es160513045s-1 report iec 62040-3

54
TRF No. IEC62040_3B Page 1 of 54 Report No.: ES160513045S-1 Ver.1.0 TEST REPORT IEC 62040-3 Uninterruptible power systems Part 3: Method of specifying the performance and test requirements Report Number. .............................. : ES160513045S-1 Date of issue ................................... : Sep. 03, 2018 Total number of pages ................... 54 pages Applicant’s name ........................... : EAST Group Co., Ltd. Address ........................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industrial Park, Dongguan City, Guangdong Province, China Test specification: Standard .......................................... : IEC 62040-3 (Second Edition): 2011 Test procedure ............................... : Compliance with IEC 62040-3 (Second Edition): 2011 Non-standard test method………..: N/A Test Report Form No. .................... : IEC62040_3B Test Report Form(s) Originator .... : Electrosuisse Master TRF...................................... : Dated 2011-08 Copyright © 2011 Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02. Test item description ..................... : Uninterruptible Power Supply Trade Mark ...................................... : EAST Manufacturer .................................. : EAST Group Co., Ltd. No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industrial Park, Dongguan City, Guangdong Province, China Model/Type reference .................... : 50kVA, 60kVA, 80kVA,100kVA,120kVA Ratings ............................................ : See marking plate

Upload: others

Post on 03-May-2022

21 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ES160513045S-1 Report IEC 62040-3

TRF No. IEC62040_3B Page 1 of 54 Report No.: ES160513045S-1 Ver.1.0

TEST REPORT IEC 62040-3

Uninterruptible power systems Part 3: Method of specifying the performance and test requirements

Report Number. .............................. : ES160513045S-1

Date of issue ................................... : Sep. 03, 2018

Total number of pages ................... 54 pages

Applicant’s name ........................... : EAST Group Co., Ltd.

Address ........................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industrial Park, Dongguan City, Guangdong Province, China

Test specification:

Standard .......................................... : IEC 62040-3 (Second Edition): 2011

Test procedure ............................... : Compliance with IEC 62040-3 (Second Edition): 2011

Non-standard test method………..: N/A

Test Report Form No. .................... : IEC62040_3B

Test Report Form(s) Originator .... : Electrosuisse

Master TRF ...................................... : Dated 2011-08

Copyright © 2011 Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.

Test item description ..................... : Uninterruptible Power Supply

Trade Mark ...................................... : EAST

Manufacturer .................................. : EAST Group Co., Ltd. No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industrial Park, Dongguan City, Guangdong Province, China

Model/Type reference .................... : 50kVA, 60kVA, 80kVA,100kVA,120kVA

Ratings ............................................ : See marking plate

Page 2: ES160513045S-1 Report IEC 62040-3
Page 3: ES160513045S-1 Report IEC 62040-3

TRF No. IEC62040_3B Page 3 of 54 Report No.: ES160513045S-1 Ver.1.0

List of Attachments (including a total number of pages in each attachment): Attachment No. 1: 4 pages of photograph.

Summary of testing:

Tests performed (name of test and test clause): The submitted samples were found to comply with the requirements of: IEC 62040-3 (Second Edition):2011

Testing location: EMTEK (SHENZHEN) CO., LTD. Bldg 69, Majialong Industry Zone, Nanshan District, Shenzhen, Guangdong, China

Summary of compliance with National Differences

National differences and Group differences as per CB bulletin.

The product fulfils the requirements of IEC 62040-3 (Second Edition):2011

Page 4: ES160513045S-1 Report IEC 62040-3

TRF No. IEC62040_3B Page 4 of 54 Report No.: ES160513045S-1 Ver.1.0

Copy of marking plate The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks.

Model: 50kVA MODEL: 60kVA

MODEL: 80kVA MODEL: 100kVA

MODEL: 120kVA

Page 5: ES160513045S-1 Report IEC 62040-3

TRF No. IEC62040_3B Page 5 of 54 Report No.: ES160513045S-1 Ver.1.0

Test item particulars .................................................. :

Classification of installation and use ...................... : [] movable [] hand-held [] transportable [X] stationary [] for building-in [] direct plug-in

Supply Connection ..................................................... : [] pluggable equipment [] type A [] type B [X] permanent connection [] detachable power supply cord [] non-detachable power supply cord [] not directly connected to the mains [] built-in component, consider in end system

Operating condition ................................................... : [X] continuous [] rated operating / resting time:

Possible test case verdicts:

- test case does not apply to the test object ........... : N/A

- test object does meet the requirement ................. : P (Pass)

- test object does not meet the requirement .......... : F (Fail)

Testing ......................................................................... :

Date of receipt of test item ........................................ : N/A

Date (s) of performance of tests ............................... : N/A

General remarks:

The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a comma / point is used as the decimal separator.

Manufacturer’s Declaration per sub-clause 6.2.5 of IECEE 02:

The application for obtaining a CB Test Certificate includes more than one factory location and a declaration from the Manufacturer stating that the sample(s) submitted for evaluation is (are) representative of the products from each factory has been provided ....................................................... :

Yes Not applicable

When differences exist; they shall be identified in the General product information section.

Name and address of factory (ies) .......................... : Same as manufacturer

Page 6: ES160513045S-1 Report IEC 62040-3

TRF No. IEC62040_3B Page 6 of 54 Report No.: ES160513045S-1 Ver.1.0

General product information: This report is amended from previous report ES160513045S, issued on Aug. 05, 2016, due to below amendments. - Updated date of issue. No any tests need be considered. The equipment is on-line type uninterruptible power supply with step-sinewave o/p (line mode and battery mode) for general supply of office equipment.

Model difference:

All models have the same constructions, circuit diagram and PCB layout. Only model name, appearance and the parameter of some parts are different. All tests were performed on model 120KVA which means the typical model.

The maximum operating temperature is 40C, Relative humidity 5 to 95%, no condensation allowed, ambient storage temperature range of -15 to +55C in the protective package.

Operating altitude up to 2000m above sea level.

Page 7: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 7 of 54 Report No.: ES160513045S-1 Ver.1.0

5 ELECTRICAL SERVICE CONDITIONS AND PERFORMANCE --

5.1 General P

5.1.1 UPS configuration P

- quantity of UPS units and their topology P

- Redundancy configuration as applicable P

- Any mayor UPS switch P

- operator access or restricted access classification in accordance with IEC 62040-1

See separate safety report. P

5.1.2 Markings and Instructions P

Marked and supplied with adequate instruction for the installation and operation of the UPS and its controls and indications

All required markings are affixed on labels located on the enclosure of UPS.

P

Markings and instructions in accordance with sub-clause 4.7 of IEC 62040-1

See separate safety report. P

5.1.3 Safety complies with the safety requirements of UPS prescribed in IEC 62040-1

See separate safety report. P

5.1.4 Electromagnetic compatibility complies with the requirements of IEC 62040-2

Emission and immunity comply with IEC 62040-2 C3, see separate report

P

5.2 UPS input specification P

5.2.1 Conditions for normal mode operation P

a) rated voltage 380/400/415V at 100% load. P

b) r.m.s. voltage variation ±25%, at 100% load P

c) rated frequency 50Hz/60Hz P

d) frequency variation ±2Hz P

e) for three phases input, voltage unbalance with an unbalance ratio of 5%

(see appended table 6.2.2.7) P

f) total harmonics distortion (THD) of voltage, according to IEC 61000-2-2

P

g) transient voltage; within the electromagnetic immunity levels prescribed in IEC 62040-2

P

5.2.2 Characteristics to be declared by the manufacturer P

a) number of phases 3 phases P

b) neutral requirements With neutral P

d) power factor at rated current 0.9pf at 100% load P

e) inrush current characteristics ≤100% of rated current for ≤1 cycles.

P

f) maximum continuous current at the worst-case condition

Maximum 303A at Normal condition, Maximum 272.7A at bypass condition.

P

Page 8: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 8 of 54 Report No.: ES160513045S-1 Ver.1.0

g) overload current Maximum 40A at Normal condition, Maximum 60A at bypass condition.

P

h) total harmonic distortion (THD) of current <35% P

i) minimum short current power capacity; in compliance with: - IEC 61000-3-2 (UPS ≤16A) - IEC 61000-3-12 (16A < UPS ≤75A) - IEC 61000-3-4 (UPS > 75A)

>75A P

j) earth leakage current characteristics Maximum Earth leakage < 5% of nominal input current rating.

P

k) a.c. power distribution system compatibility TN, TT or IT):

TN, TN-S, TN-C, TN-C-S, TT (Three-phase, four-wire + PE).

P

5.2.3 Characteristics and conditions to be identified by the purchaser P

a) pre-existing harmonic voltage distortion when of 75% of IEC 61000-2-2 compatibility level at the intended point of coupling of the UPS

Provided P

b) requirements for compatibility with the characteristics of protective devices of the UPS input supply

REC input switch, bypass input switch,output switch,maintenance switch and battery switch are optional parts.

P

c) requirements for all-pole isolation P

d) stand-by generator characteristics Compatible with generator of rating typically >2x UPS kW.

P

5.3 UPS output specification P

5.3.1 Conditions for the UPS to supply a load P

- the input conditions of 5.2.1 being satisfied, or P

- the energy storage system being available P

5.3.2 Characteristics to be declared by the manufacturer P

a) performance classification in accordance with 5.3.4

P

b) rated voltage and steady state variation AC380/400/415V, ±1% Balanced static load, ±6% with 5ms recovery from 10% to 90% load step, ±5% Balanced dynamic load for normal mode, ±0.1Hz (single module), ±0.1Hz (Parallel system) for Stored Energy Mode

P

c) rated frequency and free running variation 40-70Hz P

d) maximum frequency range 40-70Hz P

e) rate of change of frequency when synchronizing 2Hz/s P

f) number of phases available 3 phases P

Page 9: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 9 of 54 Report No.: ES160513045S-1 Ver.1.0

g) neutral availability With neutral P

h) a.c. power distribution system compatibility: TN, TN-S, TN-C, TN-C-S, TT (Three-phase, four-wire + PE).

P

i) total harmonic distortion (THD) of voltage (at linear and non-linear load as specified in annex E):

P

- in normal mode <1% with linear load, 5% with non-linear load

P

- in stored energy mode <1% (Across a linear load); 5% (Across a non-linear load)

P

j) output voltage transient deviation Vrms L-L or L-N <5% transient overshoot, 20ms recovery time

P

k) rated active and apparent output power and rated current

AC380/400/415V, 181.8A/173.9A/166.7A 120KW

P

l) overload capability 105–110% load 60 minutes, 110–125% load 10 minute, 125–150% load 1 minute, 150–200% load 200m sec, >200% load after 100ms,Change to bypass

P

m) current limit identification 1.25X rating current P

n) fault clearing capability Through upstream breaker or fusing for BYPASS. Through fusing and breaker for Rectifier.

P

o) rated load power factor 0.9 P

p) permissible displacement power factor range of the load (cos. Φ)

0.9 lagging to 0.9 leading with de-rating.

P

q) voltage unbalance and phase angle displacement <2 deg. P

e) UPS efficiency at 25%, 50%, 75% and 100% reference test load

90.2% 92.5% 92.3% 90.94% P

5.3.3 Characteristics and conditions to be identified by the purchaser P

a) loads generating harmonic currents (max. levels permitted in IEC 61000-3-2, /-12/ -4)

Provided P

b) asymmetric loads requiring circulation of a d.c. current

Provided P

c) independent earth of the neutral required Provided P

d) load distribution facilities Provided P

e) requirements of all-pole isolation Provided P

f) requirements for coordination with characteristics of protective devices

Provided P

g) future extension/expansion requirements Provided P

Page 10: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 10 of 54 Report No.: ES160513045S-1 Ver.1.0

h) stand-by generator characteristics Compatible with generator of rating typically >1,5x UPS kW.

P

i) functional availability and degree of redundancy Provided P

j) output overvoltage protection Provided P

5.3.4 Performance classification P

UPS complying with this standard in accordance with the coding: AAA BB CCC

P

AAA = Input dependency characteristic VFI P

BB = Voltage waveform characteristic SS P

CCC = Dynamic output performance 111 P

5.4 Stored energy specification P

5.4.1 General See technical specification P

5.4.2 Battery P

5.4.2.1 Requirements for all batteries See separate safety report. P

5.4.2.2 Characteristic to be declared by the manufacturer P

a) life 5 or 10 years(depends) P

b) quantity of blocks or cells and of paralleled strings

28 blocks, 168 cells per battery string or 29 blocks, 174 cells per battery string or 30 blocks, 180 cells per battery string (default)or 32 blocks, 192 cells per battery string .

P

c) nominal voltage of total battery 336V (168 Cells) or 348V (174 Cells) or 360V (180 Cells, Default)or 384V (192 Cells).

P

d) battery technology Boost/buck. P

e) nominal capacity of total battery Depend on battery size. N/A

f) stored energy time Depend on battery size. N/A

g) restored energy time Restored energy time to 90%: Maximum 10 hours recommended (depend on battery size).

P

h) ambient reference temperature Battery (installed separately): +5 to +25 battery life. 

P

i) earth condition of d.c. link/isolation P

j) r.m.s. ripple current during normal mode (see appended table) P

k) nominal discharge current during stored energy mode

DC450Vmax, 133Amax. P

l) d.c. fault current rating P

Page 11: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 11 of 54 Report No.: ES160513045S-1 Ver.1.0

m) cable voltage drop recommendation <1% of nominal DC voltage at rated battery current.

P

n) protection requirements DC input breaker or fuse. P

o) charging regime Advanced Battery Management (ABM®) = 90% resting,10% floating/charging (typical).

P

p) charging voltage and tolerance band Float charge voltage : 168/174/180/192 x 1.67V = 381/395/408/435V

P

q) end of discharge voltage Maximum charge voltage: 216/228/240 x 2.35V = 508/536/564V 1.67V/Cell

P

r) charging current limit or range Charging current (at full load) 10A

P

5.4.2.3 Characteristics and conditions to be identified by the purchaser P

5.5 UPS switch specification REC input switch, bypass input switch, maintenance switch and output switch are optional parts.

P

5.6 Communication circuits Mini-Slot cards: Web/SNMP, Relay/RS232, Industrial Relay, ModBus.

P

6 UPS tests --

6.1 Summary P

6.1.1 Venue, instrumentation and load P

6.1.1.1 Test venue P

A UPS shall generally be tested at the manufacturer’s premises and in accordance with Table 3

P

6.1.1.2 Test instrumentation P

6.1.1.3 Test load P

Test load are performed as prescribed in the relevant test clause, with

P

- reference linear load P

- reference non-linear load P

6.1.2 Routine test Decided by manufacture and purchaser

P

6.1.3 Site test N/A

6.1.4 Witness test Decided by manufacture and purchaser

P

Page 12: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 12 of 54 Report No.: ES160513045S-1 Ver.1.0

6.1.5 Type test P

6.1.6 Schedule of tests N/A

Tests shall be performed in accordance with Table 3 N/A

6.2 Routine test procedure P

6.2.2 Electrical P

6.2.2.1 Insulation and dielectric See separate safety report. P

6.2.2.2 Cable and interconnection check P

All a.c. and d.c. supply terminals are connected to the a.c. input supply, to the stored energy source and to the load

P

Any communication circuit is connected as required P

6.2.2.3 Light load and functional test P

a) all control switches and other means to activate UPS operation

P

b) protective devices P

c) auxiliary devices, such as contactors, fans, outlets, annunciators and communication devices

P

d) supervisory, monitoring and remote signalling devices

P

e) auto transfer to stored energy mode and back to normal mode by failing and subsequently restoring the a.c. input voltage

P

f) auto transfer to bypass or isolation of the inverter from a common a.c. output bus and back to normal mode by failing and subsequently restoring the inverter a.c. output voltage

P

g) manual transfer to bypass or isolation of the inverter from a common a.c. output bus and back to normal mode by operating appropriate switches and/or controls

P

6.2.2.4 No load P

6.2.2.5 Full load P

6.2.2.6 Synchronisation P

6.2.2.7 AC input failure P

6.2.2.8 AC input return (see appended table) P

6.2.2.9 Transfer to bypass P

6.3 Site test procedure N/A

Site test shall preferably occur under conditions representing those of actual service and shall use the load available on site.

N/A

Page 13: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 13 of 54 Report No.: ES160513045S-1 Ver.1.0

The load shall not exceed the rated continuous load of the complete UPS as configured on side, or

N/A

Test performed with reference test load as defined in 3.3.5

N/A

6.4 Type test procedure (electrical) P

6.4.1 Input – a.c. supply compatibility (see appended table) P

6.4.1.1 Steady-state input voltage tolerance (see appended table) P

6.4.1.2 Input frequency tolerance (see appended table) P

6.4.1.3 Inrush current (see appended table) P

6.4.1.4 Harmonic distortion of input current (see appended table) P

6.4.1.5 Power factor (see appended table) P

6.4.1.6 Efficiency (see appended table) P

6.4.1.7 Backfeed protection See separate report. P

6.4.1.8 Residual earth current See separate report. P

6.4.1.9 Stand-by generator compatibility test P

6.4.1.10 Electromagnetic compatibility See separate report. P

6.4.2 Output-Linear load (see appended table) P

6.4.2.1 Normal mode- No load (see appended table) P

6.4.2.2 Normal mode – Full load (see appended table) P

6.4.2.3 Stored energy mode – No load (see appended table) P

6.4.2.4 Stored energy mode – Full load (see appended table) P

6.4.2.5 3-phase unbalance (see appended table) P

6.4.2.6 DC component P

6.4.2.7 Load sharing test Provided P

6.4.2.8 Output overvoltage test (see appended table) P

6.4.2.9 Periodic output voltage variation test (see appended table) P

6.4.2.10 Overload and fault clearing capability P

6.4.2.10.1 Overload – Normal mode (see appended table) P

6.4.2.10.2 Overload – Stored energy mode (see appended table) P

6.4.2.10.3 Fault clearing capability – Normal mode (see appended table) P

6.4.2.10.4 Fault clearing capability – Stored energy mode (see appended table) P

6.4.2.11 Dynamic performance P

6.4.2.11.1 Normal to stored energy mode (see appended table) P

6.4.2.11.2 Stored energy to normal mode (see appended table) P

6.4.2.11.3 Normal to bypass mode – Overload (see appended table) P

6.4.2.11.4 Step load – Normal mode (see appended table) P

6.4.2.11.5 Step load – Stored energy mode (see appended table) P

Page 14: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 14 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.11.6 Test method – linear load (see appended table) P

6.4.2.12 Simulation of parallel redundant UPS fault (see appended table) P

6.4.3 Output – Non-linear load P

Tests performed with non-linear load as defined in annex E

(see appended table) P

6.4.3.1 Normal mode – Full load (see appended table) P

6.4.3.2 Stored energy mode – Full load (see appended table) P

6.4.3.3 Dynamic performance P

6.4.3.3.1 Normal to stored energy mode (see appended table) P

6.4.3.3.2 Stored energy to normal mode (see appended table) P

6.4.3.3.3 Load step – Normal mode P

a) UPS ≤ 4.0 kVA rating N/A

b) UPS > 4.0kVA rating (see appended table) P

6.4.3.3.4 Load step –stored energy mode (see appended table) P

6.4.4 Stored and restored energy P

6.4.4.1 Stored energy time N/A

6.4.4.2 Restored energy time (to 90% capacity) N/A

6.4.4.3 Battery ripple current measurement (see appended table) P

6.4.4.4 Restart test P

6.5 Type test procedure (environment) P

6.5.1 Environment and transportation test methods See separate report. P

6.5.2 Transportation P

6.5.2.1 Shock test (See separate report) P

a) initial measurement P

b) mode of operation P

c) Tests P

d) final requirements P

e) final measurements P

6.5.2.2 Free fall test See separate report. P

a) initial measurement P

b) mode of operation P

c) test P

d) measurements during testing P

e) final requirements P

f) final measurements P

6.5.3 Storage See separate report. P

Page 15: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 15 of 54 Report No.: ES160513045S-1 Ver.1.0

a) initial measurement P

b) mode of operation P

c) tests P

d) measurements during test P

e) Final requirements P

f) Final measurements P

6.5.4 Operation See separate report. P

a) initial measurement P

b) mode of operation P

c) test P

d) measurements during testing P

e) final measurements P

f) final requirements P

6.5.5 Acoustic noise (See separate report) P

Measured when UPS operates at rated steady-state linear load under the following conditions:

P

- normal mode P

- stored energy mode P

6.6 UPS functional unit tests (where not tested as a complete UPS) N/A

6.6.1 UPS rectifier test N/A

6.6.2 UPS inverter tests N/A

6.6.3 UPS switch tests N/A

6.6.4 Stored energy / battery tests N/A

Page 16: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 16 of 54 Report No.: ES160513045S-1 Ver.1.0

5.2.1.e 5.3.2.q 6.4.2.5

TABLE: - 3-phase input, voltage unbalance

P

Description of test conditions / test construction: 1) Start the UPS in normal mode at nominal input voltage and frequency (230V/50Hz), apply balance

full linear load and unbalance linear load.

2) Voltage regulation is defined as:

3) Angle deviation is defined as:

Measured data: 1、Balance load

balance load Va Vb Vc Yv(%)<2

%

< 2.5 degree

ᇫab ᇫbc ᇫca

Ph. a=b=c 100% Linear load

224.8V 224.1V 223.1

V 0.3% 0.1 0.3 0.4

2、Unbalance load 1) Ph. a=0,b=c=100% linear load

un alan e loa Va Vb Vc Yv(%)<2

%

< 2.5 degree

ᇫab ᇫbc ᇫca

%100

)2

arccos3

cos(2

)2

arccos3

cos(2

22222

22222

caab

bccaabcaabcaab

caab

bccaabcaabcaab

V

UU

UUUUUUU

UU

UUUUUUU

Y

oo

222

1201802

arccos1

bnan

abbnanAB

UU

UUU

oo

222

1201802

arccos1

cnbn

bccnbnBC

UU

UUU

oo

222

1201802

arccos1

ancn

caancnCA

UU

UUU

Page 17: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 17 of 54 Report No.: ES160513045S-1 Ver.1.0

Ph. a=0 67%Linear load

225.9V 225.2V 224.9

V 0.1% 0.0 0.3 0.3

2) Ph. b=0,a=c=100% linear load

unbalance load Va Vb Vc Yv(%)<2

%

< 2.5 degree

ᇫab ᇫbc ᇫca

Ph. b=0 67%Linear loa

226.3V 225.9V 22 .2

V 0.1% 0.2 0.4 0.2

Page 18: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 18 of 54 Report No.: ES160513045S-1 Ver.1.0

3) Ph. c=0,a=b=100% linear load

unbalance load Va Vb Vc Yv(%)<2

%

< 2.5 degree

ᇫab ᇫbc ᇫca

Ph. c=0 67%Linear load

226.4V 225.6V 225.4

V 0.2% 0.3 0.2 0.5

Page 19: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 19 of 54 Report No.: ES160513045S-1 Ver.1.0

6.2.2.8 6.4.1.3 6.4.2.11.2

TABLE: - AC input return - Inrush current - Change of operating mode – Stored energy to normal mode

P

Description of test conditions / test construction: 1. AC input return 1) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. A few seconds later, return AC input, UPS transfer to normal again. 2) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. 3) A few seconds later, return AC input with improper phase rotation, UPS can't transfer to normal and alarm "Rectifier Phase. 4) Then cut off input, and return AC input with proper phase rotation, UPS transfer to normal again. 2. Inrush current 1) Input &bypass supply at 187V/230V/264V 50Hz and battery off. analysis the inrush input current for the following cases: 2) When Vbus didn’t drop, turn on common line &bypass and battery at the moment that the input voltage is 0V first and Vmax , record the inrush current, and then turn on the system, record the inrush current again. 3) Test results: inrush current ≤120% of rated current for ≤2 cycles.

Remark Channel 1 - Output Current Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase A Channel 4 - Input Voltage Phase A

Measured graph: 1) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. A few seconds later, return AC input, UPS transfer to normal again.

2) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. A few seconds later, return AC input with improper phase rotation, UPS can't transfer to normal and alarm "Rectifier Phase Rotation Failed". Then cut off input, and return AC input with proper phase rotation, UPS transfer to normal again.

2. Inrush current < 2.5X 1)Vbus=0 input voltage=187V Inrush current=23A 2)Vbus>0 input voltage=187V Inrush current=22A

Page 20: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 20 of 54 Report No.: ES160513045S-1 Ver.1.0

3)Vbus=0 input voltage=230V Inrush current=21A 4)Vbus>0 input voltage=230V Inrush current=23A 5)Vbus=0 input voltage=272V Inrush current=20A 6)Vbus>0 input voltage=272V Inrush current=22A

Page 21: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 21 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.1.4 TABLE: -Harmonic distortion of input current P

Description of test conditions / test construction: 1) The harmonic distortion of the input current is tested at reference test load. 2) Test result THDi < 35%

Load(%) Harmonic No.

Phase 1 (dB)

Phase 2 (dB)

Phase 3 (dB)

-

99% 3 2 1 1 -

5 66 67 67 -

7 10 11 10 -

9 1 0 0 -

THD Distortion at phase 1

Distortion at phase 2

Distortion at phase 3

Expected value due to the specification of the manufacturer

-

See formula to THD below(100% load)

28.8% 28.8% 29.0% 35%

-

2

20

92

20

72

20

52

20

3

10101010100

THD

Page 22: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 22 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.1.5 & 6.4.1.6

TABLE: - Input power factor - Efficiency-Normal Mode

P

Description of test conditions / test construction: 1) UPS run in normal mode, charge off. The UPS efficiency shall be measured at 25%, 50%, 75% and 100% reference load. Input power factor = 0.999

Load (%)

Efficiency Input Power (KW)

Output Power (KW)

Expected value due to the specification of the manufacturer

Verdict

25 90.2% 28.6K 25.8K 82.5% P

50 92.5% 55.0K 50.9K 87.5% P

75 92.3% 79.8K 73.7K 89.1% P

100 90.94% 128K 116.4K 88.8% P

6.4.2.1 TABLE: - Output – Linear load: Normal mode – No load - Harmonic components measurement

P

Description of test conditions / test construction: 1)With the UPS operating in normal mode of operation at no load and nominal input voltage and frequency, measure the r.m.s. output voltage and its fundamental and harmonic components.

Load (%)

Harmonic No.

Phase 1 (dB)

Phase 2 (dB)

Phase 3 (dB)

-

0 3 0.1 0.2 0.1 -

5 0.2 0.3 0.3 -

7 0.1 0.1 0.1 -

9 0.0 0.0 0.1 -

THD Distortion at phase 1

Distortion at phase 2

Distortion at phase 3

Expected value due to the specification of the manufacturer

-

see formula to THD below

0.3% 0.4% 0.4% < 1% -

Page 23: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 23 of 54 Report No.: ES160513045S-1 Ver.1.0

2

20

92

20

72

20

52

20

3

10101010100

THD

6.4.2.2 TABLE: - Output – Linear load: Normal mode – Full load Harmonic components measurement

P

Description of test conditions / test construction: 1)UPS runs in normal mode, applying 100% reference test load to the UPS output, then measure output voltage and its fundamental and harmonic components.

Load (%)

Harmonic No.

Phase 1 (dB)

Phase 2 (dB)

Phase 3 (dB)

-

100 3 0.1 0.2 0.2 -

5 0.4 0.3 0.4 -

7 0.3 0.3 0.2 -

9 0.1 0.1 0.1 -

THD Distortion at phase 1

Distortion at phase 2

Distortion at phase 3

Expected value due to the specification of the manufacturer

-

see formula to THD below

0.6% 0.5% 0.6% < 1% -

2

20

92

20

72

20

52

20

3

10101010100

THD

Page 24: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 24 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.3 TABLE: - Output – Linear load: Stored energy mode – No load - Harmonic components measurement

P

Description of test conditions / test construction: 1)With the UPS operating in battery mode of operation at no load, measure the r.m.s. output voltage and its fundamental and harmonic components.

Load (%)

Harmonic No.

Phase 1 (dB)

Phase 2 (dB)

Phase 3 (dB)

-

0 3 0.1 0.1 0.1 -

5 0.2 0.2 0.3 -

7 0.1 0.1 0.1 -

9 0.0 0.0 0.0 -

THD Distortion at phase 1

Distortion at phase 2

Distortion at phase 3

Expected value due to the specification of the manufacturer

-

see formula to THD below

0.4% 0.4% 0.4% < 1% -

2

20

92

20

72

20

52

20

3

10101010100

THD

6.4.2.4 TABLE: - Output – Linear load: Stored energy mode – Full load Harmonic components measurement

P

Description of test conditions / test construction: 1)UPS runs in battery mode, applying 100 % reference test load to the UPS output, then measure output voltage and its fundamental and harmonic components.

Load (%)

Harmonic No.

Phase 1 (dB)

Phase 2 (dB)

Phase 3 (dB)

-

100 3 0.1 0.2 0.2 -

5 0.4 0.3 0.4 -

7 0.3 0.3 0.2 -

Page 25: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 25 of 54 Report No.: ES160513045S-1 Ver.1.0

9 0.1 0.1 0.1 -

THD Distortion at phase 1

Distortion at phase 2

Distortion at phase 3

Expected value due to the specification of the manufacturer

-

see formula to THD below

0.6% 0.5% 0.6% < 1% -

2

20

92

20

72

20

52

20

3

10101010100

THD

Page 26: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 26 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.10.1 TABLE: Overload capability test – Normal mode P

Description of test conditions / test construction: 1) UPS in normal mode, apply below loads respectively to the output, check UPS performance

and alarms. 2) Measure the overload time duration, check UPS transfer to bypass and transfer back to

normal mode automatically if removing overload.

Condition Specs

30C ambient, 1000m, nominal Uin

Overloads

105 - 125% 10 minutes

126-150% 1 minute

>150%, 200ms

Load/(%) Specified time interval Verdict

107% 615.17s P

128% 60.76s P

154% 238.4ms P

Measured data: 1) 107% linear load overload time=615.17s

2) 128% linear load overload time=60.76s

Page 27: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 27 of 54 Report No.: ES160513045S-1 Ver.1.0

3) 154% linear load overload time=238.4ms

Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B

Page 28: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 28 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.10.2 TABLE: Overload capability test – Stored energy mode P

Description of test conditions / test construction: 1) UPS in battery mode, apply below loads respectively to the output, check UPS performance and

alarms. 2) Measure the overload time duration, check UPS transfer to bypass and transfer back to battery mode

automatically if removing overload.

Condition Specs

30C ambient, 1000m, nominal Uin

Overloads

105 - 125% 10minutes

126-150% 1minutes

>150%, 200ms

Load/(%) Specified time interval Verdict

107% 613.79s P

128% 60.96s P

154% 220.4ms P

Measured data: 1)107% linear load overload time=613.79s

2)128% linear load overload time=60.96s

Page 29: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 29 of 54 Report No.: ES160513045S-1 Ver.1.0

3)154% linear load overload time=220.4ms

Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B

Page 30: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 30 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.10.3 TABLE: - Fault clearing capability – Normal mode - Short circuit test

P

Description of test conditions / test construction: 1) UPS operating in normal mode, applying 50% linear load. Input and output both are 240V/50Hz. 2) Then make output shorted, check UPS response. UPS should shut down and alarm "Inverter Output

Over Current" 3) Then remove the shorted circuit; Reset alarms, "Inverter Output Over Current" will be cleared. 4) Turn UPS on, UPS run in normal mode again.

Measured graph:

1) Output shorted, UPS shut down and alarm "Inverter Output Over Current", remove shorted circuit and reset alarm, alarm "Inverter Output Over Current" cleared, turn on UPS to normal mode.

Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B

Page 31: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 31 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.10.4 TABLE: - Fault clearing capability – Stored energy mode - Short circuit test

P

Description of test conditions / test construction: 1) UPS operating in battery mode, applying 50% linear load. Output is 240V/50Hz. 2) Then make output shorted, check UPS response. UPS should shut down and alarm "Inverter Output

Over Current". 3) Then remove the shorted circuit; Reset alarms , "Inverter Output Over Current" will be cleared. 4) Turn UPS on, UPS run in battery mode again.

Measured graph: Output shorted, UPS shut down and alarm "Inverter Output Over Current", remove shorted circuit and reset alarm, alarm "Inverter Output Over Current" cleared, turn on UPS to battery mode.

Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B

Page 32: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 32 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.11.1 TABLE: - Change of operating mode – Normal to stored energy mode - AC input failure test

P

Description of test conditions / test construction: 1) UPS initially operating at full linear load in normal mode, the input supply shall be interrupted, then

UPS transfers to battery mode. 2) Check the system when the utility failure normal operation. Measure the transient output voltage

deviation.

Power Type

Response procedure

Before After deviation < 5%

A B C A B C

deviation

Phase A

deviation Phase

B

deviation Phase

C

230V/50Hz

Normal to Battery

220.981 219.421 219.434 220.931 219.605 219.330 0.02% 0.08% 0.05%

Measured graph: Before waveform After waveform

Channel 1 - Output Voltage Phase A

Channel 2 - Input Current Phase A

Channel 3 - Output Voltage Phase C

Channel 4 - Output Voltage Phase B

Page 33: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 33 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.11.3 TABLE: - Change of operating mode – Normal to bypass mode - Overload test

P

Description of test conditions / test construction: 1) UPS has a bypass mode of operation which is automatic in operation under conditions of output

overload. 2) The input and output voltage waveforms shall be observed during transitions normal to bypass

mode.

Measured graph: Load transfer from inverter to mains

Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B

Page 34: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 34 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.2.11.4 TABLE: - Step load –Normal mode P

Description of test conditions / test construction: 1) Impact linear load as defined 20% => 100 %=> 20% nominal load with 230V/50Hz in normal mode. 2) Check the transient response

Measured graph: 1) Step load from 20% to 100% linear load

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

230V/50Hz

20% to 100% load

220.766 219.567

219.437 213.836 212.221

212.870 3.15% 3.34% 2.99%

2) Step load from100% down to 20% linear load

Page 35: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 35 of 54 Report No.: ES160513045S-1 Ver.1.0

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

230V/50Hz

100% to 20% load

221.081 219.087

221.407 226.824 225.396

226.023 2.61% 2.88% 2.10%

Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B

6.4.2.11.5 TABLE: - Step load – Stored energy mode P

Description of test conditions / test construction: 1) Impact linear load as defined 20% => 100 %=> 20% nominal load with 230V/50Hz in battery mode. 2) Check the transient response

Measured graph: 1) Step load from 20% to 100% linear load

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

230V/50Hz

0 to 100% load

220.732 219.642

219.456 214.148 212.993

212.975 3.00% 3.02% 2.95%

2) Step load from100% down to 20% linear load

Page 36: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 36 of 54 Report No.: ES160513045S-1 Ver.1.0

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

230V/50Hz

100% to 0 load

221.095 219.547

222.272 226.652 225.534

225.865 2.53% 2.72% 1.63%

Channel 1 - Output Voltage Phase A

Channel 2 - Input Current Phase A

Channel 3 - Output Voltage Phase C

Channel 4 - Output Voltage Phase B

6.4.3.1 TABLE: - Output – Non-linear load: Normal mode – Full load - Harmonic components measurement

P

Description of test conditions / test construction: UPS runs in normal mode, applying 100 % non-linear load to the UPS output, then measure output voltage and its fundamental and harmonic components.

Load (%)

Harmonic No.

Phase 1 (dB)

Phase 2 (dB)

Phase 3 (dB)

-

100 3 2.4 2.4 2.3 -

5 3.8 3.9 3.8 -

7 1.1 1.2 1.1 -

9 0.7 0.7 0.6 -

THD Distortion at phase 1

Distortion at phase 2

Distortion at phase 3

Expected value due to the specification of the manufacturer

-

see formula to THD below

5.0% 5.1% 4.9% < 8% -

Page 37: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 37 of 54 Report No.: ES160513045S-1 Ver.1.0

2

20

92

20

72

20

52

20

3

10101010100

THD

6.4.3.2 TABLE: - Output – Non-linear load: Stored energy mode – Full load - Harmonic components measurement

P

Description of test conditions / test construction: UPS runs in battery mode, applying 100 % non-linear load to the UPS output, then measure output voltage and its fundamental and harmonic components.

Load (%)

Harmonic No.

Phase 1 (dB)

Phase 2 (dB)

Phase 3 (dB)

-

100 3 2.5 2.4 2.2 -

5 3.8 3.8 3.9 -

7 1.1 1.1 1.1 -

9 0.7 0.7 0.6 -

THD Distortion at phase 1

Distortion at phase 2

Distortion at phase 3

Expected value due to the specification of the manufacturer

-

see formula to THD below

5.0% 5.0% 4.9% < 8% -

Page 38: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 38 of 54 Report No.: ES160513045S-1 Ver.1.0

2

20

92

20

72

20

52

20

3

10101010100

THD

Measured graph:

Page 39: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 39 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.3.3.1

TABLE: - Reference non-linear load – Normal to stored energy mode - AC input failure test

P

Description of test conditions / test construction: 1) UPS initially operating at full non-linear load in normal mode, the input supply shall be interrupted,

then UPS transfers to battery mode; 2) Check the system when the utility failure normal operation. Measure the transient output voltage

deviation.

Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

230V/50Hz

Normal to Battery

221.026 219.557 218.738 221.100 219.317 218.740 0.03% 0.01% 0.08%

Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B

Page 40: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 40 of 54 Report No.: ES160513045S-1 Ver.1.0

Page 41: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 41 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.3.3.2 TABLE: - Reference non-linear load – Stored energy to normal mode P

Description of test conditions / test construction: 1) UPS initially operating at full non-linear load in battery mode, the input supply shall be recovery, then

UPS transfers to normal mode, 2) Check the system when the utility response normal operation. Measure the transient output voltage

deviation.

Measured graph: Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

230V/50Hz

Normal to Battery

221.642 219.909 218.937 221.548 219.828 218.846 0.04% 0.04% 0.04%

Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B

Page 42: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 42 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.3.3.3.b TABLE: - Reference non-linear load steps – Normal mode > 4.0 kVA rating P

Description of test conditions / test construction: 1) Impact linear load as defined 33 %=> 66%=100 %=> 66 %=> 33% non-linear load with 230V/50Hz in

normal mode. 2) Check the transient response.

Measured graph: 1) Step load from 33% up to 66% non-linear load

Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

220V/50Hz

33%=>66% load

221.434 220.270 219.286 218.735 215.311 218.876 1.23% 2.25% 0.19%

2) Step load from 66% up to 100% non-linear load

Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

Page 43: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 43 of 54 Report No.: ES160513045S-1 Ver.1.0

220V/50Hz

66%=100% load

221.425 220.428 219.406 218.633 214.534 215.290 1.27% 2.68% 1.87%

3) Step load from100% down to 66% non-linear load Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

220V/50Hz

100%=66% load

221.594 220.195 219.223 223.389 221.496 220.669 0.82% 0.59% 0.66%

4) Step load from 66% down to 33% non-linear load Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

220V/50Hz

66%=33% load

221.660 220.140 219.032 222.477 220.820 220.086 0.37% 0.31% 0.48%

Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B

Page 44: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 44 of 54 Report No.: ES160513045S-1 Ver.1.0

6.4.3.3.4 TABLE: - Reference non-linear load steps – Stored energy mode > 4.0 kVA rating

P

Description of test conditions / test construction: test repeated according to sub-clause 6.4.3.3.3.b 1) Impact linear load as defined 33 %=> 66%=100 %=> 66 %=> 33% non-linear load with 230V/50Hz in

battery mode. 2) Check the transient response

Measured graph: 1) Step load from 33% up to 66% non-linear load

Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

220V/50Hz

33%=66% load

221.877 219.814 219.081 217.753 215.205 212.038 1.87% 2.10% 3.20%

2)Step load from 66% up to 100% non-linear load

Before waveform After waveform

Power Respons Before After deviation < 5%

Page 45: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 45 of 54 Report No.: ES160513045S-1 Ver.1.0

Type e procedure

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

220V/50Hz

66%=100% load

220.484 219.230 217.893 211.551 217.846 212.653 4.1% 0.63% 2.38%

3) Step load from100% down to 66% non-linear load Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

220V/50Hz

100%=66% load

222.014 220.009 219.407 222.705 221.428 220.352 0.19% 0.65% 0.43%

4) Step load from 66% downto 33% non-linear load Before waveform After waveform

Power Type

Response procedure

Before After deviation < 5%

A B C A B C deviation Phase

A

deviation Phase

B

deviation Phase

C

220V/50Hz

100%=66% load

221.589 220.002 219.153 222.842 221.480 220.415 0.57% 0.67% 0.57%

Page 46: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 46 of 54 Report No.: ES160513045S-1 Ver.1.0

Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B

Page 47: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 47 of 54 Report No.: ES160513045S-1 Ver.1.0

TABLE: List of critical components P

Object/part no. Manufacturer/ trademark

Type/model Technical data Standard Mark(s) of conformity 1.

Whole unit

Enclosure Various Steel/Aluminium

-- -- --

LCD Display SHENZHEN TOPWAY TECHNOLOGY CO.,LTD.

LM2088DFW-C

HB, 80℃ -- --

Breaker (AC INPUT)

LS Industrial System Co.,Ltd

ABE203b,3P 250A (LS)

415V,250A IEC 60947-2 Intertek CB Certif. No.: CN10817

Breaker (OUTPUT)

LS Industrial System Co.,Ltd

ABE203b,3P 250A (LS)

415V,250A IEC 60898-1 Intertek CB Certif. No.: CN10817

Breaker

(MCCB)

LS Industrial System Co.,Ltd

ABE203b,3P 250A (LS)

415V,250A IEC 60898-1 Intertek CB Certif. No.: CN10817

Internal wire (AC)

Dongguan XIN RU Hardware Electronic Co. Ltd.

600227 IEC02(RV)25mm2,450/750V

450/750V,70℃ UL UL: E304337

Internal wire (DC)

Dongguan XIN RU Hardware Electronic Co. Ltd.

600227 IEC02(RV)25mm2,450/750V

450/750V,70℃ UL UL: E304337

Inverter Capacitor

EACO SRE-300-400-MSJ 400UF 300V 65A EACO

400uF±5%,300VAC,105℃

-- Test with appliance

IGBT infineon IGBT module,FF450R07ME4,650V,450A

650V,450A -- --

SCR SKKT SKKT 106/16E

106A,1600V UL UL: E63532

Input Inductor Guang hua industrial co.,ltd

EA89Ⅱ-120KVA 0.4mH 265A

130℃ -- Test with appliance

Transformer Guang hua industrial co.,ltd

EA89Ⅱ-120K 200:415 120KVA

Class H insulation

180℃

-- Test with appliance

Page 48: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 48 of 54 Report No.: ES160513045S-1 Ver.1.0

AC fan SANJU ELECTRIC MACHINERY CO.,LTD

SJ1755HA2 BAL-(WZ)

AC220-240V,

0.18A

CE

UL

CE: N8A150268837 008

UL: E314698

Fuse MUSSMANN 170M5412 630A 690V

630A,690V IEC 60269-4 CQC CB Certif. No.: CN13985

Fuse HOLLYLAND CO LTD

61NM 6A,250V UL

KC

UL: E156471

KC: SU05008-4001B

Fuse HOLLYLAND CO LTD

65NM 5A,250V UL

KC

UL: E156471

KC: SU05008-4001B

SMPS(AUX-POWER-C2),

PCB Various Various V-0, 130℃ -- UL: E230225

X-Capacitor (C17)

Xiamen Faratronic Co., Ltd.

C42P2225KBSC400

X1, 275VAC,2.2uF IEC 60384-14 VDE:DE1-49862

KC: SU03060-12004

Y-Capacitor (C5, C6)

Xiamen Faratronic Co., Ltd.

C43Q1224MB0C400

Y-Cap, 300VAC,0.22uF

IEC 60384-14 VDE: SE-60440

KC: SU03060-12005

Inductor (L1)

JEPULS TECHNOLOGY(SHENZHEN) CO.,LTD

LC9-116 130℃ -- Test with appliance

Transformer (T1)

SHENZHEN FERROCOIL

ER42 CLASS B -- Test with appliance

-BOBBIN CHANG CHUN PLASTICS CO.,LTD

T375J -- UL 94V-0 UL: E59481(S)

-WIRE PACIFIC ELECTRIC WIRE & CABLE CO.,LTD

UEW-U 130℃ UL UL: E201757(S)

-TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY

PZ 130℃ UL UL: E165111(N)

-VARNISH HANG CHEUNG PETROCHEMICAL LTD

8562/C -- UL UL: E200154

Page 49: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 49 of 54 Report No.: ES160513045S-1 Ver.1.0

-TUBE FLUO TECH INDUSTRIES CO.,LTD

TEFLON TUBE

-- UL UL: E175982(N)

-MARGIN TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY

WF 130℃ UL UL: E165111(N)

Transformer (T3)

SHENZHEN FERROCOIL

EEL16 CLASS B -- Test with appliance

-BOBBIN CHANG CHUN PLASTICS CO.,LTD

T375J -- UL 94V-0 UL: E59481(S)

-WIRE PACIFIC ELECTRIC WIRE & CABLE CO.,LTD

UEW-U 130℃ UL UL: E201757(S)

-TAPE SHENGDAFENG ELECTRONICS CO., LTD

PZ 130℃ UL UL: E317896

-VARNISH HANG CHEUNG PETROCHEMICAL LTD

8562/C -- UL UL: E200154

-TUBE FLUO TECH INDUSTRIES CO.,LTD

TEFLON TUBE

-- UL UL: E175982(N)

-MARGIN TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY

WF 130℃ UL UL: E165111(N)

Opto-coupler (IS1)

TOSHIBA TLP781-BL Dti>0.4mm, 115℃ min.

UL

VDE

UL:E67349

VDE :40021173

3PH Interface PCB(GF_INTERFACE),

Relay

(RL1, RL2, RL3, RL4, RL5, RL6)

Xiamen Hongfa Electronics Sales Co.

HFD27 60W,120VA UL UL: E133481

PCB Various Various V-0, 130℃ UL UL: E230225

<Inverter Drive PCB>(EA990Ⅱ_IGBTDR_D1)

Page 50: ES160513045S-1 Report IEC 62040-3

IEC 62040-3

Clause Requirement + Test Result - Remark Verdict

TRF No. IEC62040_3B Page 50 of 54 Report No.: ES160513045S-1 Ver.1.0

Transformer JEPULS TECHNOLOGY(SHENZHENG)CO.,LTD

Switch Power Transformer,E3HP-IGBT-T1-27:27:20-0.510mH-+/-30%-PG232

130℃ -- --

PCB Various Various V-0, 130℃ UL UL: E230225

<3PH SCR PCB>(REC-SCR-Drive)

Transformer Shenzhen Feiyue Electronic Technology Co., Ltd.

Driver Transformer,E3HPPT2,22:22:22,300uH

130℃ -- --

PCB Various Various V-0, 130℃ UL UL: E230225

CNTL BOARD(Main_Control-C1)

TRANSFOMER SHENZHEN FERROCOIL

EE16 CLASS B -- Test with appliance

-BOBBIN CHANG CHUN PLASTICS CO.,LTD

T375J -- UL 94V-0 UL: E59481(S)

-WIRE PACIFIC ELECTRIC WIRE & CABLE CO.,LTD

UEW-U 130℃ UL UL: E201757(S)

-TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY

PZ 130℃ UL UL: E165111(N)

-VARNISH HANG CHEUNG PETROCHEMICAL LTD

8562/C -- UL UL: E200154

Opto-coupler (IS1)

LITE-ON TECHNOLOGY CORP.

LTV-816S-TA1(C)

Dti>0.4mm, 110℃ min.

UL UL:E113898

PCB Various Various V-0, 130℃ UL UL: E230225

Supplementary information:

An asterisk indicates a mark that assures the agreed level of surveillance.

Page 51: ES160513045S-1 Report IEC 62040-3

Pictures

TRF No. IEC62040_3B Page 51 of 54 Report No.: ES160513045S-1 Ver.1.0

Fig. 1 –Overview I

Page 52: ES160513045S-1 Report IEC 62040-3

Pictures

TRF No. IEC62040_3B Page 52 of 54 Report No.: ES160513045S-1 Ver.1.0

Fig. 2 –Overview II

Page 53: ES160513045S-1 Report IEC 62040-3

Pictures

TRF No. IEC62040_3B Page 53 of 54 Report No.: ES160513045S-1 Ver.1.0

Fig. 3 –Overview III

Page 54: ES160513045S-1 Report IEC 62040-3

Pictures

TRF No. IEC62040_3B Page 54 of 54 Report No.: ES160513045S-1 Ver.1.0

Fig. 4 –Overview IIII