www.orioncontrols.com

CU

S

R

Mo

du

lar

Sy

ste

m M

an

ag

er

SD

Sy

ste

m M

an

ag

er

TS

-L

No

te:

Th

e S

MT

S-L

IsA

nE

nd

-Use

r In

terf

ace

On

ly.

It C

an

no

t B

e U

se

dTo

Co

nfig

ure

Th

e C

on

tro

llers

.

Lin

eV

olt

ag

e

Sy

ste

m M

an

ag

er

TS

-L(B

ac

k V

iew

)

24

VA

C(6

VA

)

RS

T+

BLACK (R)

Co

nn

ec

t To

T,

SH

, R

Te

rmin

als

On

HV

AC

Un

itC

on

tro

lle

r

RED (24 VAC)

BROWN (GND)

WHITE (T)

BARE (S)

.1uF

YS

102178 R

4

WQ

VG

AG

raphic

al In

terf

ace

WattM

aste

r C

ontr

ols

, In

c

C24

R9R7

R6

R5

R2

R1

C51

C39

C20

C19

C15

C14

C13

C12C11

C10

C9

C7

C1

X3

8.0

0M

hz

OF

F

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

10021002

10021002

1002

1002

10021002

1002

1002

10021002

1002

1002

1002

1002 10021002

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

.1uF

1002

.1uF

1002

1002

.1uF

.1uF

.1uF

.1uF

LTC

3824

1002

1002

1002

1002

1002

1002

66.0

00M

hz

MA

DE

IN

US

A

33

0u

F 5

0V

33

0u

F

1002

SE

RIA

L#

OPT4

OPT3

OPT2

OPT1

TE

RM

RT

C

YS

102178 R

4

WQ

VG

AG

raphic

al In

terf

ace

WattM

aste

r C

ontr

ols

, In

c

CA

L

5V

3.3

V2.5

V

J3

R34R16

R13 R8

R39

X2

R26

R17

R14

C24

U13

R49

R48

R47R46

R45

R44

R43

R40

R37

R35

R32 R31

R29

R27

R24

R22

R12

R11

R10

R9R7

R6

R5

R2

R1

L5

L4

D12

D11

D1

C51

C50

C45

C41

C39

C36

C20

C19

C18

C17

C16

C15

C14

C13

C12C11

C10

C9

C8

C7

C6

C5

C4

C1

J1

R41

C23

C25

C26

R42

X3

R20

C27

C34

C40

U10

U11

C28

C29

R18

C35

D2

L1

R25C31R19

U9

R28C32R30

R33

C30

R15

Q2

R21

R23

SW

1

C2 C3

V1

R36

1002

RS

T+

1002

R T

5V

GN

D

TE

RM

Fo

r S

tan

dA

lon

eA

pp

lica

tio

ns

Bo

th J

um

pe

rs M

ust

Be

ON

4GB

Mo

du

lar

Sy

ste

m M

an

ag

er

SD

(Ba

ck

Vie

w)

M

EN

TE

R

UP

DO

WN

AL

AR

M

ME

NU

RE

LA

YC

ON

TA

CT

RA

TIN

G I

S 1

AM

PM

AX

@ 2

4 V

AC

RS

-48

5 C

OM

ML

OO

P.

WIR

E“R

”T

O“R

”,“T

”T

O“T

”“S

HLD

”T

O“S

HLD

24

VA

C P

OW

ER

ON

LY

WA

RN

ING

!

PO

LA

RIT

Y

MU

ST

BE

OB

SE

RV

ED

OR

TH

E

CO

NT

RO

LL

ER

WIL

LB

E

DA

MA

GE

D

ww

w.a

aon.c

om

ww

w.o

rio

nc

on

tro

ls.c

om

VC

CX

2 C

ON

TR

OL

LE

RO

rio

n N

o.:

OE

338-2

6B

-VC

CX

2A

AO

N N

o.:

V87900

BIN

AR

YIN

PU

TS

BI1

= P

RO

OF

OF

AIR

FL

OW

BI2

BI3

BI5

BI6

AI1

AI2

AI3

AI4

AI5

A6

= D

IRT

YF

ILT

ER

= H

OO

D O

N/O

FF

= R

EM

OT

E O

CC

UP

IED

= R

EM

OT

E C

OO

LIN

G=

RE

MO

TE

HE

AT

ING

= R

EM

OT

E D

EH

UM

IDIF

ICA

TIO

N=

EM

ER

GE

NC

YS

HU

TD

OW

N

= S

PA

CE

TE

MP

ER

AT

UR

E=

SP

AC

E S

LID

E O

FF

SE

T=

SU

PP

LY

AIR

TE

MP

ER

AT

UR

E=

RE

TU

RN

AIR

TE

MP

ER

AT

UR

E=

BU

ILD

ING

PR

ES

SU

RE

= S

UP

PLY

AIR

TE

MP

RE

SE

T=

OU

TD

OO

RA

IRT

EM

PE

RA

TU

RE

= N

OT

CO

NN

EC

TE

D U

SE

DU

CT

STA

TIC

CO

NN

EC

TO

R

BI4

BI7

BI8 I

AI7

AI8

AN

AL

OG

IN

PU

TS

Wa

ttM

aste

rO

ve

rla

y#

S0

00

07

9R

ev.

: 1

AW

DU

AL

E-B

US

+24VAC

GND

MA

IN F

AN

RE

LA

Y2

RE

LA

Y3

RE

LA

Y4

RE

LA

Y5

RE

LA

Y6

RE

LA

Y7

RE

LA

Y8

RE

LA

YC

OM

MO

N

MA

IN S

UP

PLY

FA

N V

FD

=E

CO

NO

MIZ

ER

AC

TU

AT

OR

=M

OD

UL

AT

ING

HE

AT

ING

=E

XH

AU

ST

FA

N V

FD

=

AO

1

AO

2

AO

3

AO

4

BA

CN

ET

BA

CN

ET

SH

IEL

D

BA

CN

ET

+

=T

=S

H

=R

DU

CT

STA

TIC

Figure 22: Networked Multiple Loop System Wiring With VAV/Zone Controllers

Zone

ZoneAPPENDIX

46 VAV/Zone Controller Package

VAV/Zone Controller System Architecture

Page 47: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

A-G

INDEX

47VAV/Zone Controller Package

1 Stage Electric or On/Off HW Heat..............182-Conductor Wire..............1424-Gauge..............1424 VAC Power Terminal Block..............1924 VAC-to-24 VAC..............15

AActuator

Diagnostics..............40Actuator Modular Connector..............19Address Switch Setting..............25AHU Heating Call..............28Airfl ow K-Factor (CFM) Requirements..............27Airfl ow Sensor..............18

Troubleshooting..............39Alarm Detection..............36Allow Box Heat..............27Allow Box Heat With AHU Heat..............27Analog Space Sensor..............18

Troubleshooting..............39APP HB LED..............38Auxiliary Heat..............28, 31, 33Auxiliary Reheat Relay..............18

BBaud Rate Setting..............25Baud Rate Switch Setting..............25Belden #82760 Wire..............14, 43Box Control Method..............27Box Heating Minimum..............30Box Heat With AHU Heat..............27Box Reheat..............28

CCFM Factor..............27Clockwise-to-Open Damper..............27CommLink 5..............8, 26Communications Terminal Block..............19Communication Wiring..............17Connection Diagram

Slaved Zone..............24Controller

Voltage and Environment Requirements..............14, 27Controller Addressing..............25Cooling Minimum..............29Cooling Only Box..............27Counterclockwise-to-Open Damper..............27

DDamper

Control..............34Operating Mode..............27Positions..............29

Diagnostics..............39, 40Digital Room Sensor..............29

Troubleshooting..............39Digital Space Sensor..............18Dimensions..............10, 11, 12Discharge Temperature Sensor..............13, 18Duct Temperature Sensor..............18

Described..............7Duct Temperature Sensor - 6” Probe..............7Duct Temperature Sensor - 12” Probe..............7Dump Zone..............28

EEB101505..............8E-BUS Cables..............9

Described..............9E-BUS Connectors..............19E-BUS Digital Room Sensor..............7

Troubleshooting..............39, 41Electric Staged Heat..............21Expansion Board Modular Connector..............19Expansion Module

Diagnostics..............40Dimensions..............10Outputs..............19Troubleshooting..............40Wiring..............21, 22, 23

Expansion Relays..............27, 28Expansion Relays - Steps of Reheat..............27

FFactory Mounted..............13Fan Enable..............19Fan Relay Staging..............31Fan Terminals..............21, 23Force Modes..............37

GGND-to-GND..............15

Page 48: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

H-O

Zone

ZoneINDEX

48 VAV/Zone Controller Package

HHeating

Minimum..............29Stage 1..............19Stage 2..............19Stage 3..............19

Hot Water Valve..............19HVAC Modes..............29

IInitialization..............26Installation..............13Interconnected System

Addressing..............25Internal Trend Logging..............36, 37Internet/LAN Connection..............9IP Module Kit..............9

KK-Factor..............27

LLED Blink Codes..............38LED Locations..............38LEDs

APP HB..............38Operation..............38OS HB..............38STATUS 1..............38STATUS 2..............38WDOG..............38

LED Troubleshooting..............38

MMain Fan Status..............27, 28Maverick Zones..............35MiniLink PD 5..............9, 36

Addressing..............25Modes of Operation..............29Modular Connectors

Actuator..............19Modular Service Tool SD..............8, 26Modular System Manager SD..............8, 26Modulating Heat..............31, 33Modulating Hot Water Heat Wiring..............21, 22Modulating HW Heat..............22Modulating (Proportional) Heat..............31, 33Motion Sensor Occupancy Detection..............18, 28

Mounting..............13Multiple Daily Setpoints/Schedules..............27Multiple Loop VAV/Zoning..............43

NNetworked Multiple Loop System..............46Networked Single Loop System..............44, 45Networked System Addressing..............25Night Minimum..............30

OOccupied Mode..............29Occupied Mode Sequences..............30, 31Occupied or Window Switch..............18Occupied/Unoccupied Mode..............29OE210 - OE213.............7OE217-02..............7OE217-03..............7OE230..............7OE231..............7OE282-01..............6OE282-03..............7, 24OE325-03..............4, 6OE326-23D-OR..............4, 6OE326-23I-OR..............4, 6OE336-23-EM1..............6OE361-13..............8OE364-22..............9OE364-23..............9OE364-23-OR..............9OE366..............9OE391-12..............8OE392-11..............8OE392-12..............8OE415-02..............9OE508..............9OE520-XX-PT..............7OE521-XX-PT..............7OE523..............24OE736-03-PT..............5OE742-03-OR..............4, 5OE744-03-OR..............4, 5Off Mode..............29, 32On/Off HW Heat..............22Operation Modes..............29Operator Interfaces..............26OS HB LED..............38Override Button

Digital Room Sensor..............29Overrides..............37

Page 49: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

P-S

PParallel Flow Fan Terminals..............30, 32, 34Polarity..............14, 15Power/Comm Board

Connection Diagram..............17Sizing..............14Wiring..............14, 17

Powering Up..............25Power Wiring..............15Power Wiring Diagram..............17Pressure Dependent Rectangular Damper Kit..............5Pressure Dependent VAV/Zone Controller..............6Pressure Dependent VAV/Zone Controller Package..............5Pressure Independent Boxes..............27Pressure Independent Boxes - Airfl ow..............27Pressure Independent VAV/Zone Controller..............6Pressure Independent VAV/Zone Controller Package..............5Pressure Independent VAV/Zone Controller with

Terminal Blocks..............6Prism 2..............9, 26, 35Proof of Flow..............19Proportional Heat..............31, 33Proportional Heating Signal..............27Push-Button Override..............28, 29Push-Button Override Group ID#..............28Push-button Override Operation..............29

RRectangular Damper Kit..............5

Dimensions..............11Mounting..............13

Reheat..............27Reheat Relay Staging..............31Relay Output #2 - Heating Stage 1..............19Relay Output #3 - Heating Stage 2..............19Relay Output #4 - Heating Stage 3..............19Relays

Analog Output..............19Fan Enable..............19Heating Stage 1..............19Heating Stage 2..............19Outputs..............19Staging..............31

Resistance TestingDigital Room Sensor..............41Modular Room Sensor..............41

Round Damper..............7Round Damper Kit..............12

Dimensions..............12Mounting..............13

SScheduling..............29SCR Electric Heat..............23Sensors

Mounting..............13Temperature Sensor Testing..............41

Series Flow Fan Terminals..............30, 32, 33Service Tool..............26Setup

Zone/VAV..............27Single Loop VAV/Zoning..............43Sizing Transformer..............15Slaved Zone Damper

Connection Diagram..............24Wiring..............24

Slaved Zone Damper Kit..............7, 11Dimensions..............11

Slave Wiring Adapters..............24SMTS-L..............8, 26, 44-46Space Cooling Mode..............29, 30, 32Space Heating Mode..............29, 31, 32, 33Space Sensor

Type of..............28Space Temperature Sensor

Diagnostics..............39Troubleshooting..............39

Space Temperature Sensors..............13Mounting..............13

Space Vent Mode..............29, 30, 32Stand Alone Box Running Continuous Occupied

Mode..............28Stand Alone System Addressing..............25Standard Room Sensor..............7, 29STATUS1 LED..............38STATUS2 LED..............38STATUS 2 LED Blink Codes..............38Steps of Reheat..............27, 28Supply Air Cooling Mode..............29Supply Air Duct Temperature Sensors

Mounting..............13Supply Air Heating Mode..............29Supply Air Temperature Sensor..............13, 18

Diagnostics..............39Troubleshooting..............39

Supply Air Vent Mode..............29System

Powering-Up..............15System Manager TS-L..............8, 26

Wiring..............17, 21, 22, 23, 44-46

INDEX

49VAV/Zone Controller Package

Page 50: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

T-Z

TTemperature/Resistance/Voltage Table..............42Temperature Sensor Testing..............41Tenant Override Logs..............34, 36Terminal Block..............19Testing for Maverick Zones..............35Thermistor Sensors

Resistance..............42Temperature..............42Testing..............42

Touch Screen System Manager..............26Transformer Sizing..............14, 15, 16Trend Logging..............37Troubleshooting

Airfl ow Sensor..............39E-BUS Digital Room Sensor..............39, 41Expansion Module..............40LEDs..............38Space Temperature Sensor..............39Supply Air Temperature Sensor..............39VAV/Zone Controller Expansion Module..............40Zone Damper Actuator..............40

UUnoccupied Mode..............29Unoccupied Mode Sequence..............32USB-Link 2 Kit..............9

VVA Load Requirements..............14VA Rating..............14VAV/Zone Controller

Confi guration..............27Dimensiions..............10Inputs..............18LED Locations..............38Outputs..............18Set-Up..............27Wiring..............14, 17

VAV/Zone Controller Expansion Module..............6Dimensions..............10Inputs..............18Outputs..............19Troubleshooting..............40Wiring..............21, 22, 23

VAV/Zone Controller Package..............5Mounting..............13Wiring..............20

VAV/Zone Controller System Architecture..............43

VAV/Zone Damper Control..............34VAV/Zone Force Modes..............37Vent Minimum..............29Voltage

Proper..............15Voltage and Environment Requirements..............14, 27Voting Zone..............27

WWDOG LED..............38Window Open Detection..............28Window Open Detection Mode..............18Wire

Belden #82760..............14, 43Wire Size

Minimum for 24 VAC..............14Wiring..............14

24-gauge..............1424 VAC-to-24 VAC..............15GND-to-GND..............15Modulating Hot Water Heat..............21, 22Power/Comm Board..............17SCR Electric Heat..............23Slaved Zone..............24Slaved Zone Damper..............24VAV/Zone Controller..............14VAV/Zone Controller Expansion Module..............21, 22, 23VAV/Zone Controller Actuator Package..............20

Wiring Considerations..............14

ZZone Controller Actuator Package Wiring..............20Zone Damper Actuator..............6

Dimensions..............10Troubleshooting..............40

Zone Polling..............35Zone Voting..............35Zoning..............35

Zone

ZoneINDEX

50 VAV/Zone Controller Package

Page 51: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

VAV/Zone Controller 51

NOTES

VAV/Zone Controller Package

Page 52: VAV/Zone Controller Package Technical GuideThe OE326-23I-OR VAV/Zone Controller is designed for pres-sure independent VAV Box and Zone Damper applications. It is supplied with an integral

Form: OR-VAVZP-TGD-01B Printed in the USA October 2017All rights reserved Copyright 2017WattMaster Controls Inc. • 8500 NW River Park Drive • Parkville, MO 64152 Phone (816) 505-1100 www.orioncontrols.com Fax (816) 505-1101