es160513045s-1 report iec 62040-3
TRANSCRIPT
TRF No. IEC62040_3B Page 1 of 54 Report No.: ES160513045S-1 Ver.1.0
TEST REPORT IEC 62040-3
Uninterruptible power systems Part 3: Method of specifying the performance and test requirements
Report Number. .............................. : ES160513045S-1
Date of issue ................................... : Sep. 03, 2018
Total number of pages ................... 54 pages
Applicant’s name ........................... : EAST Group Co., Ltd.
Address ........................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industrial Park, Dongguan City, Guangdong Province, China
Test specification:
Standard .......................................... : IEC 62040-3 (Second Edition): 2011
Test procedure ............................... : Compliance with IEC 62040-3 (Second Edition): 2011
Non-standard test method………..: N/A
Test Report Form No. .................... : IEC62040_3B
Test Report Form(s) Originator .... : Electrosuisse
Master TRF ...................................... : Dated 2011-08
Copyright © 2011 Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
Test item description ..................... : Uninterruptible Power Supply
Trade Mark ...................................... : EAST
Manufacturer .................................. : EAST Group Co., Ltd. No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industrial Park, Dongguan City, Guangdong Province, China
Model/Type reference .................... : 50kVA, 60kVA, 80kVA,100kVA,120kVA
Ratings ............................................ : See marking plate
TRF No. IEC62040_3B Page 3 of 54 Report No.: ES160513045S-1 Ver.1.0
List of Attachments (including a total number of pages in each attachment): Attachment No. 1: 4 pages of photograph.
Summary of testing:
Tests performed (name of test and test clause): The submitted samples were found to comply with the requirements of: IEC 62040-3 (Second Edition):2011
Testing location: EMTEK (SHENZHEN) CO., LTD. Bldg 69, Majialong Industry Zone, Nanshan District, Shenzhen, Guangdong, China
Summary of compliance with National Differences
National differences and Group differences as per CB bulletin.
The product fulfils the requirements of IEC 62040-3 (Second Edition):2011
TRF No. IEC62040_3B Page 4 of 54 Report No.: ES160513045S-1 Ver.1.0
Copy of marking plate The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks.
Model: 50kVA MODEL: 60kVA
MODEL: 80kVA MODEL: 100kVA
MODEL: 120kVA
TRF No. IEC62040_3B Page 5 of 54 Report No.: ES160513045S-1 Ver.1.0
Test item particulars .................................................. :
Classification of installation and use ...................... : [] movable [] hand-held [] transportable [X] stationary [] for building-in [] direct plug-in
Supply Connection ..................................................... : [] pluggable equipment [] type A [] type B [X] permanent connection [] detachable power supply cord [] non-detachable power supply cord [] not directly connected to the mains [] built-in component, consider in end system
Operating condition ................................................... : [X] continuous [] rated operating / resting time:
Possible test case verdicts:
- test case does not apply to the test object ........... : N/A
- test object does meet the requirement ................. : P (Pass)
- test object does not meet the requirement .......... : F (Fail)
Testing ......................................................................... :
Date of receipt of test item ........................................ : N/A
Date (s) of performance of tests ............................... : N/A
General remarks:
The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a comma / point is used as the decimal separator.
Manufacturer’s Declaration per sub-clause 6.2.5 of IECEE 02:
The application for obtaining a CB Test Certificate includes more than one factory location and a declaration from the Manufacturer stating that the sample(s) submitted for evaluation is (are) representative of the products from each factory has been provided ....................................................... :
Yes Not applicable
When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : Same as manufacturer
TRF No. IEC62040_3B Page 6 of 54 Report No.: ES160513045S-1 Ver.1.0
General product information: This report is amended from previous report ES160513045S, issued on Aug. 05, 2016, due to below amendments. - Updated date of issue. No any tests need be considered. The equipment is on-line type uninterruptible power supply with step-sinewave o/p (line mode and battery mode) for general supply of office equipment.
Model difference:
All models have the same constructions, circuit diagram and PCB layout. Only model name, appearance and the parameter of some parts are different. All tests were performed on model 120KVA which means the typical model.
The maximum operating temperature is 40C, Relative humidity 5 to 95%, no condensation allowed, ambient storage temperature range of -15 to +55C in the protective package.
Operating altitude up to 2000m above sea level.
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 7 of 54 Report No.: ES160513045S-1 Ver.1.0
5 ELECTRICAL SERVICE CONDITIONS AND PERFORMANCE --
5.1 General P
5.1.1 UPS configuration P
- quantity of UPS units and their topology P
- Redundancy configuration as applicable P
- Any mayor UPS switch P
- operator access or restricted access classification in accordance with IEC 62040-1
See separate safety report. P
5.1.2 Markings and Instructions P
Marked and supplied with adequate instruction for the installation and operation of the UPS and its controls and indications
All required markings are affixed on labels located on the enclosure of UPS.
P
Markings and instructions in accordance with sub-clause 4.7 of IEC 62040-1
See separate safety report. P
5.1.3 Safety complies with the safety requirements of UPS prescribed in IEC 62040-1
See separate safety report. P
5.1.4 Electromagnetic compatibility complies with the requirements of IEC 62040-2
Emission and immunity comply with IEC 62040-2 C3, see separate report
P
5.2 UPS input specification P
5.2.1 Conditions for normal mode operation P
a) rated voltage 380/400/415V at 100% load. P
b) r.m.s. voltage variation ±25%, at 100% load P
c) rated frequency 50Hz/60Hz P
d) frequency variation ±2Hz P
e) for three phases input, voltage unbalance with an unbalance ratio of 5%
(see appended table 6.2.2.7) P
f) total harmonics distortion (THD) of voltage, according to IEC 61000-2-2
P
g) transient voltage; within the electromagnetic immunity levels prescribed in IEC 62040-2
P
5.2.2 Characteristics to be declared by the manufacturer P
a) number of phases 3 phases P
b) neutral requirements With neutral P
d) power factor at rated current 0.9pf at 100% load P
e) inrush current characteristics ≤100% of rated current for ≤1 cycles.
P
f) maximum continuous current at the worst-case condition
Maximum 303A at Normal condition, Maximum 272.7A at bypass condition.
P
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 8 of 54 Report No.: ES160513045S-1 Ver.1.0
g) overload current Maximum 40A at Normal condition, Maximum 60A at bypass condition.
P
h) total harmonic distortion (THD) of current <35% P
i) minimum short current power capacity; in compliance with: - IEC 61000-3-2 (UPS ≤16A) - IEC 61000-3-12 (16A < UPS ≤75A) - IEC 61000-3-4 (UPS > 75A)
>75A P
j) earth leakage current characteristics Maximum Earth leakage < 5% of nominal input current rating.
P
k) a.c. power distribution system compatibility TN, TT or IT):
TN, TN-S, TN-C, TN-C-S, TT (Three-phase, four-wire + PE).
P
5.2.3 Characteristics and conditions to be identified by the purchaser P
a) pre-existing harmonic voltage distortion when of 75% of IEC 61000-2-2 compatibility level at the intended point of coupling of the UPS
Provided P
b) requirements for compatibility with the characteristics of protective devices of the UPS input supply
REC input switch, bypass input switch,output switch,maintenance switch and battery switch are optional parts.
P
c) requirements for all-pole isolation P
d) stand-by generator characteristics Compatible with generator of rating typically >2x UPS kW.
P
5.3 UPS output specification P
5.3.1 Conditions for the UPS to supply a load P
- the input conditions of 5.2.1 being satisfied, or P
- the energy storage system being available P
5.3.2 Characteristics to be declared by the manufacturer P
a) performance classification in accordance with 5.3.4
P
b) rated voltage and steady state variation AC380/400/415V, ±1% Balanced static load, ±6% with 5ms recovery from 10% to 90% load step, ±5% Balanced dynamic load for normal mode, ±0.1Hz (single module), ±0.1Hz (Parallel system) for Stored Energy Mode
P
c) rated frequency and free running variation 40-70Hz P
d) maximum frequency range 40-70Hz P
e) rate of change of frequency when synchronizing 2Hz/s P
f) number of phases available 3 phases P
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 9 of 54 Report No.: ES160513045S-1 Ver.1.0
g) neutral availability With neutral P
h) a.c. power distribution system compatibility: TN, TN-S, TN-C, TN-C-S, TT (Three-phase, four-wire + PE).
P
i) total harmonic distortion (THD) of voltage (at linear and non-linear load as specified in annex E):
P
- in normal mode <1% with linear load, 5% with non-linear load
P
- in stored energy mode <1% (Across a linear load); 5% (Across a non-linear load)
P
j) output voltage transient deviation Vrms L-L or L-N <5% transient overshoot, 20ms recovery time
P
k) rated active and apparent output power and rated current
AC380/400/415V, 181.8A/173.9A/166.7A 120KW
P
l) overload capability 105–110% load 60 minutes, 110–125% load 10 minute, 125–150% load 1 minute, 150–200% load 200m sec, >200% load after 100ms,Change to bypass
P
m) current limit identification 1.25X rating current P
n) fault clearing capability Through upstream breaker or fusing for BYPASS. Through fusing and breaker for Rectifier.
P
o) rated load power factor 0.9 P
p) permissible displacement power factor range of the load (cos. Φ)
0.9 lagging to 0.9 leading with de-rating.
P
q) voltage unbalance and phase angle displacement <2 deg. P
e) UPS efficiency at 25%, 50%, 75% and 100% reference test load
90.2% 92.5% 92.3% 90.94% P
5.3.3 Characteristics and conditions to be identified by the purchaser P
a) loads generating harmonic currents (max. levels permitted in IEC 61000-3-2, /-12/ -4)
Provided P
b) asymmetric loads requiring circulation of a d.c. current
Provided P
c) independent earth of the neutral required Provided P
d) load distribution facilities Provided P
e) requirements of all-pole isolation Provided P
f) requirements for coordination with characteristics of protective devices
Provided P
g) future extension/expansion requirements Provided P
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 10 of 54 Report No.: ES160513045S-1 Ver.1.0
h) stand-by generator characteristics Compatible with generator of rating typically >1,5x UPS kW.
P
i) functional availability and degree of redundancy Provided P
j) output overvoltage protection Provided P
5.3.4 Performance classification P
UPS complying with this standard in accordance with the coding: AAA BB CCC
P
AAA = Input dependency characteristic VFI P
BB = Voltage waveform characteristic SS P
CCC = Dynamic output performance 111 P
5.4 Stored energy specification P
5.4.1 General See technical specification P
5.4.2 Battery P
5.4.2.1 Requirements for all batteries See separate safety report. P
5.4.2.2 Characteristic to be declared by the manufacturer P
a) life 5 or 10 years(depends) P
b) quantity of blocks or cells and of paralleled strings
28 blocks, 168 cells per battery string or 29 blocks, 174 cells per battery string or 30 blocks, 180 cells per battery string (default)or 32 blocks, 192 cells per battery string .
P
c) nominal voltage of total battery 336V (168 Cells) or 348V (174 Cells) or 360V (180 Cells, Default)or 384V (192 Cells).
P
d) battery technology Boost/buck. P
e) nominal capacity of total battery Depend on battery size. N/A
f) stored energy time Depend on battery size. N/A
g) restored energy time Restored energy time to 90%: Maximum 10 hours recommended (depend on battery size).
P
h) ambient reference temperature Battery (installed separately): +5 to +25 battery life.
P
i) earth condition of d.c. link/isolation P
j) r.m.s. ripple current during normal mode (see appended table) P
k) nominal discharge current during stored energy mode
DC450Vmax, 133Amax. P
l) d.c. fault current rating P
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 11 of 54 Report No.: ES160513045S-1 Ver.1.0
m) cable voltage drop recommendation <1% of nominal DC voltage at rated battery current.
P
n) protection requirements DC input breaker or fuse. P
o) charging regime Advanced Battery Management (ABM®) = 90% resting,10% floating/charging (typical).
P
p) charging voltage and tolerance band Float charge voltage : 168/174/180/192 x 1.67V = 381/395/408/435V
P
q) end of discharge voltage Maximum charge voltage: 216/228/240 x 2.35V = 508/536/564V 1.67V/Cell
P
r) charging current limit or range Charging current (at full load) 10A
P
5.4.2.3 Characteristics and conditions to be identified by the purchaser P
5.5 UPS switch specification REC input switch, bypass input switch, maintenance switch and output switch are optional parts.
P
5.6 Communication circuits Mini-Slot cards: Web/SNMP, Relay/RS232, Industrial Relay, ModBus.
P
6 UPS tests --
6.1 Summary P
6.1.1 Venue, instrumentation and load P
6.1.1.1 Test venue P
A UPS shall generally be tested at the manufacturer’s premises and in accordance with Table 3
P
6.1.1.2 Test instrumentation P
6.1.1.3 Test load P
Test load are performed as prescribed in the relevant test clause, with
P
- reference linear load P
- reference non-linear load P
6.1.2 Routine test Decided by manufacture and purchaser
P
6.1.3 Site test N/A
6.1.4 Witness test Decided by manufacture and purchaser
P
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 12 of 54 Report No.: ES160513045S-1 Ver.1.0
6.1.5 Type test P
6.1.6 Schedule of tests N/A
Tests shall be performed in accordance with Table 3 N/A
6.2 Routine test procedure P
6.2.2 Electrical P
6.2.2.1 Insulation and dielectric See separate safety report. P
6.2.2.2 Cable and interconnection check P
All a.c. and d.c. supply terminals are connected to the a.c. input supply, to the stored energy source and to the load
P
Any communication circuit is connected as required P
6.2.2.3 Light load and functional test P
a) all control switches and other means to activate UPS operation
P
b) protective devices P
c) auxiliary devices, such as contactors, fans, outlets, annunciators and communication devices
P
d) supervisory, monitoring and remote signalling devices
P
e) auto transfer to stored energy mode and back to normal mode by failing and subsequently restoring the a.c. input voltage
P
f) auto transfer to bypass or isolation of the inverter from a common a.c. output bus and back to normal mode by failing and subsequently restoring the inverter a.c. output voltage
P
g) manual transfer to bypass or isolation of the inverter from a common a.c. output bus and back to normal mode by operating appropriate switches and/or controls
P
6.2.2.4 No load P
6.2.2.5 Full load P
6.2.2.6 Synchronisation P
6.2.2.7 AC input failure P
6.2.2.8 AC input return (see appended table) P
6.2.2.9 Transfer to bypass P
6.3 Site test procedure N/A
Site test shall preferably occur under conditions representing those of actual service and shall use the load available on site.
N/A
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 13 of 54 Report No.: ES160513045S-1 Ver.1.0
The load shall not exceed the rated continuous load of the complete UPS as configured on side, or
N/A
Test performed with reference test load as defined in 3.3.5
N/A
6.4 Type test procedure (electrical) P
6.4.1 Input – a.c. supply compatibility (see appended table) P
6.4.1.1 Steady-state input voltage tolerance (see appended table) P
6.4.1.2 Input frequency tolerance (see appended table) P
6.4.1.3 Inrush current (see appended table) P
6.4.1.4 Harmonic distortion of input current (see appended table) P
6.4.1.5 Power factor (see appended table) P
6.4.1.6 Efficiency (see appended table) P
6.4.1.7 Backfeed protection See separate report. P
6.4.1.8 Residual earth current See separate report. P
6.4.1.9 Stand-by generator compatibility test P
6.4.1.10 Electromagnetic compatibility See separate report. P
6.4.2 Output-Linear load (see appended table) P
6.4.2.1 Normal mode- No load (see appended table) P
6.4.2.2 Normal mode – Full load (see appended table) P
6.4.2.3 Stored energy mode – No load (see appended table) P
6.4.2.4 Stored energy mode – Full load (see appended table) P
6.4.2.5 3-phase unbalance (see appended table) P
6.4.2.6 DC component P
6.4.2.7 Load sharing test Provided P
6.4.2.8 Output overvoltage test (see appended table) P
6.4.2.9 Periodic output voltage variation test (see appended table) P
6.4.2.10 Overload and fault clearing capability P
6.4.2.10.1 Overload – Normal mode (see appended table) P
6.4.2.10.2 Overload – Stored energy mode (see appended table) P
6.4.2.10.3 Fault clearing capability – Normal mode (see appended table) P
6.4.2.10.4 Fault clearing capability – Stored energy mode (see appended table) P
6.4.2.11 Dynamic performance P
6.4.2.11.1 Normal to stored energy mode (see appended table) P
6.4.2.11.2 Stored energy to normal mode (see appended table) P
6.4.2.11.3 Normal to bypass mode – Overload (see appended table) P
6.4.2.11.4 Step load – Normal mode (see appended table) P
6.4.2.11.5 Step load – Stored energy mode (see appended table) P
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 14 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.11.6 Test method – linear load (see appended table) P
6.4.2.12 Simulation of parallel redundant UPS fault (see appended table) P
6.4.3 Output – Non-linear load P
Tests performed with non-linear load as defined in annex E
(see appended table) P
6.4.3.1 Normal mode – Full load (see appended table) P
6.4.3.2 Stored energy mode – Full load (see appended table) P
6.4.3.3 Dynamic performance P
6.4.3.3.1 Normal to stored energy mode (see appended table) P
6.4.3.3.2 Stored energy to normal mode (see appended table) P
6.4.3.3.3 Load step – Normal mode P
a) UPS ≤ 4.0 kVA rating N/A
b) UPS > 4.0kVA rating (see appended table) P
6.4.3.3.4 Load step –stored energy mode (see appended table) P
6.4.4 Stored and restored energy P
6.4.4.1 Stored energy time N/A
6.4.4.2 Restored energy time (to 90% capacity) N/A
6.4.4.3 Battery ripple current measurement (see appended table) P
6.4.4.4 Restart test P
6.5 Type test procedure (environment) P
6.5.1 Environment and transportation test methods See separate report. P
6.5.2 Transportation P
6.5.2.1 Shock test (See separate report) P
a) initial measurement P
b) mode of operation P
c) Tests P
d) final requirements P
e) final measurements P
6.5.2.2 Free fall test See separate report. P
a) initial measurement P
b) mode of operation P
c) test P
d) measurements during testing P
e) final requirements P
f) final measurements P
6.5.3 Storage See separate report. P
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 15 of 54 Report No.: ES160513045S-1 Ver.1.0
a) initial measurement P
b) mode of operation P
c) tests P
d) measurements during test P
e) Final requirements P
f) Final measurements P
6.5.4 Operation See separate report. P
a) initial measurement P
b) mode of operation P
c) test P
d) measurements during testing P
e) final measurements P
f) final requirements P
6.5.5 Acoustic noise (See separate report) P
Measured when UPS operates at rated steady-state linear load under the following conditions:
P
- normal mode P
- stored energy mode P
6.6 UPS functional unit tests (where not tested as a complete UPS) N/A
6.6.1 UPS rectifier test N/A
6.6.2 UPS inverter tests N/A
6.6.3 UPS switch tests N/A
6.6.4 Stored energy / battery tests N/A
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 16 of 54 Report No.: ES160513045S-1 Ver.1.0
5.2.1.e 5.3.2.q 6.4.2.5
TABLE: - 3-phase input, voltage unbalance
P
Description of test conditions / test construction: 1) Start the UPS in normal mode at nominal input voltage and frequency (230V/50Hz), apply balance
full linear load and unbalance linear load.
2) Voltage regulation is defined as:
3) Angle deviation is defined as:
Measured data: 1、Balance load
balance load Va Vb Vc Yv(%)<2
%
< 2.5 degree
ᇫab ᇫbc ᇫca
Ph. a=b=c 100% Linear load
224.8V 224.1V 223.1
V 0.3% 0.1 0.3 0.4
2、Unbalance load 1) Ph. a=0,b=c=100% linear load
un alan e loa Va Vb Vc Yv(%)<2
%
< 2.5 degree
ᇫab ᇫbc ᇫca
%100
)2
arccos3
cos(2
)2
arccos3
cos(2
22222
22222
caab
bccaabcaabcaab
caab
bccaabcaabcaab
V
UU
UUUUUUU
UU
UUUUUUU
Y
oo
222
1201802
arccos1
bnan
abbnanAB
UU
UUU
oo
222
1201802
arccos1
cnbn
bccnbnBC
UU
UUU
oo
222
1201802
arccos1
ancn
caancnCA
UU
UUU
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 17 of 54 Report No.: ES160513045S-1 Ver.1.0
Ph. a=0 67%Linear load
225.9V 225.2V 224.9
V 0.1% 0.0 0.3 0.3
2) Ph. b=0,a=c=100% linear load
unbalance load Va Vb Vc Yv(%)<2
%
< 2.5 degree
ᇫab ᇫbc ᇫca
Ph. b=0 67%Linear loa
226.3V 225.9V 22 .2
V 0.1% 0.2 0.4 0.2
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 18 of 54 Report No.: ES160513045S-1 Ver.1.0
3) Ph. c=0,a=b=100% linear load
unbalance load Va Vb Vc Yv(%)<2
%
< 2.5 degree
ᇫab ᇫbc ᇫca
Ph. c=0 67%Linear load
226.4V 225.6V 225.4
V 0.2% 0.3 0.2 0.5
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 19 of 54 Report No.: ES160513045S-1 Ver.1.0
6.2.2.8 6.4.1.3 6.4.2.11.2
TABLE: - AC input return - Inrush current - Change of operating mode – Stored energy to normal mode
P
Description of test conditions / test construction: 1. AC input return 1) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. A few seconds later, return AC input, UPS transfer to normal again. 2) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. 3) A few seconds later, return AC input with improper phase rotation, UPS can't transfer to normal and alarm "Rectifier Phase. 4) Then cut off input, and return AC input with proper phase rotation, UPS transfer to normal again. 2. Inrush current 1) Input &bypass supply at 187V/230V/264V 50Hz and battery off. analysis the inrush input current for the following cases: 2) When Vbus didn’t drop, turn on common line &bypass and battery at the moment that the input voltage is 0V first and Vmax , record the inrush current, and then turn on the system, record the inrush current again. 3) Test results: inrush current ≤120% of rated current for ≤2 cycles.
Remark Channel 1 - Output Current Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase A Channel 4 - Input Voltage Phase A
Measured graph: 1) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. A few seconds later, return AC input, UPS transfer to normal again.
2) UPS run in normal mode, applying 100% linear load. Then cut off input, UPS transfer to battery. A few seconds later, return AC input with improper phase rotation, UPS can't transfer to normal and alarm "Rectifier Phase Rotation Failed". Then cut off input, and return AC input with proper phase rotation, UPS transfer to normal again.
2. Inrush current < 2.5X 1)Vbus=0 input voltage=187V Inrush current=23A 2)Vbus>0 input voltage=187V Inrush current=22A
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 20 of 54 Report No.: ES160513045S-1 Ver.1.0
3)Vbus=0 input voltage=230V Inrush current=21A 4)Vbus>0 input voltage=230V Inrush current=23A 5)Vbus=0 input voltage=272V Inrush current=20A 6)Vbus>0 input voltage=272V Inrush current=22A
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 21 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.1.4 TABLE: -Harmonic distortion of input current P
Description of test conditions / test construction: 1) The harmonic distortion of the input current is tested at reference test load. 2) Test result THDi < 35%
Load(%) Harmonic No.
Phase 1 (dB)
Phase 2 (dB)
Phase 3 (dB)
-
99% 3 2 1 1 -
5 66 67 67 -
7 10 11 10 -
9 1 0 0 -
THD Distortion at phase 1
Distortion at phase 2
Distortion at phase 3
Expected value due to the specification of the manufacturer
-
See formula to THD below(100% load)
28.8% 28.8% 29.0% 35%
-
2
20
92
20
72
20
52
20
3
10101010100
THD
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 22 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.1.5 & 6.4.1.6
TABLE: - Input power factor - Efficiency-Normal Mode
P
Description of test conditions / test construction: 1) UPS run in normal mode, charge off. The UPS efficiency shall be measured at 25%, 50%, 75% and 100% reference load. Input power factor = 0.999
Load (%)
Efficiency Input Power (KW)
Output Power (KW)
Expected value due to the specification of the manufacturer
Verdict
25 90.2% 28.6K 25.8K 82.5% P
50 92.5% 55.0K 50.9K 87.5% P
75 92.3% 79.8K 73.7K 89.1% P
100 90.94% 128K 116.4K 88.8% P
6.4.2.1 TABLE: - Output – Linear load: Normal mode – No load - Harmonic components measurement
P
Description of test conditions / test construction: 1)With the UPS operating in normal mode of operation at no load and nominal input voltage and frequency, measure the r.m.s. output voltage and its fundamental and harmonic components.
Load (%)
Harmonic No.
Phase 1 (dB)
Phase 2 (dB)
Phase 3 (dB)
-
0 3 0.1 0.2 0.1 -
5 0.2 0.3 0.3 -
7 0.1 0.1 0.1 -
9 0.0 0.0 0.1 -
THD Distortion at phase 1
Distortion at phase 2
Distortion at phase 3
Expected value due to the specification of the manufacturer
-
see formula to THD below
0.3% 0.4% 0.4% < 1% -
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 23 of 54 Report No.: ES160513045S-1 Ver.1.0
2
20
92
20
72
20
52
20
3
10101010100
THD
6.4.2.2 TABLE: - Output – Linear load: Normal mode – Full load Harmonic components measurement
P
Description of test conditions / test construction: 1)UPS runs in normal mode, applying 100% reference test load to the UPS output, then measure output voltage and its fundamental and harmonic components.
Load (%)
Harmonic No.
Phase 1 (dB)
Phase 2 (dB)
Phase 3 (dB)
-
100 3 0.1 0.2 0.2 -
5 0.4 0.3 0.4 -
7 0.3 0.3 0.2 -
9 0.1 0.1 0.1 -
THD Distortion at phase 1
Distortion at phase 2
Distortion at phase 3
Expected value due to the specification of the manufacturer
-
see formula to THD below
0.6% 0.5% 0.6% < 1% -
2
20
92
20
72
20
52
20
3
10101010100
THD
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 24 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.3 TABLE: - Output – Linear load: Stored energy mode – No load - Harmonic components measurement
P
Description of test conditions / test construction: 1)With the UPS operating in battery mode of operation at no load, measure the r.m.s. output voltage and its fundamental and harmonic components.
Load (%)
Harmonic No.
Phase 1 (dB)
Phase 2 (dB)
Phase 3 (dB)
-
0 3 0.1 0.1 0.1 -
5 0.2 0.2 0.3 -
7 0.1 0.1 0.1 -
9 0.0 0.0 0.0 -
THD Distortion at phase 1
Distortion at phase 2
Distortion at phase 3
Expected value due to the specification of the manufacturer
-
see formula to THD below
0.4% 0.4% 0.4% < 1% -
2
20
92
20
72
20
52
20
3
10101010100
THD
6.4.2.4 TABLE: - Output – Linear load: Stored energy mode – Full load Harmonic components measurement
P
Description of test conditions / test construction: 1)UPS runs in battery mode, applying 100 % reference test load to the UPS output, then measure output voltage and its fundamental and harmonic components.
Load (%)
Harmonic No.
Phase 1 (dB)
Phase 2 (dB)
Phase 3 (dB)
-
100 3 0.1 0.2 0.2 -
5 0.4 0.3 0.4 -
7 0.3 0.3 0.2 -
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 25 of 54 Report No.: ES160513045S-1 Ver.1.0
9 0.1 0.1 0.1 -
THD Distortion at phase 1
Distortion at phase 2
Distortion at phase 3
Expected value due to the specification of the manufacturer
-
see formula to THD below
0.6% 0.5% 0.6% < 1% -
2
20
92
20
72
20
52
20
3
10101010100
THD
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 26 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.10.1 TABLE: Overload capability test – Normal mode P
Description of test conditions / test construction: 1) UPS in normal mode, apply below loads respectively to the output, check UPS performance
and alarms. 2) Measure the overload time duration, check UPS transfer to bypass and transfer back to
normal mode automatically if removing overload.
Condition Specs
30C ambient, 1000m, nominal Uin
Overloads
105 - 125% 10 minutes
126-150% 1 minute
>150%, 200ms
Load/(%) Specified time interval Verdict
107% 615.17s P
128% 60.76s P
154% 238.4ms P
Measured data: 1) 107% linear load overload time=615.17s
2) 128% linear load overload time=60.76s
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 27 of 54 Report No.: ES160513045S-1 Ver.1.0
3) 154% linear load overload time=238.4ms
Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 28 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.10.2 TABLE: Overload capability test – Stored energy mode P
Description of test conditions / test construction: 1) UPS in battery mode, apply below loads respectively to the output, check UPS performance and
alarms. 2) Measure the overload time duration, check UPS transfer to bypass and transfer back to battery mode
automatically if removing overload.
Condition Specs
30C ambient, 1000m, nominal Uin
Overloads
105 - 125% 10minutes
126-150% 1minutes
>150%, 200ms
Load/(%) Specified time interval Verdict
107% 613.79s P
128% 60.96s P
154% 220.4ms P
Measured data: 1)107% linear load overload time=613.79s
2)128% linear load overload time=60.96s
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 29 of 54 Report No.: ES160513045S-1 Ver.1.0
3)154% linear load overload time=220.4ms
Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 30 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.10.3 TABLE: - Fault clearing capability – Normal mode - Short circuit test
P
Description of test conditions / test construction: 1) UPS operating in normal mode, applying 50% linear load. Input and output both are 240V/50Hz. 2) Then make output shorted, check UPS response. UPS should shut down and alarm "Inverter Output
Over Current" 3) Then remove the shorted circuit; Reset alarms, "Inverter Output Over Current" will be cleared. 4) Turn UPS on, UPS run in normal mode again.
Measured graph:
1) Output shorted, UPS shut down and alarm "Inverter Output Over Current", remove shorted circuit and reset alarm, alarm "Inverter Output Over Current" cleared, turn on UPS to normal mode.
Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 31 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.10.4 TABLE: - Fault clearing capability – Stored energy mode - Short circuit test
P
Description of test conditions / test construction: 1) UPS operating in battery mode, applying 50% linear load. Output is 240V/50Hz. 2) Then make output shorted, check UPS response. UPS should shut down and alarm "Inverter Output
Over Current". 3) Then remove the shorted circuit; Reset alarms , "Inverter Output Over Current" will be cleared. 4) Turn UPS on, UPS run in battery mode again.
Measured graph: Output shorted, UPS shut down and alarm "Inverter Output Over Current", remove shorted circuit and reset alarm, alarm "Inverter Output Over Current" cleared, turn on UPS to battery mode.
Channel 1 - Output Current Phase A Channel 2 - Output Voltage Phase B Channel 3 - Input Voltage Phase A Channel 4 - Input Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 32 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.11.1 TABLE: - Change of operating mode – Normal to stored energy mode - AC input failure test
P
Description of test conditions / test construction: 1) UPS initially operating at full linear load in normal mode, the input supply shall be interrupted, then
UPS transfers to battery mode. 2) Check the system when the utility failure normal operation. Measure the transient output voltage
deviation.
Power Type
Response procedure
Before After deviation < 5%
A B C A B C
deviation
Phase A
deviation Phase
B
deviation Phase
C
230V/50Hz
Normal to Battery
220.981 219.421 219.434 220.931 219.605 219.330 0.02% 0.08% 0.05%
Measured graph: Before waveform After waveform
Channel 1 - Output Voltage Phase A
Channel 2 - Input Current Phase A
Channel 3 - Output Voltage Phase C
Channel 4 - Output Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 33 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.11.3 TABLE: - Change of operating mode – Normal to bypass mode - Overload test
P
Description of test conditions / test construction: 1) UPS has a bypass mode of operation which is automatic in operation under conditions of output
overload. 2) The input and output voltage waveforms shall be observed during transitions normal to bypass
mode.
Measured graph: Load transfer from inverter to mains
Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 34 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.2.11.4 TABLE: - Step load –Normal mode P
Description of test conditions / test construction: 1) Impact linear load as defined 20% => 100 %=> 20% nominal load with 230V/50Hz in normal mode. 2) Check the transient response
Measured graph: 1) Step load from 20% to 100% linear load
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
230V/50Hz
20% to 100% load
220.766 219.567
219.437 213.836 212.221
212.870 3.15% 3.34% 2.99%
2) Step load from100% down to 20% linear load
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 35 of 54 Report No.: ES160513045S-1 Ver.1.0
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
230V/50Hz
100% to 20% load
221.081 219.087
221.407 226.824 225.396
226.023 2.61% 2.88% 2.10%
Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B
6.4.2.11.5 TABLE: - Step load – Stored energy mode P
Description of test conditions / test construction: 1) Impact linear load as defined 20% => 100 %=> 20% nominal load with 230V/50Hz in battery mode. 2) Check the transient response
Measured graph: 1) Step load from 20% to 100% linear load
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
230V/50Hz
0 to 100% load
220.732 219.642
219.456 214.148 212.993
212.975 3.00% 3.02% 2.95%
2) Step load from100% down to 20% linear load
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 36 of 54 Report No.: ES160513045S-1 Ver.1.0
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
230V/50Hz
100% to 0 load
221.095 219.547
222.272 226.652 225.534
225.865 2.53% 2.72% 1.63%
Channel 1 - Output Voltage Phase A
Channel 2 - Input Current Phase A
Channel 3 - Output Voltage Phase C
Channel 4 - Output Voltage Phase B
6.4.3.1 TABLE: - Output – Non-linear load: Normal mode – Full load - Harmonic components measurement
P
Description of test conditions / test construction: UPS runs in normal mode, applying 100 % non-linear load to the UPS output, then measure output voltage and its fundamental and harmonic components.
Load (%)
Harmonic No.
Phase 1 (dB)
Phase 2 (dB)
Phase 3 (dB)
-
100 3 2.4 2.4 2.3 -
5 3.8 3.9 3.8 -
7 1.1 1.2 1.1 -
9 0.7 0.7 0.6 -
THD Distortion at phase 1
Distortion at phase 2
Distortion at phase 3
Expected value due to the specification of the manufacturer
-
see formula to THD below
5.0% 5.1% 4.9% < 8% -
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 37 of 54 Report No.: ES160513045S-1 Ver.1.0
2
20
92
20
72
20
52
20
3
10101010100
THD
6.4.3.2 TABLE: - Output – Non-linear load: Stored energy mode – Full load - Harmonic components measurement
P
Description of test conditions / test construction: UPS runs in battery mode, applying 100 % non-linear load to the UPS output, then measure output voltage and its fundamental and harmonic components.
Load (%)
Harmonic No.
Phase 1 (dB)
Phase 2 (dB)
Phase 3 (dB)
-
100 3 2.5 2.4 2.2 -
5 3.8 3.8 3.9 -
7 1.1 1.1 1.1 -
9 0.7 0.7 0.6 -
THD Distortion at phase 1
Distortion at phase 2
Distortion at phase 3
Expected value due to the specification of the manufacturer
-
see formula to THD below
5.0% 5.0% 4.9% < 8% -
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 38 of 54 Report No.: ES160513045S-1 Ver.1.0
2
20
92
20
72
20
52
20
3
10101010100
THD
Measured graph:
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 39 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.3.3.1
TABLE: - Reference non-linear load – Normal to stored energy mode - AC input failure test
P
Description of test conditions / test construction: 1) UPS initially operating at full non-linear load in normal mode, the input supply shall be interrupted,
then UPS transfers to battery mode; 2) Check the system when the utility failure normal operation. Measure the transient output voltage
deviation.
Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
230V/50Hz
Normal to Battery
221.026 219.557 218.738 221.100 219.317 218.740 0.03% 0.01% 0.08%
Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 40 of 54 Report No.: ES160513045S-1 Ver.1.0
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 41 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.3.3.2 TABLE: - Reference non-linear load – Stored energy to normal mode P
Description of test conditions / test construction: 1) UPS initially operating at full non-linear load in battery mode, the input supply shall be recovery, then
UPS transfers to normal mode, 2) Check the system when the utility response normal operation. Measure the transient output voltage
deviation.
Measured graph: Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
230V/50Hz
Normal to Battery
221.642 219.909 218.937 221.548 219.828 218.846 0.04% 0.04% 0.04%
Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 42 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.3.3.3.b TABLE: - Reference non-linear load steps – Normal mode > 4.0 kVA rating P
Description of test conditions / test construction: 1) Impact linear load as defined 33 %=> 66%=100 %=> 66 %=> 33% non-linear load with 230V/50Hz in
normal mode. 2) Check the transient response.
Measured graph: 1) Step load from 33% up to 66% non-linear load
Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
220V/50Hz
33%=>66% load
221.434 220.270 219.286 218.735 215.311 218.876 1.23% 2.25% 0.19%
2) Step load from 66% up to 100% non-linear load
Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 43 of 54 Report No.: ES160513045S-1 Ver.1.0
220V/50Hz
66%=100% load
221.425 220.428 219.406 218.633 214.534 215.290 1.27% 2.68% 1.87%
3) Step load from100% down to 66% non-linear load Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
220V/50Hz
100%=66% load
221.594 220.195 219.223 223.389 221.496 220.669 0.82% 0.59% 0.66%
4) Step load from 66% down to 33% non-linear load Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
220V/50Hz
66%=33% load
221.660 220.140 219.032 222.477 220.820 220.086 0.37% 0.31% 0.48%
Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 44 of 54 Report No.: ES160513045S-1 Ver.1.0
6.4.3.3.4 TABLE: - Reference non-linear load steps – Stored energy mode > 4.0 kVA rating
P
Description of test conditions / test construction: test repeated according to sub-clause 6.4.3.3.3.b 1) Impact linear load as defined 33 %=> 66%=100 %=> 66 %=> 33% non-linear load with 230V/50Hz in
battery mode. 2) Check the transient response
Measured graph: 1) Step load from 33% up to 66% non-linear load
Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
220V/50Hz
33%=66% load
221.877 219.814 219.081 217.753 215.205 212.038 1.87% 2.10% 3.20%
2)Step load from 66% up to 100% non-linear load
Before waveform After waveform
Power Respons Before After deviation < 5%
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 45 of 54 Report No.: ES160513045S-1 Ver.1.0
Type e procedure
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
220V/50Hz
66%=100% load
220.484 219.230 217.893 211.551 217.846 212.653 4.1% 0.63% 2.38%
3) Step load from100% down to 66% non-linear load Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
220V/50Hz
100%=66% load
222.014 220.009 219.407 222.705 221.428 220.352 0.19% 0.65% 0.43%
4) Step load from 66% downto 33% non-linear load Before waveform After waveform
Power Type
Response procedure
Before After deviation < 5%
A B C A B C deviation Phase
A
deviation Phase
B
deviation Phase
C
220V/50Hz
100%=66% load
221.589 220.002 219.153 222.842 221.480 220.415 0.57% 0.67% 0.57%
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 46 of 54 Report No.: ES160513045S-1 Ver.1.0
Channel 1 - Output Voltage Phase A Channel 2 - Input Current Phase A Channel 3 - Output Voltage Phase C Channel 4 - Output Voltage Phase B
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 47 of 54 Report No.: ES160513045S-1 Ver.1.0
TABLE: List of critical components P
Object/part no. Manufacturer/ trademark
Type/model Technical data Standard Mark(s) of conformity 1.
Whole unit
Enclosure Various Steel/Aluminium
-- -- --
LCD Display SHENZHEN TOPWAY TECHNOLOGY CO.,LTD.
LM2088DFW-C
HB, 80℃ -- --
Breaker (AC INPUT)
LS Industrial System Co.,Ltd
ABE203b,3P 250A (LS)
415V,250A IEC 60947-2 Intertek CB Certif. No.: CN10817
Breaker (OUTPUT)
LS Industrial System Co.,Ltd
ABE203b,3P 250A (LS)
415V,250A IEC 60898-1 Intertek CB Certif. No.: CN10817
Breaker
(MCCB)
LS Industrial System Co.,Ltd
ABE203b,3P 250A (LS)
415V,250A IEC 60898-1 Intertek CB Certif. No.: CN10817
Internal wire (AC)
Dongguan XIN RU Hardware Electronic Co. Ltd.
600227 IEC02(RV)25mm2,450/750V
450/750V,70℃ UL UL: E304337
Internal wire (DC)
Dongguan XIN RU Hardware Electronic Co. Ltd.
600227 IEC02(RV)25mm2,450/750V
450/750V,70℃ UL UL: E304337
Inverter Capacitor
EACO SRE-300-400-MSJ 400UF 300V 65A EACO
400uF±5%,300VAC,105℃
-- Test with appliance
IGBT infineon IGBT module,FF450R07ME4,650V,450A
650V,450A -- --
SCR SKKT SKKT 106/16E
106A,1600V UL UL: E63532
Input Inductor Guang hua industrial co.,ltd
EA89Ⅱ-120KVA 0.4mH 265A
130℃ -- Test with appliance
Transformer Guang hua industrial co.,ltd
EA89Ⅱ-120K 200:415 120KVA
Class H insulation
180℃
-- Test with appliance
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 48 of 54 Report No.: ES160513045S-1 Ver.1.0
AC fan SANJU ELECTRIC MACHINERY CO.,LTD
SJ1755HA2 BAL-(WZ)
AC220-240V,
0.18A
CE
UL
CE: N8A150268837 008
UL: E314698
Fuse MUSSMANN 170M5412 630A 690V
630A,690V IEC 60269-4 CQC CB Certif. No.: CN13985
Fuse HOLLYLAND CO LTD
61NM 6A,250V UL
KC
UL: E156471
KC: SU05008-4001B
Fuse HOLLYLAND CO LTD
65NM 5A,250V UL
KC
UL: E156471
KC: SU05008-4001B
SMPS(AUX-POWER-C2),
PCB Various Various V-0, 130℃ -- UL: E230225
X-Capacitor (C17)
Xiamen Faratronic Co., Ltd.
C42P2225KBSC400
X1, 275VAC,2.2uF IEC 60384-14 VDE:DE1-49862
KC: SU03060-12004
Y-Capacitor (C5, C6)
Xiamen Faratronic Co., Ltd.
C43Q1224MB0C400
Y-Cap, 300VAC,0.22uF
IEC 60384-14 VDE: SE-60440
KC: SU03060-12005
Inductor (L1)
JEPULS TECHNOLOGY(SHENZHEN) CO.,LTD
LC9-116 130℃ -- Test with appliance
Transformer (T1)
SHENZHEN FERROCOIL
ER42 CLASS B -- Test with appliance
-BOBBIN CHANG CHUN PLASTICS CO.,LTD
T375J -- UL 94V-0 UL: E59481(S)
-WIRE PACIFIC ELECTRIC WIRE & CABLE CO.,LTD
UEW-U 130℃ UL UL: E201757(S)
-TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY
PZ 130℃ UL UL: E165111(N)
-VARNISH HANG CHEUNG PETROCHEMICAL LTD
8562/C -- UL UL: E200154
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 49 of 54 Report No.: ES160513045S-1 Ver.1.0
-TUBE FLUO TECH INDUSTRIES CO.,LTD
TEFLON TUBE
-- UL UL: E175982(N)
-MARGIN TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY
WF 130℃ UL UL: E165111(N)
Transformer (T3)
SHENZHEN FERROCOIL
EEL16 CLASS B -- Test with appliance
-BOBBIN CHANG CHUN PLASTICS CO.,LTD
T375J -- UL 94V-0 UL: E59481(S)
-WIRE PACIFIC ELECTRIC WIRE & CABLE CO.,LTD
UEW-U 130℃ UL UL: E201757(S)
-TAPE SHENGDAFENG ELECTRONICS CO., LTD
PZ 130℃ UL UL: E317896
-VARNISH HANG CHEUNG PETROCHEMICAL LTD
8562/C -- UL UL: E200154
-TUBE FLUO TECH INDUSTRIES CO.,LTD
TEFLON TUBE
-- UL UL: E175982(N)
-MARGIN TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY
WF 130℃ UL UL: E165111(N)
Opto-coupler (IS1)
TOSHIBA TLP781-BL Dti>0.4mm, 115℃ min.
UL
VDE
UL:E67349
VDE :40021173
3PH Interface PCB(GF_INTERFACE),
Relay
(RL1, RL2, RL3, RL4, RL5, RL6)
Xiamen Hongfa Electronics Sales Co.
HFD27 60W,120VA UL UL: E133481
PCB Various Various V-0, 130℃ UL UL: E230225
<Inverter Drive PCB>(EA990Ⅱ_IGBTDR_D1)
IEC 62040-3
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC62040_3B Page 50 of 54 Report No.: ES160513045S-1 Ver.1.0
Transformer JEPULS TECHNOLOGY(SHENZHENG)CO.,LTD
Switch Power Transformer,E3HP-IGBT-T1-27:27:20-0.510mH-+/-30%-PG232
130℃ -- --
PCB Various Various V-0, 130℃ UL UL: E230225
<3PH SCR PCB>(REC-SCR-Drive)
Transformer Shenzhen Feiyue Electronic Technology Co., Ltd.
Driver Transformer,E3HPPT2,22:22:22,300uH
130℃ -- --
PCB Various Various V-0, 130℃ UL UL: E230225
CNTL BOARD(Main_Control-C1)
TRANSFOMER SHENZHEN FERROCOIL
EE16 CLASS B -- Test with appliance
-BOBBIN CHANG CHUN PLASTICS CO.,LTD
T375J -- UL 94V-0 UL: E59481(S)
-WIRE PACIFIC ELECTRIC WIRE & CABLE CO.,LTD
UEW-U 130℃ UL UL: E201757(S)
-TAPE JINGJIANG PRESSURE SENSITIVE GLUE FIY
PZ 130℃ UL UL: E165111(N)
-VARNISH HANG CHEUNG PETROCHEMICAL LTD
8562/C -- UL UL: E200154
Opto-coupler (IS1)
LITE-ON TECHNOLOGY CORP.
LTV-816S-TA1(C)
Dti>0.4mm, 110℃ min.
UL UL:E113898
PCB Various Various V-0, 130℃ UL UL: E230225
Supplementary information:
An asterisk indicates a mark that assures the agreed level of surveillance.
Pictures
TRF No. IEC62040_3B Page 51 of 54 Report No.: ES160513045S-1 Ver.1.0
Fig. 1 –Overview I
Pictures
TRF No. IEC62040_3B Page 52 of 54 Report No.: ES160513045S-1 Ver.1.0
Fig. 2 –Overview II
Pictures
TRF No. IEC62040_3B Page 53 of 54 Report No.: ES160513045S-1 Ver.1.0
Fig. 3 –Overview III
Pictures
TRF No. IEC62040_3B Page 54 of 54 Report No.: ES160513045S-1 Ver.1.0
Fig. 4 –Overview IIII