—WEBINAR 19 NOVEMBER 2020
Houd het proces in beweging met de juiste combinatie van motorstartersErwin Rodenburgh – Product Marketing Specialist
—Motors are an integral part of everyone’s lives
19 November 2020 Slide 2
Applications that keep the world turning
Imagine if…?
...opening a water tap
...being in an airconditioned building
...your daily commute to work
...buying processed food in the supermarket
...refueling your car
This is only a small fraction of examples where motors keep the world turning –efficiently, reliably and safely.
—
– Pumps
– Fans
– Compressors
– Gear boxes
– Conveyors
– Mixers
– General machinery
– etc
Motors
19 November 2020 Slide 3
Applications
—Motor starting methods
—Market trends
19 November 2020
https://www.globalefficiencyintel.com/new-blog/2017/infographic-energy-industrial-motor-systemsInternational Energy Agency (IEA)https://www.prnewswire.com/news-releases/global-low-voltage-electric-motor-market-2018-2023-300655640.htmlhttps://www.capiel.eu/data/6685-Capiel-Tryptique-EN2-Version-Web.pdf
Slide 5
Increasing industrialization creates a huge demand for low-voltage electric motors
47%Electric motor-driven systems account for around 47 % of global electricity consumption
68 %About 68 % of the electricity consumed by electric motors is used by medium-size motors, those in the 0.75 kW to 375 kW input power range.
80 %of all motors are used in full speed applications
—Starting methods
19 November 2020 Slide 6
Direct-on-linefrom 0.06 up to ~22 kW
Star-deltafrom 30 up to ~200 kW
—Starting methods
19 November 2020 Slide 7
Softstartersfrom 1.5 up to 710 kW
VFDfrom 0.75 up to 710 kW
—How to select the starting method
19 November 2020 Slide 8
Installation criteria
Starting/control Economical interest Energy saving
Engineering simplicity
Maintenance easiness
Footprint & weight
Flexibility of adaptation
Direct on line
Star-Delta
Softstarter
Drive
—Energy efficiency
—
One of the biggest challenges of our time is the reduction of CO2 emissions. ABB's motor starting solutions are ready for super premium efficiency motors and help reduce the CO2 footprint with energy-efficient technology.
Energy-efficient motor starting solutions
19 November 2020 Slide 10
Reduce CO2 emissions with ABB’s solutions
2015
IE3 IE2 + variable speed drive(for motors 7.5-375 kW)
2017
IE3 IE2 + variable speed drive (for motors 0.75-375 kW)
2023-7
IE4
(for motors 75-200 kW)
2021-7
IE3
(for motors 0.75-375 kW)
IE4 = Super premium efficiencyIE3 = Premium efficiencyIE2 = High efficiencyIE1 = Standard efficiency
—Energy-efficient motor starting solutions
19 November 2020 Slide 11
IE3/IE4 – (Super) Premium efficiency motors
Starting current can be roughly 25 % higher than in IE1/IE2 motors, which may lead to unwanted tripping of the protection device. In addition, a correct evaluation of the electrical endurance of the contactor should be carried out.
Reduce CO2 emissions with ABB’s solutions
—Energy-efficient motor starting solutions
19 November 2020 Slide 12
Reduce CO2 emissions with ABB’s solutions
—
Het vervangen van een motor voor een energiezuinige variant kan een energiebesparing opleveren van 20-30% op het verbruik.Welke acties ondernemen jullie om energie te besparen?
• Toepassing van < IE2 motoren (in combinatie met drive)• Vervangen voor energiezuinige motoren IE3• Vervanging voor energiezuinige motoren IE3 in combinatie met drive • Vervangen voor energiezuinige motoren IE4
Poll #1
19 November 2020 Slide 13
—Between the network and a motor load
—Between the network and a motor loadWhat are the functions on the power circuit in between the supply source and a motor?
• Isolate / Disconnect the line
• Protect against short-circuit
• Switch on and off the motor
• Protect against overload
• Protect against phase failure
• Control motor speed
Supply
Functions:
Motor
—Between the network and a motor loadWhat low voltage component can you use to fill these functions?
• Fuse
• Switch
• Switch fuse
• Breaker
• Manual Motor starter
• Contactor
• Soft starter
• Drive
• Overload relay
• Electronic Compact Starter
• ….
Supply
Components:
Motor
—Between the network and a motor loadWhat component does which function?
Fuse Switch fuse Breaker Manual Motor Starter Contactor Overload relay Soft Starter Variable speed
driveElectronic
Compact Starter
Short Circuit Protection
Isolate the line for maintenance
Start and stop the motor
Protect against overload
Protect against phase failure
Soft Start
Speed Control
—Fundamentals of Contactors Utilization categories defined by the standards
© ABB Group 19 November 2020 | Slide 18
ApplicationUtilization category
AC-1 AC-3 AC-4 AC6b DC-1
Machine tool motors
Heating resistances
Cooling compressor motors
Ventilation motors
Elevator motors
Overhad crane motors
Irrigation pump motors
Mining & Conveyers motors
PV Plant solar panels
Power factor correction capacitor bank
—Between the network and a motor loadWhat is your ideal components arrangement to operate a motor?
Manual Motor Starter
Manual Motor Starter
Magneticonly MMS
Contactor Contactor Contactor
Overload relay
Overload relay
Switch Fuse
Magnetic only MMS
Electronic compact starter
MCCB EkipM
Contactor
Mini contactors
Magneticonly MMS
—Vragen
© ABB Group 19 November 2020 | Slide 20
—Co-ordinationSelection of motor starting & protection devices
—
Three important criteria:
1. System Limitation• Transformer capacity• Breaker / Cable capacity
2. Voltage fluctuation • Cable length• Base loads
3. Co-ordination
Electrical System Selection of motor starting & protection devices
19 November 2020 Slide 22
MSB
M
Common Point
M M
MCC
Dotted lines are base load or other loads
Grid
—
Risks of not having Co-ordination.
• Risk of FIRE, damage to property and causes harm to personal
• ARC flash/blast may occur, injury to personal
• Damage to components,
• Longer down time
Co-ordination with short circuit protective device
Selection of motor starting & protection devices
19 November 2020 Slide 23
—
IEC 60947-4-1 is the standard where co-ordination is defined.
There are 2 types of co-ordination.
Type "1" co-ordination requires that, under short-circuit conditions, the contactor or starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement of parts.
Type "2" co-ordination requires that, under short-circuit conditions, the contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment.
Co-ordination with short circuit protective deviceSelection of motor starting & protection devices
19 November 2020 Slide 24
—Selection of motor starting & protection devices
19 November 2020 Slide 25
Selected optimized coordination tables
ABB provides coordination tables for the selection of low voltage equipment, specifically tested for starting and protecting IE3/IE4 motors in the SOC tool.
Usage of coordination tables helps reduce the time for selection and design of solutions as well as the risk of unwanted downtime, e.g. caused by nuisance tripping. This provides protection and safety, further driving down the total cost of ownership.
Co-ordination with short circuit protective device
—
Demo met de SOC tool
Selection of motor starting & protection devices
19 November 2020 Slide 26
Live demo
—Keep things moving with protection and controlat every level.
—Enhanced solutions
19 November 2020 Slide 28
Get robust protection with enhanced safety, control and monitoring
—Motor protection
19 November 2020 Slide 29
Thermistor motor protection
Direct monitored motor temperature
Monitoring of all possible different disturbing influences like:• Insufficient cooling• Too small dimensioning• Overload• Differences in the ambient temperatures
between panel board and the motor environment
• High switching frequencies
F1
I >I >I >Q1
K1
M1
L1L2L3
A1
A2
υ
—Additional protection
19 November 2020 Slide 30
Monitoring functions
• Over- and under voltage• Phase failure• Phase sequence• Imbalance
F1
I >I >I >Q1
K1
M1
L1L2L3
3-phase monitoring relay
Motor starting solution
—
Hybrid technology - Combination of semiconductors with relaysProduct Introduction
19 November 2020 AC 53 a: (IEC-60947-4-2; 5.4.2: „Control of squirrel cage motors: 8h duty with on-load currents for start, acceleration, run“Slide 31
Long electrical durability- Up to 30 Mio electrical cycles Contactor: ~10 Mio
ELECTRONIC COMPACT STARTER
„Semiconductor“ „Relay“
—
19 November 2020 Slide 32
Electronic Compact StarterOverview of space saving
Direct Online Starter DOL
Direct Online Starter with Emergency Stop - DOLE
Reversed Online Starter ROL
Reversed Online Starter with Emergency Stop - ROLE
~71 % space saving
~86 %space saving
~81 %space saving
~90 % space saving~72 % space saving
Reverser
—
Starting and Safety functions of the Electronic Compact Starter
19 November 2020 SIL: „Safety Integraty level“ PL e : Performance level „e“Slide 33
Emergency stop versions
- Combination with Sentry Safety relays
- Complying with SIL 3 and Pl e
- ATEX certified
Direct Online Starter - DOL Reversing Starter - ROL Emergency Stop Function
Electronic Compact Starter
F F R
Advantage of HMI
– LED confirmation that Motor is switched on
• Forward running
Advantage of HMI
– LED confirmation that Motor is switched on
• Reverse running
—
Motor protection functionElectronic Compact Starter
19 November 2020 Slide 34
Overload protection
– ECS protects against phase asymmetry
• Trip is indicated though LED’s
• Shut down ≥ 33% 2 min≥ 67% 1.8 sec
Protection against phase failure
I1 I2 I3
Class 10A – ECS protects motor against overload current
– Tripping Class 10A
Protection against phase asymmetry
– detected through current measurements
– switches off the motor after 1.5 to 2 s, to protect from overheating
– Phase failure indicated by the LED’s
—
Een motor en de startercombinatie gaan meestal niet plotseling kapot, vaak zijn er al aanwijzingen dat er iets mis is.Wanneer komen jullie in actie om onderhoud uit te voeren?
• Vervangen wanneer het kapot gaat• Onderhoud met een vast interval• Voorspellend onderhoud
Poll #2
19 November 2020 Slide 35
—Total cost of ownership
—Market drives
19 November 2020
https://www.globalefficiencyintel.com/new-blog/2017/infographic-energy-industrial-motor-systemshttps://news.thomasnet.com/companystory/downtime-costs-auto-industry-22k-minute-survey-481017U.S. National Response Centerhttps://iac.university/technicalDocs/prodman.pdf
Slide 37
Cost incurred by downtime
In process industries, the financial losses from downtime can be extensive.
30 %Of global electricity isconsumed in electric motorsystems in the industry
1.3 M$/hCost per hour of production downtime for automotive industry
50 % Additional costs for repairing a failed asset than if the problem had been addressed before
8 hoursIs the average time it takes to remove and replace a failed production motor
—Advanced solution benefits
19 November 2020 Slide 38
Safe and reliable Integrated and future ready Simple configuration
—Advanced solutions
19 November 2020 Slide 39
Tmax XT5 Ekip M Touch LRIU
ABB Ability™ EDCS7 com. protocols plus cloud connectivity
Fieldbus networks • Modbus RTU• Profibus DP• DeviceNet™
Ethernet networks• Modbus TCP• Profinet• Ethernet/IP™• IEC 61850
Ekip Cartridge• Ekip Supply• Ekip CI• Ekip Com...• Ekip Com Hub
Interface to the contactor
PTC thermistor
XT5 Ekip M Touch LRIU
AF contactor
—Advanced solutions
19 November 2020 Slide 40
Universal Motor Controller UMC100.3
Connection to DCS, ABB Ability™800xA and
gateway for ABB Ability™ EDCS
Universal Motor Controller
UMC100.3
AF contactors
Manual motor starter Voltage module
Digital module
Analog / temperature module
Fieldbus• Modbus RTU• DeviceNet™• Profibus DP
Industrial Ethernet• EtherNet/IP™• Profinet IO• Modbus TCP
—
The purchasing price makes up only a fraction of the total cost of ownership. Discover how ABB constant speed motor starting and protection solutions can help drive down the total cost of ownership of your installations.
Reduce the total cost of ownership
19 November 2020 Slide 41
Easy selection of compatible solutions
Cost of purchasing Cost of running
~1/3
Cost of not running
~2/3
Total cost of ownership
—Afsluiting
—Meer informatie?
19 November 2020 Slide 43
Contactor Guide Manual Motor Starter Guide
Explosive Atmospheres
—
SOC (Selected Optimized Coordination) is een webapplicatie die de mogelijkheid biedt voor het selecteren van geteste motor starting & protection-combinaties.
Open de SOC-tool: https://www.lowvoltage-tools.abb.com/soc
Aan de slag
19 November 2020 Slide 44
SOC-tool
—Meer weten? Ideeën, vragen of opmerkingen, we horen het graag
19 November 2020 Slide 45
Erwin Rodenburgh Technical Support
—Technical Support
—Erwin RodenburghProduct Marketing Specialist motorstarting & safety
[email protected]+31 (0)6 21 10 57 40
linkedin.com/in/rodenburgh
[email protected]+31 88 26 00 900