quick selection guide-trox

60
Quick Selection Guide Issue Date November 2013

Upload: luis-gabriel-bautista

Post on 26-Nov-2015

143 views

Category:

Documents


8 download

DESCRIPTION

Grilles & Slot Diffusers Guide

TRANSCRIPT

  • Quick Selection Guide

    Issue Date November 2013

  • Quick Selection

    This selection guide has been designed to allow quick and simple

    selection for a broad range of TROX Grille and Diffuser product. Full product

    and system details for these and other TROX equipment can be found on our

    website www.troxuk.co.uk.

    As part of our commitment to a collaborative design process our local Sales Engineers

    are available to offer assistance and advice on these and other TROX systems and product.

    To contact you local engineer call 01842 754545.

    In addition to the Grille and Diffuser product in this guide, TROX offer a complete range of air

    distribution products and systems, these include:

    Active Chilled Beams

    Passive Chilled Beams

    Multi Service Chilled Beams (MSCB)

    Chilled Ceilings

    Fan Coil Units

    Acoustics

    Filtration

    VAV Terminal Units

    Labcontrol

    Dealer Desk Cooling

    Low to High Density Cooling

    TROX UK Ltd Caxton Way

    Thetford Norfolk IP24 3SQ

    Tel: +44 (0) 1842 754545Fax: +44 (0) 1842 763051E-Mail: [email protected]

    www.troxuk.co.uk

  • PageSection1 - Adjustable GrillesAT/VAT 04

    Section 2 - Extract GrilleAE 06

    Section 3 - Floor GrillesAFG 08FB 10

    Section 4 - Linear GrillesAH/WAP/AF 12

    Section 5 - Transfer GrillesAGS/LCG/LVV40 14

    Section 6 - Slot DiffusersVSD50 - High Capacity 16VSD35 18ALS-25 - High Capacity 20ALS-20 22Slot Diffuser Plenum Boxes 24

    Section 7 - Fixed Blade Linear DiffuserADM 26

    Section 8 - Louvre Faced DiffusersSquare DiffuserADT 28ADLQ 32Circular DiffuserADLR 34

    Section 9 - Perforated Face DiffuserADLQL 36

    Section 10 - Disc ValvesLVS/ZLVS 38

    Section 11 - Swirl DiffusersSelection Methodology 40SDW 42VDW 44FD 46DCS 48TDF 50TDV 52RFD 54

    Section 12 - Jet NozzlesDUK 56AJA 58

    Contents

  • 643

    2

    Adjustable Grille Type VATSupply or return air grille with individually adjustable verticalaerofoil blades. Front border 32mm wide with visible screw fixing(border counter-punched). Available on request with concealedfixing and sub frame.

    Adjustable Grille Type ATSupply or return air grille with individually adjustable horizontalaerofoil blades. Front border 32mm wide with visible screw fixing(border counter-punched). Available on request with concealedfixing and sub frame.

    Sizes AvailableMinimum size 150 x 100. Maximum Size 1200 x 600. Standardincrements 50mm.

    For full details see publication 1/1.1/B/...

    Order Code

    Rear Assembly

    SECTION 1

    Adjustable Grilles

    04

    Type

    AT = Horizontal front blade

    VAT = Vertical front blade

    Rear Assemblies

    A = Grille face only

    AG = Rear opposed blade damper

    D = Rear adjustable blades

    DG = Rear adjustable blades and damper

    0 = No subframe

    B30 = 75mm

    subframe bracketFixing Variant0 = Without (screw fix)S11 = With (secret fix)X = Without flange drilling or secret fix

    L x H (mm) Powder coat finish

    AT - AG 800 x 200 B30 S11 P3 RAL 9010 20% Gloss/ / / / / /

    10

    775

    H /

    L

    H +

    22

    /L +

    22

    H +

    45

    /L +

    45

    16,7

    10

    775

    ...-AGOpposed blade action volume controldamper, adjustable from the front face.

    ...-DA set of individually adjustable vertical airpattern control blades. For type VAT theseblades are horizontal.

    ...-DGVolume control dampers as ...-AG plus a setof individually adjustable vertical air patterncontrol blades.

    Type AT VAT

    Type AT shown

  • Performance DataGrille with ceiling effect (grille installed within 300mm of ceiling). Throw is the distance from sidewall grille to anaverage velocity of 0.35 m/s. The minimum distance between multiple units must be 20% of Throw.

    Throw assumes direction blades set at 45 bladedivergence. For 0 blade divergence multiple throw by1.4 and divide pressure drop by 1.1.

    By limiting effective jet velocity to 7 m/s all grille sizesshown meet NC35 assuming 8dB room attenuation andfully open damper.

    SECTION 1Adjustable Grilles

    05

    Subframe Secret Fixing Detail

    75

    32

    X

    Type B30 - 30mm border : X = 15

    Screwdriver operationto locate fastenertongue behind subframe

    Concealed fastenerfactory fitted togrille border

    L+6/H+6 Subframe fixedto surround(No 8 screw by others)

    15

    100

    150

    200

    250

    300

    350

    400

    450

    500

    600

    Nominalheight(mm)

    H

    PivotLine

    150

    200

    250

    300

    400

    350

    450

    500

    600

    700

    800

    900

    1000

    1200

    Nominalwidth(mm)

    L

    60

    40

    20

    10

    5

    Pressuredrop (total)

    (Pa)

    8

    65

    4

    3

    2

    Effective JetVelocity

    (m/s)

    10

    8

    6

    5

    4

    3

    1100

    1000900

    800

    700

    600

    500

    400

    350

    300

    250

    200

    175

    150

    125

    10090

    70

    50

    40

    30

    20

    Air Volume(l/s)

    Throw(m)

    Pivotline

  • Eggcrate Grille Type AEReturn air grille with fixed square pattern core. Front border32mm with visible screw fixing. Available on request withconcealed fixing.

    The grille is available with rear mounted opposed blade volumecontrol damper adjustable from the front face.

    Size AvailableMinimum Size 150 x 100. Maximum Size 1200 x 600. Standardincrements 50mm.

    For full details see publication 1/1.3/B/...

    SECTION 2

    Extract Grilles

    Order Code

    TypeAE

    Rear Assemblies A = Grille face onlyAG = Rear opposed blade damper

    Subframe0 = without subframeB30 = 75mm subframe bracket

    Fixing Variant0 = Without (screw fix)S11 = With (secret fix)X = Without flange drilling or secret fix

    L x H (mm)Powder coat finish

    AE - AG 200 x 200 B30 S11 P3 RAL 9010 20% Gloss/ / / / / /

    Screw Fixing Secret Fixing Detail Subframe

    H /

    L

    H +

    45/L

    + 4

    5

    H +

    22/L

    + 2

    2

    13 75

    32

    X

    Type B30 - 30mm border : X = 15

    Screwdriver operationto locate fastenertongue behind subframe

    Concealed fastenerfactory fitted togrille border

    L+6/H+6 Subframe fixedto surround(No 8 screw by others)

    15

    Rear Assembly

    ...-AG

    10

    470

    06

  • Performance Data

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    1100

    1200

    Nominalwidth(mm)

    L

    1000

    500

    400

    300

    200

    100

    50

    25

    Air Volume(l/s)

    Effective JetVelocity

    (m/s)

    Pressuredrop (total)

    (Pa)

    15

    10

    5

    2

    Pivotline

    765

    4

    3

    2

    1

    0.5

    Pivotline

    Nominalheight(mm)

    H100

    150

    200

    250

    300

    350

    400

    450

    500

    600

    SECTION 2Extract Grilles

    By limiting effective jet velocity to 7 m/s all grille sizes shown meet NC35 assuming 8 dB room attenuation (nodamper or damper fully open).

    07

  • Note: 1) 75mm CFG depth option available

    DetailA

    X standard 25mm. Can be 25-50mm in 1mm steps

    Shims to suit height required(factory fitted)

    X

    90mm MaximumPedestal

    599u +0.5/-1mm

    125m

    m1)

    Power Inlet Plug (C14)

    6mm13mm Nominal Pitch

    68.5

    140m

    m A

    ppro

    x

    SECTION 3

    Floor Grilles

    Order Code

    Type CFG Type AFG

    Detail A

    08

    Computer Room Floor Grille Type CFG/AFGFloor grille types CFG and AFG are specifically developed for mounting in RaisedAccess Floors in such areas as Computer Rooms, where load and damageresistance are of the utmost importance.

    Having a heavy duty construction, they can replace 600mm square floor tiles.Grille border depth can be specified to suit the type of floor system used. A rangeof surface finishes is available.

    The type CFG is a fan assisted computer room floor grille thateliminates hotspots and reduces risk of equipment failure byproviding up to 5kW of cooling per cabinet.

    The type AFG is a static grille assembly which can handle supplyair or alternatively extract air and be fitted with rear opposedblade damper assembly for air volume flow control.

    For full details see publication PI/1/9/B/...

    Frame Depth (mm)between face of grille and face of pedestal25 standardOptionally 26 - 50 in 1mm steps

    *Does not have the structural performance of 125mm unit

    TypeCFGAFG

    // / /600 x 600 35 P2

    P2 = Polyester powder coat silver grey RAL 9006 25% Gloss (Standard)

    P4 = Polyester powder coat black RAL 9006 20% Gloss

    N1 = Polyester powder coat with nylon reinforcing black RAL 9005

    Unit Depth (mm)125 = Standard*75 = Optional0 = Not used AFG

    Size (mm)

    Rear AssemblesF1 = Fan Pack (230V Standard) CFG onlyA = Face only, AFG onlyAG = Rear opposed blade damper, AFG only

    CFG - F1 125

  • SECTION 3Floor Grilles

    09

    CFG Fan SpecificationWatts/Motor 26Total Watts 104Amps/Motor 0.12Total Amps 0.48Motor 230V AC 50Hz

    Selection GuideThe floor grille should be located at the front of theI.T./Comms cabinet experiencing hot spot conditions thecabinet should incorporate a perforated door. The floorvoid static pressure must be considered in the selectionprocess (see Potential cooling below). Sufficient void air(cooled by others) must be available to be drawn by thegrille at the specific point of need.

    CFG Acoustic DataSound power level for one CFG 76dB(A)In an area with several units the noise level will increasedue to multiple sources. To allow for this and roomattenuation an assessment should be made by anacoustic engineer to ensure required room noise levelsare achieved.

    Structural performance

    Test Result

    Stability of deflection (centre of grille):

    4.5 kN static load through 25mmsquare indentor

    Impact load test:

    40 kg Sand Bag from 1mheight

    Dynamic rolling load test:

    4.5 kN load 50 passes of wheel3 kN load 50 passes of wheel

    3 kN load 50 passes of wheel

    Safety load test(centre of grille):

    13.5 kN load through 25mm squareindentor

    Deflection 23 hours after loadapplied - 3mmDeflection 24 hours after loadapplied - 3mm0.09mm permanent deformation0.01mm permanent indentation

    Did not collapse

    Did not collapse0.40mm Vertical permanentdeformation (max)0.20mm Horizontal permanentdeformation (max)

    Did not collapse

    6.00

    5.00

    4.00

    3.00

    2.00

    1.00

    0.00

    kW C

    oolin

    g C

    apac

    ity

    CFG

    5.11kW

    0.81kW

    AFG Grille(no fans)

    Potential cooling

    -15 -10 -5 0 5 10 15

    Air

    Vol

    ume

    (l/s)

    Floor Void Static Pressure (Pa)

    0

    600

    100

    200

    300

    500

    400

    CFG: 4 fans AFG: no fans

    Note: Based on 10k rise across I.T. equipment with 1 Pascal floor void static pressure

    The 125mm deep unit will provide the following strength against the performance specification:

    PSA MOB PF2 PS/SPU March 1992, with the following results:

  • Floor Grille Type FBFloor Swirl Diffusers available in either aluminium or plasticconstruction in a range of finishes/colours.

    Diffusers may be installed into a floor with either a pressurised void(no plenum box) or duct connection to optional side entry plenum box.

    Air discharge pattern may be adjusted to provide either horizontal orvertical by adjustment of optional control element (not type VF).

    For full details see publication 1/8/EN/...

    SECTION 3

    Floor Grilles Order Code - Aluminium Construction

    Type

    Surface of diffuser core and trim ring:Die cast and deburred 1Die cast, deburred, tumble fettled 2Die cast, deburred, tumble fettled 3and polished black stove enamel paint,face skimmed naturalDie cast, deburred, tumble fettled 4face skimmed

    Adjustable swirl element2) vertical Vdirectional control horizontal H

    vertical - fixed VF3)K = Trim ring1)

    FBA - 1 - V - K - SM - A 150/

    10

    SM = Dirt trap including adjustable volume control at rearSV = Dirt trap including adjustable volume control at face

    A = Plenum box

    Size (mm)150200

    Order Code - Plastic Construction

    Type

    Surface of diffuser, core and trim ring:Ash grey - similar to RAL 7037 1Black - similar to RAL 9005 2

    Adjustable swirl element2) vertical Vdirectional control horizontal H

    vertical - fixed VF3)

    1) For orders without trim ring a spacing ring is provided for technical performance reasons and to ensure correct height of grille core.2) For orders without adjustable swirl element the direction of air discharge is vertical.3) Only available for size 200.

    1) For orders without trim ring a spacing ring is provided for technical performance reasons and to ensure correct height of grille core.2) For orders without adjustable swirl element the direction of air discharge is vertical.3) Only available for size 200.

    K = Trim ring1)

    FBK - 1 - V - K - SM - A 150/

    SM = Dirt trap including adjustable volume control at rearSV = Dirt trap including adjustable volume control at face

    A = Plenum box

    Size (mm)150200

    V00/

    0 = Standard polyamide(PA 6)

    V00 = Polyamide(PA 6-V0)

    0/

    1

    2

    3

    4

    6

    5

    6 Plenum Box5 Dirt Trap4 Clamping Ring3 Trim Ring

    2 Swirl element for adjustmentof air discharge direction

    1 Diffuser Core

  • Horizontal Discharge Vertical

    SizeThrow (m) Discharge

    0.3 m 0.9 m 1.2 m 1.5 m

    150Air Volume (l/s) min - max 10 - 16 15 - 25 18 - 30 - 10 - 30Press Drop (Pa) min - max 8 - 20 18 - 50 28 - 70 - 5 - 35

    200Air Volume (l/s) min - max 16 - 27 21 - 35 25 - 41 30 - 50 10 - 50Press Drop (Pa) min - max 8 - 20 13 - 35 18 - 50 28 - 70 5 - 50

    R1

    c1

    SECTION 3Floor Grilles

    11

    Performance Data

    Max noise level NC38 assuming 4dB room attenuation. Data for FBA diffusers and dirt trap, damper fully open noplenum box. Horizontal discharge is Throw distance to terminal velocity of 0.15m/s (min vol) and 0.25m/s (maxvol). A 600mm clear zone (from centre of diffuser) is recommmended with vertical discharge.

    Size D G E H1 H2 K1 K2 R1 R2 R3 R4 R5 c1 c2150 98 50 160 125 71.5 200 198.5 149.5 138 137 150.1 150.3 21 22200 123 48 200 150 84 250 248.8 199.5 188 187 200.1 200.3 21 22

    Dimensions

    Diffuser core FBA/FBK

    Adjustable swirl element to change direction of discharge

    Vertical - fixed (VF)Vertical/Horizontal (V,H)

    Clamping ringFor installation in floor panels - min. 25mm thickness

    Clamping ringFor installation in floor panels - max. 55mm thickness

    Dirt trap SM/SV

    Trim ring K

    Plenum box A

    R2

    2

    R3

    1,5

    47

    R4-9,5

    R424

    c2

    70

    4,5

    H1

    18 GK1/K2

    H2

    D

    E

    R2

    2

    R521

    2

  • Linear Grille Types AH - WAPSupply or return air grille with fixed horizontal profiled blades.Type AH - 5.5mm blades on 12.5mm pitch. WAP - 3mm blades on12.5mm pitch. Front border 30mm wide, blades with either 0 or15 deflection, Type AH-0 and AH-15 respectively, with visiblescrew fixing (border counter punched). Available on request withconcealed fixing. Standard finish: Powder coated RAL9010 20%gloss.

    Type AFSupply or return air grilles for lay in floor mounting with fixedhorizontal profiled blades, blades with either 0 or 15deflection. Type AF-0 and AF-15 respectively. The grille core isremovable. The grille can be fitted into masonry. Standard finish:Powder coated RAL 9006 25% gloss.

    Sizes AvailableMinimum Size 150 x 100. Maximum Size 1800 x 600. Standardincrements 50mm.

    For full details see publication 1/1.1/B/...

    SECTION 4

    Linear Grilles

    Order Code

    TypeAFAHWAPAHR (20mm border)WAPR (20mm border)

    Blade deflection150

    Subframe0 = No subframeB30 = 75mm subframe bracket(30mm borders) for finite grilleB20 = as above but for 20mmborder grilleL30 = 1800mm subframe (30mmborders) for linear grille**L20 = as above but for 20mm border grille

    Note: ** = Also for use when S11 fix plenum box supplied

    Rear AssembliesA = Grille Face onlyAG = Rear opposedblade damperD = Rear adjustablebladesDG = Rear adjustableblades and damper

    Fixing0 = Without (screwfix)S11 = With (secret fix)X = Without flange drilling

    L x H (mm)Powder coat finish

    AH - 15 - AG 1000 x 150 B30 S11 P3 20% Gloss/ / / / / /

    ...-AGOpposed blade actionvolume control damper,adjustable from thefront face.

    ...-DA set of individuallyadjustable vertical airpattern control blades.

    ...-DGVolume control dampersas ...-AG plus a set ofindividually adjustablevertical air patterncontrol blades.

    Type AH - WAP Type AF

    10

    775

    H/L

    H +

    41

    (21

    )/L +

    41

    (21

    )

    12

    .5

    AH-0WAP-0

    AH-15WAP-15

    H/L

    12.5H+30/L+30

    AF-0

    643

    2

    10

    775

    Rear Assembly

    12

    RAL 9010

  • Performance DataLinear grille (with aspect ratio >12 to 1) with ceiling effect (grille installed within 300mm of ceiling). Throw is thedistance from sidewall grille to an average velocity of 0.35 m/s.

    By limiting effective jet velocity to 6 m/s all grille sizesshown up to 3m long meet NC35 assuming 8 dB roomattenuation and fully open damper.

    LThrow

    (m)

    Effective JetVelocity

    (m/s)

    Pressuredrop (total)

    (Pa)

    Nominalheight(mm)

    HType

    AH/AF

    WAP

    AH/AF

    WAP

    AH/AF

    WAP

    WAPAH/AF

    AH/AF

    WAP

    AH/AF

    WAP

    75

    75

    100

    100

    150

    150

    200250

    200

    250

    300

    300

    60

    40

    30

    20

    15

    10

    7

    Pivot line

    7

    6

    5

    4

    3

    2

    1.5

    400

    350

    300

    250

    200

    175

    150

    125

    100

    80

    70

    60

    50

    40

    30

    Air Volume(l/s.m)

    20

    10

    15

    5

    2

    1

    SECTION 4Linear Grilles

    Subframe Secret Fixing Detail

    75

    32

    X

    Type B30 - 30mm border : X = 15Type B20 - 20mm border : X = 5

    Screwdriver operationto locate fastenertongue behind subframe

    Concealed fastenerfactory fitted togrille border

    L+6/H+6 Subframe fixedto surround(No 8 screw by others)

    15

    13

  • Order Code

    TypeAGSAGS-T (Matching frame - T)

    0 = without subframe

    0 = ScrewfixX = Without flange drilling

    L x H (mm) Powder coat finish

    AGS - T 250 x 250 0 0 P3 RAL 9010 20% Gloss/ / / / / /

    TypeLVV 40

    Note: For use with LCG Grilles

    L x H (mm)

    Order Code - Fire Block

    LVV 40 150 x 150/

    TypeLCG

    L x H (mm) Powder coat finish

    Order Code - Pressed Steel Grille

    LCG 150 x 150 0 0 P3 RAL 9010 20% Gloss/ / / / / /

    Transfer Grille Type AGSNon vision grille for supply or return air with fixed inverted veeblades with visible screw fixing (border counter-punched). Thenon-vision grille is also available with a matching rear frame -Type AGS-T

    Transfer Grille Type LCG / LVV40Pressed steel grilles and integral intumescent fireblock (1 hourrated), for use in fire rated doors and partitions.

    Size AvailableMinimum Size 150 x 100. Maximum Size 1200 x 600. Standardincrements 50mm.

    For full details see publication 1/1.1/B/...

    Transfer Grilles

    SECTION 5

    14

  • Transfer GrillesSECTION 5

    Performance Data

    Type LCG/LVV40Type AGS-TType AGS

    H/L

    H1/L

    1 H/L

    H1+

    10

    /L1+

    10

    min25max44

    Intumescentmastic by others

    LVV40 intumescentfireblock

    LCG cover grille

    Neck Pressure Drop (Pa) 3 7 12.5 19.5 28 38Size Jet Velocity 1 1.5 2 2.5 3 3.5

    150 x 150 Volume (l/s) 7 10 14 17 20 24200 x 150 Volume (l/s) 9 14 19 24 28 33200 x 200 Volume (l/s) 15 23 30 38 45 53300 x 200 Volume (l/s) 24 35 47 59 71 82300 x 300 Volume (l/s) 38 57 76 96 115 134400 x 300 Volume (l/s) 52 78 104 130 156 182450 x 300 Volume (l/s) 59 88 117 147 176 205450 x 450 Volume (l/s) 90 135 181 226 271 316600 x 400 Volume (l/s) 110 164 219 274 329 384500 x 500 Volume (l/s) 116 174 232 290 348 406600 x 600 Volume (l/s) 171 256 341 426 512 597800 x 600 Volume (l/s) 229 344 459 573 688 8031000 x 600 Volume (l/s) 288 432 576 720 864 10081200 x 600 Volume (l/s) 347 520 694 867 1041 1214

    Neck NC20 NC25 NC30 NC35Size Volume l/s TPa Volume (l/s) TPa Volume (l/s) TPa Volume (l/s) TPa

    150 x 150 45 15 55 23 65 30 80 45200 x 150 55 15 70 21 80 30 100 40200 x 200 74 15 86 19 105 27 120 35300 x 200 100 12 120 18 145 24 170 32300 x 300 140 11 170 16 200 20 240 29400 x 300 175 10 210 15 250 20 300 26450 x 300 200 10 235 14 285 20 340 25450 x 450 285 9 325 13 380 17 470 24600 x 400 310 9 380 12 450 16 550 22500 x 500 325 8 390 12 485 16 560 21600 x 600 435 8 530 11 640 15 750 20

    By limiting effective jet velocity to 3 m/s all grille sizes shown meet NC35 assuming 8 dB roomattenuation.

    Data is for composite unit of 2No. grilles and integral fireblock. NC levels based on 8dB roomattenuation.

    AGS

    LCG / LVV40

    15

  • High Capacity Linear Slot Diffuser Type VSD50The Type VSD50 slot diffuser is available with 1-4 slots. They are characterised by high induction, which results in a rapid decay of supplyair velocity and temperature differential.

    The direction of air discharge can be adapted on site (by others) to the requiredroom conditions.

    Size Available1 to 4 slot lengths available in increments of 150mm.

    For full details see publication 2/2.5/B/1...

    Slot Diffusers

    SECTION 6

    16

    Order Code - Diffuser

    Order Code - Plenum

    Note: For details of Plenum Boxes see leaflet 2/2.5/B/..

    / / / / / /

    Blade SettingHH1 = All blades in one directionHH2 = Alternating blades every 300mmHA2 = 45o Alternating blades every 150mmHH3 = Alternating blade 33%/66%.

    150mm then 300mm

    Finish/colourP3 = powder coated to RAL 9010 20%1P2 = powder coated to RAL 9006 25%P4 = powder coated to RAL 9005 20%P6 = other colours to RAL

    1) standard finish

    TypeVSD50

    Style BlackWhiteBF WFBL WLBN WNBE WE

    F = FiniteL = LinearN = Non activeE = Mitre*

    FlangeNF = Not flangedFL = FlangedPL = Plank ceiling1TZ = Techzone2

    1) 4 slot only2) VSD35 only

    End CapP02 = Plate A02 = AngleL02 = Offset anglePL02 = Plank Fixings

    0 = WithoutFK = Fixing kit

    / /

    Length450mm to 1800mm 150mm increments

    No. of Slots1 to 4

    TypeVSD50

    Plenum Type0 = Standard plenumEH - Extended heightRA - Light baffle return air

    No. of Slots1 to 4

    Spigot Damper0 = Standard spigotM = Spigot damperMC = Cord operatedspigot damper

    Extended neckY = dimension mm0 = without extended neck

    Spigot dia

    No. of Spigots1 to 4

    VSD50-V3-BF-4-FL-P02 0 P3 20%RAL 9010

    AKV-VSD50-V3-0-4-D12-M 0

    HH2

    Length L1 mm length of diffuser orangle* of mitre in degrees*Only in 90o or 135o with 300mminside leg

    Lining None D12 = 12mm

    1200

    1200 x 1 x 198 x 0

  • Slot DiffusersSECTION 6

    Performance Data

    Perimeter throw pattern for VSD diffusers to a maximum terminal velocity of 0.75 m/s with average room velocitiesof 0.25 m/s. Blade configuration as detailed below to be set up on site, by others.

    Diffuser recommended active length between 75% and 80% of facade length.

    Maximum air change rates up to 25 per hour using special perimeter blade configuration as detailed below.

    Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.

    VSD50

    Number of SlotsThrow (m)

    3.0 m 4.5 m 6.0 m

    1Air Volume (l/s/m) min - max 20 - 55 20 - 70 20 - 80

    Press Drop (Pa) max 22 36 47

    2Air Volume (l/s/m) min - max 40 - 80 40 - 100 40 - 115

    Press Drop (Pa) max 14 22 29

    3Air Volume (l/s/m) min - max 60 - 100 60 - 120 60 - 145

    Press Drop (Pa) max 10 15 20

    4Air Volume (l/s/m) min - max 80 - 115 80 - 140 80 - 165

    Press Drop (Pa) max 8 13 18

    17

    SlotsP

    FL NF PL1 79.5 59.5 -2 121.5 101.5 -3 163.5 143.5 -4 205.5 185.5 299

    Slot Width Dimensions VSD50

    Example shown: 4 slot diffuser Faade

    150

    300

    200 to1000mm

    Throw (m)

    2.7m PartitionWall

    Faade

    Perimeter Throw Pattern

    Sections NF FL

    PL

    Tolerance Length L1 +/- 1 Width P +/- 1

    End Caps Type P Type A Type L Type PL

  • SECTION 6

    Slot Diffusers

    Linear Slot Diffuser Type VSD35The type VSD35 slot diffuser is available with 1-4 slots. They are characterised by high induction, which results in a rapid decay of supplyair velocity and temperature differential.

    The direction of air discharge can be adapted on site (by others) to the requiredroom conditions.

    Size Available1 to 4 slots lengths available in increments of 150mm.

    For full details see publication 2/2.5/B/1...

    Order Code - Diffuser

    Order Code - Plenum

    Note: For details of Plenum Boxes see leaflet 2/2.5/B/..

    18

    / / / / / /

    Blade SettingHH1 = All blades in one directionHH2 = Alternating blades every 300mmHA2 = 45o Alternating blades every 150mmHH3 = Alternating blade 33%/66%.

    150mm then 300mm

    Finish/colourP3 = powder coated to RAL 9010 20%1P2 = powder coated to RAL 9006 25%P4 = powder coated to RAL 9005 20%P6 = other colours to RAL

    1) standard finish

    TypeVSD35

    Style BlackWhiteBF WFBL WLBN WNBE WE

    F = FiniteL = LinearN = Non activeE = Mitre*

    FlangeNF = Not flangedFL = FlangedPL = Plank ceiling1TZ = Techzone2

    1) 4 slot only2) VSD35 only

    End CapP02 = Plate A02 = AngleL02 = Offset anglePL02 = Plank Fixings

    0 = WithoutFK = Fixing kit

    / /

    Length450mm to 1800mm 150mm increments

    No. of Slots1 to 4

    Spigot Damper0 = Standard spigotM = Spigot damperMC = Cord operatedspigot damper

    Extended neckY = dimension mm0 = without extended neck

    Spigot dia

    No. of Spigots1 to 4

    VSD35-V3-BF-4-FL-P02 0 P3 20%RAL 9010

    01200 x 1 x 198 x 0

    HH2

    Length L1 mm length of diffuser orangle* of mitre in degrees*Only in 90o or 135o with 300mminside leg

    Lining None D12 = 12mm

    1200

    TypeVSD35

    Plenum Type0 = Standard plenumEH - Extended heightRA - Light baffle return air

    No. of Slots1 to 4

    AKV-VSD35-V3-0-4-D12-M

  • SlotsP

    FL NF PL TZ

    1 64 44 - -2 91 71 - -3 118 98 - 1334 144.5 124.5 299 -

    Slot DiffusersSECTION 6

    Performance Data

    Slot Width Dimensions VSD35

    Perimeter throw pattern for VSD diffusers to a maximum terminal velocity of 0.75 m/s with average room velocitiesof 0.25 m/s. Blade configuration as detailed to be set up on site, by others.

    Diffuser recommended active length between 75% and 80% of facade length.

    Maximum air change rates up to 25 per hour using special perimeter blade configuration as detailed.

    Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.

    VSD35

    Number of SlotsThrow (m)

    3.0 m 4.5 m 6.0 m

    1Air vol. (l/s/m) min - max 15 - 40 15 - 50 15 - 50

    Press drop (Pa) max 31 44 44

    2Air vol. (l/s/m) min - max 30 - 60 30 - 70 30 - 75

    Press drop (Pa) max 15 23 26

    3Air vol. (l/s/m) min - max 45 - 70 45 - 85 45 - 95

    Press drop (Pa) max 10 16 20

    4Air vol. (l/s/m) min - max 60 - 80 60 - 100 60 - 110

    Press drop (Pa) max 9 14 17

    19

    Example shown: 4 slot diffuser Faade

    150

    300

    200 to1000mm

    Throw (m)

    2.7m PartitionWall

    Faade

    Perimeter Throw Pattern

    Sections NF FL TZ

    PL

    Tolerance Length L1 +/- 1 Width P +/- 1End Caps Type P Type A Type L Type PL

  • Slot Diffusers

    SECTION 6 High Capacity Linear Slot Diffuser Type ALS25

    Supply slot diffuser with integral baffle plate and air deflection blades. Inthe supply mode the discharge can either be set to horizontal or verticaldirection by adjustment of the air deflection blades. Available as extractdiffuser and also blanked dummy variant.

    For full details see publication 2/2.2/B/...

    Order Code - Plenum

    Plenum

    Diffuser TypeALS25

    Number of Slots 1 - 4

    Fix TypeCF = Clip fixBF = Bridge fixBX = Bridge fix for extended height plenum

    M = Spigot Damper or no entry

    D = Lining or no entry

    Spigot(mm)

    Number of spigots1 - 4

    1) Overall Height (mm)(including diffuser plusany neck extension Y)

    1) Minimum overall height including diffuser with CF fixing = spigot diameter + 98 mm + YMinimum overall height including diffuser with BF fixing = spigot diameter + 122 mm + Y

    Note: For details of Plenum Boxes see page 24.

    Length(mm)

    AKV - ALS25 - 3 - BF - D - M 1200 x 248 x 2 x 370 0 0/ / /

    Order Code - Diffuser

    TypeALS25

    StyleS = Return (without blades)NA = Non-Active (without blades)E = Mitred corner (non-active without blades300mm inside legs)T2 = (2 supply blades withspreader plate)

    Number of slots1 to 4

    Not Used

    FixingsSB = Support BracketsCF = Clip FixingsBF = Bridge FixingsBX = Bridge Fixings for extended height plenum0 = Without

    Length of diffuser in mm or Angle of mitre in degrees

    End Caps / End PlatesA1 = One end cap fittedA2 = End cap both ends fittedP1 = One end plate fittedP2 = End plate both ends fitted0 = None

    Powder coat finish

    ALS25 - T2 - 3 - A2 1200 SB 0 P3 RAL 9010 20% Gloss/ / / / / /

    20

  • Slot DiffusersSECTION 6

    ALS25-T2-1 ALS25-T2-2

    DIM A mm

    SLOT

    2528

    DIM P mm

    28

    DIM A mm

    2825

    SLOTSLOT

    19.52528

    DIM P mm

    AIR DEFLECTION BLADESADJUSTABLE FROM FACE

    AIR BAFFLE PLATEIN EACH SLOT

    76

    End Angle End Plate Dimensions

    Number of Slots Neck A Face P

    1 46.0 81.02 90.5 125.53 135.0 170.04 179.5 214.5

    Performance Data

    Air volume shown is based on diffuser used in a 1-way blow configuration to a maximum terminal velocity of 0.75m/s with average room velocities of 0.25 m/s.

    Diffuser recommended active length between 75% and 80% of facade length.

    Maximum air change rates up to 20 per hour for 1-way discharge pattern, 23 per hour for 2-way discharge pattern.

    Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.

    ALS25

    Number of SlotsThrow (m)

    3.0 m 4.5 m 6.0 m

    1Air vol. (l/s/m) min - max 20 - 55 20 - 70 20 - 80

    Press drop (Pa) max 22 36 47

    2Air vol. (l/s/m) min - max 40 - 80 40 - 100 40 - 115

    Press drop (Pa) max 14 22 29

    3Air vol. (l/s/m) min - max 60 - 100 60 - 120 60 - 145

    Press drop (Pa) max 10 15 20

    4Air vol. (l/s/m) min - max 80 - 115 80 - 140 80 - 165

    Press drop (Pa) max 8 13 18

    75

    1.5

    28

    75

    1.5

    21

  • Order Code - Diffuser

    TypeALS20

    StyleS = Return (without blades)NA = Non-Active (without blades)E = Mitred corner (non-active without blades 300mm inside legs)T2 = (2 supply blades with spreader plate)

    Number of slots1 to 6

    Not Used

    FixingsSB = Support BracketsCF = Clip FixingsBF = Bridge FixingsBX = Bridge Fixings for extended height plenum0 = Without

    Length of diffuser in mm or Angle of mitre indegrees

    End Caps / End PlatesA1 = One end cap fittedA2 = End cap both ends fittedP1 = One end plate fittedP2 = End plate both ends fitted0 = None

    Powder coat finish

    1200 SB 0 P3 RAL 9010 20% Gloss/ / / / / /

    Slot Diffusers

    SECTION 6 Type ALS20

    Supply slot diffuser with integral air straightener, hit and miss damper andair deflection blades. In the supply mode the discharge can either be set tohorizontal or vertical direction by adjustment of the air deflection blades.Available as extract diffuser and also blanked dummy variant.

    For full details see publication 2/2.1/B/...

    Order Code - Plenum

    VariablePlenum

    Diffuser TypeALS20

    Number of Slots 1 - 6

    FixingCF = Clip fixBF = Bridge fixBX = Bridge fix for extended height plenum

    M = Spigot Damper or no entry

    D = Lining or no entry

    Spigot(mm)

    Number of spigots1 - 4

    1) Overall Height (mm)(including diffuser plusany neck extension Y)

    1) Minimum overall height including diffuser with CF fixing = spigot diameter + 98 mm + YMinimum overall height including diffuser with BF fixing = spigot diameter + 122 mm + Y

    Note: For details of Plenum Boxes see page 24.

    Length(mm)

    AKV - ALS20 - 3 - BF - D - M 1200 x 248 x 2 x 430 0 0/ / /

    22

    ALS20 - T2 - 3 - A2

  • Slot Diffusers

    ALS20-DS-1 ALS20-DS-2

    DIM A mm

    SLOT

    2028

    DIM P mm

    28

    DIM A mm

    2820

    SLOTSLOT

    19.52028

    DIM P mm

    ADJUSTABLE FROM FACEAIR DEFLECTION BLADES

    AIR BAFFLE/HIT & MISSSECTION IN EACH SLOT

    76

    End Angle End Plate

    75

    1.5

    28

    75

    1.5

    Performance Data

    Air volume shown is based on diffuser used in a 1-way blow configuration to a maximum terminal velocity of 0.75m/s with average room velocities of 0.25 m/s.

    Diffuser recommended active length between 75% and 80% of facade length.

    Maximum air change rates up to 20 per hour for 1-way discharge pattern, 23 per hour for 2-way discharge pattern.

    Max NC35 assuming 8dB room attenuation, 1200mm long plenum, recommended max spigot velocity 3.5 m/s.

    ALS20

    Number of SlotsThrow (m)

    3.0 m 4.5 m 6.0 m

    1Air vol. (l/s/m) min - max 15 - 45 15 - 55 15 - 55

    Press drop (Pa) max 39 55 55

    2Air vol. (l/s/m) min - max 30 - 65 30 - 80 30 - 85

    Press drop (Pa) max 19 29 33

    3Air vol. (l/s/m) min - max 45 - 80 45 - 95 45 - 105

    Press drop (Pa) max 13 18 22

    4Air vol. (l/s/m) min - max 50 - 90 50 - 110 50 - 120

    Press drop (Pa) max 9 14 16

    5Air vol. (l/s/m) min - max 70 - 100 70 - 125 70 - 135

    Press drop (Pa) max 7 11 13

    6Air vol. (l/s/m) min - max 75 - 110 75 - 135 75 - 150

    Press drop (Pa) max 6 9 11

    Dimensions

    Number of Slots Neck A Face P

    1 41.0 76.02 80.5 115.53 120.0 155.04 159.5 194.55 199.0 234.06 238.5 273.5

    SECTION 6

    23

  • Slot Diffusers

    SECTION 6 Slot Diffuser Plenum Type AKV

    All plenums are supplied loose for site assembly to diffuser, Type CFclipped to diffuser prior to installation, Types BF & BX plenum pre-installed for 2nd fix diffuser.

    Plenum from pre-galvanised, mild steel natural finish.Damper Type M from pre-galvanised perforated sheet.Assembly supported by others (4 no holes provided at top edge ofplenum).

    Plenum internally lined with 15mm black faced Class O foam if required.

    Order Code

    VariablePlenum

    Diffuser TypeALS20ALS25

    Number of slots

    FixingCF = Clip fixBF = Bridge fixBX = Bridge fix for extended height plenum

    Overall Height (mm)Length(mm)

    AKV - ALS20 - 3 - BF - D - M 1200 x 248 x 2 x 430 0 0

    Spigot (mm)

    Number of spigots

    M = Spigot Damper or no entry

    D = Lining or no entry

    / //

    Spigot Lengths

    Spigot Length Dimension XSpigot Damper Order Suffix

    Up to 178 198 to 398

    YES - M - 75mm 100mm

    NO - 40mm 40mm

    L Max = 2100L Min = D+100

    L Max = 2100L Min = 2D+100

    Plenum Lengths & Spigot Positions

    L

    L/2L/4 L/4

    24

  • Slot DiffusersSECTION 6

    Slot Diffuser Plenum Details

    Type BF Type CF Type BX or CF

    Extended Neck Plenum(Type BX shown)

    Extension YMaximum = 1150mm CF Types

    1100mm BX TypesMinimum = 25mm All Types

    Bb

    D

    D

    (D+

    22)

    Eb O

    /A H

    EIG

    HT

    W X

    TYPICAL SLOT(VSD TYPE SHOWN)

    Bc

    D

    D

    (D+

    22)

    Ec O

    /A H

    EIG

    HT

    W X

    Bb

    D

    D

    W X

    1100mm BX TYPES MIN Y = 25mm ALL TYPES

    EXTENSIONY

    (*)(D

    +22)

    Ec+

    Y)

    OR

    (E

    b+

    Y)

    O/A

    HE

    IGH

    T

    Dimensions

    Type Number of slots W Bc Bb Ec Eb D Max

    1 138 43 61 (D+98) (D+122) 1982 176 82.5 100.5 (D+98) (D+122) 248

    AKV-ALS203 214 122 140 (D+98) (D+122) 2984 254 161.5 179.5 (D+98) (D+122) 3535 310 201 219 (D+98) (D+122) 4486 380 240.5 258.5 (D+98) (D+122) 4981 138 48 66 (D+98) (D+122) 1982 214 92.5 110.5 (D+98) (D+122) 298AKV-ALS253 254 137 155 (D+98) (D+122) 3534 310 181.5 199.5 (D+98) (D+122) 448

    25

  • Fixed Blade Linear Diffusers

    SECTION 7 Linear Diffuser Type ADM

    Opposed blade damper can be provided and where diffuser length exceeds1200mm, this should be mounted in the plenum box. Plenum boxrequirements should be forwarded to Trox for assessment/design proposals.

    Size AvailableHeights 150 to 450 in increments of 50mm. Length 300mm minimum

    For full details see publication 2/2.4/B/...

    Order Code

    Screw Fixing Secret Fixing Detail

    TypeADM1ADM2

    StyleA = Face onlyAG = Opposed blade damper1)

    Note 1) Where supplied with plenum AG will be mounted in the plenum only.

    L x H (mm)

    Subframe0 = withoutA00= subframe

    Fixing Variant0 = without (screwfix)S11 = with (secret fix)N2 = with crossbar fixingSB = with support bracket(mitred corner only)

    Powder coat finish

    ADM1 - A 1000 x 200 0 0 P3 RAL 9010 20% Gloss/ / / / / /

    Type O Standard Supply

    Type N2 Optional Extra, Cross Bar fixing

    Type S11 Optional Extra subframe with concealed fasteners.

    Border drilled forfixing to duct

    35

    Opening sizeH + 6 L + 6

    T

    Opening size H x LIncludedin supply

    Duct

    70

    Type /

    A140

    Type /

    AG

    Type ADM1-A Type ADM2-A

    M-1A Opening size H x L Type-0 fix

    70

    AG

    section

    A s

    ection

    50

    overall size H + 38 / L + 38

    H-22 / L-22

    125Blade Pitch

    3030

    7

    2A Opening size H x L Type-0 fix

    70

    AG

    section

    A s

    ection

    50

    overall size H + 38 / L + 38

    H-22 / L-22

    125Blade Pitch

    3030

    7

    26

  • Supply Aerodynamic Data ADM-1

    Performance Data

    Fixed Blade Linear DiffusersSECTION 7

    The above selections meet noise levels up to and including NC35 assuming 8dB room attenuation. ADM lineardiffuser with ceiling effect (horizontal throw). Throw is the distance from diffuser to a velocity of 0.5 m/s.

    H Pressure Drop (Pa)in mm

  • Louvre Faced Diffusers

    SECTION 8 Type ADT

    Square louvred face, removable core, ceiling diffusers type ADT giving horizontal airdischarge, are suitable for use in rooms with ceiling heights between 2.60 and 4.00m. The recommended supply air temperature differential is 10K. The ADT diffuser can beused for supply or extract air applications.

    ADT Plenum BoxManufactured from pre-galvanised mild steel. Supplied loose forsite fixing with either side or top entry spigots, with or withoutspigot dampers.

    Plenums are also available internally lined if required and must besupported by the four holes provided on the top edge.

    For full details see publication PI/2/10.3/B/...

    28

    Order Code - Diffuser

    Order Code - Plenum Box

    Type ADTFADTBADTAADTTADTM**ADTS**ADTH***

    150 x 150225 x 225300 x 300375 x 375450 x 450525 x 525600 x 600*

    Size

    ADTF - 4 - AG 225 x 225 P3 RAL 9010 20%/ / / /

    VariablePlenum

    Diffuser Type ADT

    ZH Horizontal spigot (supply)AH Horizontal spigot (extract)ZV Vertical spigot (supply)AV Vertical spigot (extract)

    0 No damperM Spigot damper 2)MC Spigot damper cord operated 2)AGF Opposed blade damper fitted to

    rear of diffuserAGP Opposed blade damper fitted to

    body of plenum

    0 No liningD Lining

    Spigot Dia (mm)

    Plenum size (mm)

    0 UnpaintedC Painted inside and outE Painted outsideI Painted inside

    Blanking PlateBP-ADT / 450Diffuser size

    Overall Height (mm)(including diffuser)1)

    1) For ZH, AH minimum height spigot diameter + 102 mmMinimum height with AGF/AGP damper, spigot diameter + 154 mmMinimum height with reduced size plenum + 30 mm on either of aboveFor ZV, AV height fixed at 242mm or 272mm for full or reduced plenum respectively

    2) Not available for vertical spigots

    DiffuserSize (mm)

    450 x 248 x 300 x 380 0/ / / / RAL9005/ 20%/

    Discharge 4directions 3

    22C1

    Rear AncillariesA Diffuser face onlyAG Opposed blade damper fitted to rear of diffuser

    P3 Powder coated white RAL9010 20% gloss (standard)P4 Powder coated black RAL9005 20% glossP6 Powder coated colour RAL...

    Gloss level

    Gloss level

    State colour

    P4 Painted black RAL9005 20% gloss

    P3 Painted white RAL9010 20% gloss

    P6 Painted colour RAL...

    Note:*ADTF only**only sizes 150 and 450***only size 375

    State colour

    AKV - ADT - ZH - D - M P4E

  • Louvre Faced DiffusersSECTION 8

    Diffuser OnlyType ADTF performance data (without damper, if fitted, 100% open)4-Way Discharge

    29

    Nomenclature:V in l/s Volume flow per diffuserL in m Distance from the outlet where the maximum

    time average air velocity is 0.5 m/svk in m/s Diffuser neck velocitypt in Pa Total pressure drop LpNC NC rating of room sound pressure level based

    on an assumed 8dB room attenuation.

    Note:The throw distance L should be between 75% and 100%of the distance to the nearest wall or 50% of the diffuserspacing dimension, based on a ceiling height of 2.7 -2.9m.

    Nominal vk m/s 1.0 1.5 2.0 2.5

    L x H pt in Pa 6 13 24 37

    V in l/s L in m LpNC V in l/s L in m LpNC V in l/s L in m LpNC V in l/s L in m LpNC

    150x150 4-way 25 0.8 < 36 1.0 < 50 1.5 22 60 2.1 27

    225x225 4-way 55 1.2 < 80 1.5 < 105 2.1 19 130 2.7 26

    300x300 4-way 95 1.5 < 140 2.2 < 190 3.1 22 240 3.7 28

    375x375 4-way 150 1.8 < 225 2.7 < 300 3.7 24 375 4.3 30

    450x450 4-way 210 2.1 < 320 3.4 < 425 4.3 25 530 4.6 32

    525x525 4-way 290 2.7 < 430 4.0 18 575 4.6 27 720 5.2 32

    600x600 4-way 375 3.1 < 560 4.3 19 750 4.9 28 940 5.5 34

    < indicates values less than 15

    Type AKV (side entry spigot)Performance is based on sizes and spigot sizes shown in table below.

    Noise level correction for plenum (damper 100% open)

    Total pressure drop correction for plenum (damper 100% open)

    Nominal L x H 150 225 300 375 450 525 600Spigot D 123 198 248 313 313 313 313/398Height E min 277 352 402 467 467 467 467/552

    Function Size 150x150 225x225 300x300 375x375 450x450 525x525 600x6001) 600x6002)

    Supply F x2.2 x1.6 x1.6 x1.7 x2.4 x3.7 x5.0 x3.2Extract F x2.2 x1.6 x1.7 x2.0 x2.6 x3.2 x4.3 x2.7

    1) with 313 spigot 2) with 398 spigot

    Function Size 150x150 225x225 300x300 375x375 450x450 525x525 600x6001) 600x6002)

    Supply LpNC +11 +7 +9 +9 +10 +13 +16 +11Extract LpNC +11 +6 +5 +7 +9 +10 +12 +8

    1) with 313 spigot 2) with 398 spigot

    General guidance on changing spigot diameter D with damper 100% open

    Type AKV (Top entry spigot)The effect on performance is small providing spigot velocities do not exceed 3.5 to 4.0 m/s

    Spigot velocity m/s 2.5 3 3.5 4.0

    Approx LpNC 25 30 35 40

    Diffuser with plenum box

  • The type ADTF has a shaped flanged border for directlymounting to a closed flush ceiling (to maintain horizontaldischarge)To fit over ceiling opening size (L+100) (H+100)

    Type ADTA to locate in clip-in ceiling to match bevelled edgetile with PIP height = 27.5mm (ie SAS system 150) or 25mm(ie Burgess type A)Type ADTB to locate in clip-in ceiling to match square edgedtile with PIP height = 25mm (ie Burgess type B or D)

    The type ADTT has a flat flanged border to enable the diffuserface to be mounted on the back of an exposed T bar ordirectly to a closed flush ceilingType *ADTH (size 375 only): 495 O/A to lay-on 500 squareceiling T supports

    The types ADTM and ADTS each have a border designed to layinto an exposed Threadline support bar systemType ADTM to lay-on threadline ceiling T support bar 15mmwide x 16mm deep (dimension Z)Type ADTS to lay-on threadline ceiling T support bar 15mmwide x 8mm deep (dimension Z)Standard nom (L x H) sizes 150/450

    Louvre Faced Diffusers

    SECTION 8

    30

    TypeNominal duct size L x H

    150 225 300 375 450 525 600

    ADTF

    ADTA/ADTB

    ADTT

    ADTH*

    ADTM/ADTS

    *Overall face 495mm lay on 500 mm square ceiling "T" supports

    Location clipson border (2 eachon opposite sides)

    Location clipson border (2 eachon opposite sides)

    25

    Detail X ADTA PIP heights

    Standard PIP heights:25mm or 27.5mmNB: Non-standard heightsavailable on request

    Detail Y ADTB PIP heights

    Standard PIP height:25mmNB: Non-standard heightsavailable on request

    Detail X & Y

    Type ADTF Type ADTT (*ADTH)

    Type ADTA - ADTB Type ADTM - ADTS

    L x H

    (L + 145) (H + 145) O/A

    53

    15

    (L + 145) (H + 145) O/A

    53 7

    L x H

    (L + 150) (H + 150) O/A

    53

    715

    L x H

    (L + 133) (H + 133) O/A

    53

    Z

    L x H

  • Louvre Faced DiffusersSECTION 8

    31

    (L-2) (H-2) X

    25

    Optiontype AGF

    D

    ADTF border style shown (refer table 1)

    E O

    /A h

    eigh

    t re

    qui

    red

    (refe

    r to

    tab

    le 3

    )

    (Ref

    er t

    able

    2)

    Option type M1)

    (L1-2) (H1-2) X

    25

    Effective

    (Ref

    er t

    able

    2)

    F O

    /A h

    eigh

    t re

    qui

    red

    (refe

    r to

    tab

    le 3

    )

    D

    Option type AGP fitted to the plenum

    Option type M1)

    Table 2 - Available spigot sizes 3)Table 1 - Maximum Spigot Sizes

    L x H Side Entry Top EntryAvailable for diffusers typeNom. Max Dmm Max Dmm

    150 148 123 ADT / F / A / B / T / M / S225 222 198 ADT / F / A / B / T300 298 278 ADT / F / A / B / T375 353 353 ADT / F / A / B / T / H450 4482) 398 ADT / F / A / B / T / M / S525 4982) 498 ADT / F / A / B / T600 5582) 558 ADT / F / A / B / T

    Table 3 - Overall height diffuser + plenum

    Reduced plenum sizesEffective plenum size L1 x H1 must be at least one sizedown on nominal L x H.

    Plenum Option E min E max F min F max

    AKV-ADT 0 &M D+102 1000 D+132 1000AKV-ADT AGF/AGP D+154 1000 D+184 1000

    Notes:1) Also available with cord operated damper type MC2) 398 is maximum D for type M or MC dampers3) For performance guidance information on spigot size selection see page 29

    DmmSubiect to limitations as shown in table 1 & as noted

    98 198 348123 222 398138 248 448148 278 498158 298 558178 313

    D

    (L-2) (H-2) I/S

    40

    242

    Optiontype AGF

    I/S Plenum

    272

    D

    40

    Option typeAGP fitted to

    the plenum

    (L1-2) (H1-2)

    Table 4 - ADT Side Entry

    Spigot Length Dimension XSpigot Damper Order Suffix

    Up to 178 198 to 398

    YES - M - 75mm 100mm

    NO - 40mm 40mm

    Notes:1) For full plenum code details refer to page 282) All plenums, and if required transformations, are supplied loose for site

    assembly by others3) All full size plenums are supplied with clips for diffuser face fixing

    4) Holes (4) provided at top edge of plenum for hanging by others5) AGF and AGP damper adjustment requires core removal6) Plenum can be internally lined code D

    (lining material 12mm black faced class O) foam

  • Louvre Faced Diffusers

    SECTION 8 Square Diffuser Type ADLQ

    Type ADLQ high capacity ceiling diffuser comprises a fixed diffuser face withplenum box supplied loose (to be fitted by others), where specified.

    Low pressure drop and noise levels due to curved blade construction.

    Available as a four-way face configuration.

    For full details see publication 2/11/EN/...

    Type

    A = Diffuser faceAG = With OBDAR = With rear

    mounting ring Subframe0 = Without installation subframeE1 = Duct cross bar

    Size (mm)250300400500600625

    Not Used Powder coat finish

    Order Code - Diffuser

    ADLQ - A 250 0 0 P3 RAL 9010 20% Gloss/ / / / / /

    Plenum

    Diffuser Type

    ZH = horizontal spigot (supply)AH = horizontal spigot (extract)ZV = vertical spigot (supply)AV = vertical spigot (extract)

    M1) = Spigot, damper or blank

    D = Lining or no entry

    Spigot size

    Not Used

    Reduced plenum size or blankif standard diffuser size

    Note : 1) Only available for horizontal spigot (ZH, AH)

    Diffuser Size

    Order Code - Plenum

    AK - ADLQ - ZH - D - M 400 x 198 x 6 0 0/ / /

    32

  • Type ADLQ-AK

    Type ADLQ-AType ADLQ-AG

    D

    K 50

    H

    Q1

    Q2-58

    Q1

    Q2

    42

    108

    Type ADLQ-AR

    Q2-55

    ADLQ-AR

    65

    Performance Data

    ADLQ louvre diffuser with ceiling effect (horizontal throw). Throw is the distance from diffuser to a velocity of 0.5 m/sfor a 4-Way discharge. All selections shown meet NC35 assuming 8 dB room attenuation.

    Supply (4 - Way Discharge)

    Extract

    SizeLwnc 15 21 25 30 35

    Pressure Drop (Pa) 10 15 20 30 45

    250Volume (l/s) 30 38 45 55 62Throw (m) - - 1.0 1.2 1.4

    300Volume (l/s) 45 53 65 80 95Throw (m) - - 1.0 1.2 1.3

    400Volume (l/s) 80 100 115 150 170Throw (m) - 1.1 1.2 1.9 2.5

    500Volume (l/s) 135 160 175 225 275Throw (m) - 1.2 1.6 2.0 2.7

    600Volume (l/s) 210 275 290 350 450Throw (m) - 2.0 2.1 2.75 3.5

    SizeLwnc 15 21 25 30 35

    Pressure Drop (Pa) 10 15 20 30 45250 Volume (l/s) 30 38 45 54 60300 Volume (l/s) 50 60 70 90 100400 Volume (l/s) 90 110 125 170 200500 Volume (l/s) 180 200 250 300 375600 Volume (l/s) 300 375 450 500 600

    Size D H K Q1 Q2250 158 262 204 248 198300 158 262 254 298 248400 198 307 354 398 348500 248 357 454 498 448600 313 420 554 598 548

    Louvre Faced DiffusersSECTION 8

    Dimensions

    33

  • Louvre Faced Diffusers

    SECTION 8 Circular Diffuser Type ADLR

    Aluminium diffusers Type ADLR and ADLR-Q arerecommended for flush installation in ceilings.

    Circular or square configurations can be used instandard ceiling systems.

    Plenum boxes are available with top or side entry.

    For full details see publication 2/16/EN/...

    Order Code

    TypeADLR(Circular diffuser)

    Q = Square diffuser(or blank)

    A = Diffuser faceC = With flap damperAR = With connecting ring

    Top entry plenumZV = Supply airAV = Extract air

    Side entry plenumZH = Supply airAH = Extract air

    M = Damper in plenum box spigot

    4)MN = Volume setting by cord and measurement test point

    L = Spigot with lip seal

    AccessoriesRZ Circular flap damper and equalising gridPlease order accessory RZ separately stating size required

    2) Size of Facesection593598

    Size ofDiffuser12345678

    0 = Standard surface finish stove enamelled to 3)RAL 9010

    S1 = Stove enamelled to RAL...

    0 = Without subframe1)D0 = Duct subframe1)F0 = Standard subframe

    Type ADLR - Q593 - for installation in visible T-bar598 - for installation in ceiling grid with rear sub-structure

    State colour

    No entry for standard construction

    ADLR - Q - ZH - M - L 598 x 4 0 0 S1 RAL 9016/ / / / /

    D

    K

    H2

    R1 (ADLR)

    P

    35

    6

    H1

    R1 (ADLR)

    D

    B

    1) Required on constructions without plenum box2) Only on variants with square face section Type ADLR - Q3) GL = Gloss level 50 - 60%4) Available side entry plenum only

    Type ADLR-Q Type ADLR-Q

    34

  • Louvre Faced DiffusersSECTION 8

    Performance Data

    Dimensions

    Linear Pattern based on a single row of Diffusers. Square Pattern with Diffusers at equal centres.

    Ceiling diffuser with ceiling effect (horizontal throw). At diffuser centres shown, maximum terminal velocity is0.25 m/s at 1.0m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including sideentry plenum box and spigot damper (fully open).

    Diffuser Centres (m)Size Selection Method 1.2 (m) 1.8 (m) 2.4 (m) 3.0 (m) 3.6 (m) 4.2 (m)

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol PaLinear Pattern 35 22 55 60 80 130 - - - - - -

    1Square Pattern 32 19 45 35 60 68 - - - - - -Linear Pattern 50 15 80 35 110 70 - - - - - -

    2Square Pattern 35 7 55 17 80 35 100 58 - - - -

    3Linear Pattern 60 7 95 17 130 30 175 60 - - - -Square Pattern 50 5 65 8 95 17 130 30 155 50 - -

    4Linear Pattern - - 110 13 150 25 200 35 250 55 300 85Square Pattern - - 70 5 100 10 140 19 180 32 220 40

    5Linear Pattern - - - - 180 23 230 37 280 65 360 90Square Pattern - - - - 130 12 160 19 200 25 260 50

    6Linear Pattern - - - - 220 15 260 25 330 40 400 50Square Pattern - - - - 150 9 180 13 220 15 290 30

    7Linear Pattern - - - - 240 15 290 20 360 37 450 50Square Pattern - - - - 175 8 210 10 270 19 330 32

    8Linear Pattern - - - - 250 13 320 22 400 30 500 50Square Pattern - - - - 180 7 220 10 280 17 360 28

    Size B D H1 H2 K P R1 R21 201.5 123 233 220 266 202 244 1922 257.5 158 233 250 290 258 300 2483 313.5 198 233 295 372 314 356 3044 369.5 248 267 345 476 362 412 3605 425.5 248 267 345 476 426 468 4166 481.5 313 298 410 567 482 542 4727 537.5 313 298 410 590 578 598 5288 593.5 313 298 410 615 590 654 584

    R2-55

    R1

    R2

    35

    R2-55 35

    593 or 598

    R2

    Type ADLR Type ADLR-Q

    R2-51

    60

    Type ADLR-AR/ADRL-Q-AR

    35

  • Perforated Face Diffusers

    SECTION 9 Perforated Diffuser Type ADLQL

    Type ADLQL ceiling diffuser comprises a perforated diffuser face with rearplenum box, top or side entry.

    Spigot dampers are only available with side entry plenums. Blanking plates areavailable on request for site fitting by others.

    For full details see publication 2/15.1/B/...

    Order Code

    Type

    K = 27mm cover borderP = 11mm flush border

    SupplyZH = horizontal spigotZV = vertical spigot

    ExtractAH = horizontal spigotAV = vertical spigot

    Note: 1) Only available for horizontal spigot 2) Only available for flush border & layin T bar

    Size (mm)300400500600295 2)

    595 2)

    Not used

    M = spigot1) damper or blankD = Lining1) or blank

    Spigot size

    Reduced plenum size or blankif standard diffuser size

    Powder Coat finish

    ADLQL - K - ZH - D - M 300 X 158 X 0 0 0 P3 RAL 9010 20% Gloss/ / / / / /

    DimensionsSize D DA1 DA2 H1 H2 H3 K1 K2 Q1 Q2300 158 290 300 300 75 83 274 269 336 298400 198 390 400 340 75 83 374 369 436 398500 248 490 500 390 75 83 474 469 536 498600 313 590 600 455 75 83 574 569 636 598295 158 - 300 300 - 83 271 266 - 295595 313 - 600 455 - 83 571 566 - 595

    Blanking Plates

    ates

    Blanking plate

    36

  • Perforated Face DiffusersSECTION 9

    Type ADLQL-K-V Type ADLQL-P-V

    D

    K2

    H2

    DA1

    Q1

    8

    D

    K2

    H3

    Q2

    DA2

    Type ADLQL-K-H Type ADLQL-P-H

    DA1

    Q1

    8

    K1

    D

    H1

    Q2

    DA2

    K1

    D

    H1

    Supply (4 - Way Discharge)Size Pressure Drop 10 15 20 25 30

    300Volume (l/s) 45 60 70 78 85Throw (m) 0.7 0.8 1.0 1.1 1.2

    400Volume (l/s) 80 100 118 130 145Throw (m/s) 0.85 1.1 1.3 1.4 1.5

    500Volume (l/s) 110 135 158 175 190Throw (m) 0.85 1.1 1.4 1.5 1.6

    600Volume (l/s) 170 210 240 260 290Throw (m/s) 1.2 1.4 1.6 1.8 2.0

    ExtractSize Pressure Drop 10 15 20 25 30300 Volume (l/s) 80 105 120 135 150400 Volume (l/s) 105 130 150 170 180500 Volume (l/s) 135 160 185 210 225600 Volume (l/s) 210 260 300 330 360

    Note: Pressure drop and acoustic data shown is for top entry spigot.For side entry supply & extract acoustic and pressure drop data refer to leaflet 2/15.1/B/...

    Performance Data

    Horizontal throw distance from diffuser to a velocity of 0.5 m/s for a 4-Way discharge. All selections shown meet NC35assuming 8 dB room attenuation.

    37

  • Disc Valves

    SECTION 10

    Disc Valve Type LVS Z-LVSThe disc valves consist of a valve ring, centraldisc and installation subframe. To guarantee aperfect seal, the valve ring is fitted with aperipheral sealing strip. A bayonet fitting is usedto mount the unit in the installation subframe.

    The air volume flow is adjusted by rotating thecentral disc which alters the gap between thedisc and the valve ring. The central disc is heldin position with a locknut.

    For full details see publication 1/4/EN/...

    Order Code

    Type LVS (Extract Valve) Type Z-LVS (Supply Valve)

    Dimensions

    SupplyZ - LVS

    ExtractLVS

    Size (mm)100125160200

    G1 - Subframe

    O - No Subframe

    160 G1/ /

    Size B C D E

    100 40 99 132 104

    125 46 124 162 129

    160 54 159 205 164

    200 61 199 245 204

    C

    E

    D

    50

    B

    8

    C

    E

    D

    50

    B

    8

    S

    38

    LVS

  • SECTION 10Disc Valves

    Type LVS (Extract Valve)

    Performance Data

    Note: Maximum Noise Level NC38, assuming 8dB room attenuation. Throw to a terminal velocity of 0.2 m/s. Performance based on air gap dimension S = 9mm.

    Type Z-LVS (Supply Valve)

    SizePressure drop (Pa)

    10 20 30 50 70Volume (l/s) 10 15 18 23 28

    100Throw (m) 0.7 1.1 1.5 2.0 2.7Volume (l/s) 13 18 21 28 33

    125Throw (m) 0.9 1.4 1.6 2.0 2.7Volume (l/s) 15 22 27 35 42

    160Throw (m) 0.9 1.5 1.8 2.5 3.0Volume (l/s) 20 28 35 45 55

    200Throw (m) 1.5 2.1 2.8 3.8 4.5

    39

    Size Air gap(mm) S

    Air Volume (l/s)

    10 20 30 40 50 60 80 100 120-15 - - - - - - - - --5 30 120 - - - - - - -

    1000 12 50 112 300 - - - - -+5 5 28 56 100 - - - - --15 70 270 - - - - - - --5 14 50 100 200 - - - - -

    1250 5 25 50 89 139 - - - -+5

  • Swirl D

    iffusers

    SECTION 11

    The layout and centres of the swirl diffusers must be carefully considered to ensure maximum comfort is achieved. Wehave provided three alternative arrangements for positioning diffusers, selection methods 1, 2 and 3. Each of theselections will ensure that the maximum terminal velocity in the occupied zone (VH1) will not exceed 0.25m/s, 1.0mbelow ceiling.

    Swirl Diffuser Selection Methodology

    Swirl diffusers offer a high induction air distribution method thatenables the highest comfort criteria to be achieved.

    The following range of diffusers each discharge an air streamhorizontally across the ceiling. The entrainment and expansion takesplace rapidly, and the velocity decay of the air-stream occurs in directproportion with the distance from the device.

    High turbulence occurs immediately within the proximity of thediffuser, which allows high air change rates to be successfully suppliedinto the room. With careful selection swirl diffusers can handle up to30 air changes per hour while still satisfying relevant comfort criteria.

    2.7

    m

    1.0

    m

    Minimum Diffuser CentresA, B or C

    X

    VH1

    Occupied Zone

    40

  • Swirl Diffusers

    SECTION 11

    When the diffuser rows are at least 4.0m apart, the minimum diffuser centres should be A.

    When the diffuser rows are at least 3.0m apart, the minimum diffuser centres should be B.

    When the diffuser centres in each direction are equal, the minimum diffuser centres should be C.

    Selection Method 1 - Rows 4.0m apart

    Min

    imu

    m D

    iffu

    se

    r a

    tC

    en

    tre

    s A

    Diffuser Rows at Centres 4.0m

    Selection Method 2 - Rows 3.0m apart

    Min

    imum

    Diff

    user

    at

    Centr

    es B

    Diffuser Rows at Centres 3.0m

    Selection Method 3 - Rows on Square Grid

    Min

    imum

    Diff

    user

    at

    Centr

    es C

    Diffuser Rows atCentres C

    41

  • Swirl D

    iffusers

    SECTION 11

    Type SDWSquare faced adjustable blade swirl diffuser. Type SDW is available in a range ofsizes.

    The removable face plate is held in the plenum box with a centre screw fixing.The head of the screw is covered with a decorative cap.

    The plenum box is available with side or top entry spigot and a volume controldamper.

    For full details see publication 2/7/EN/...

    Order Code - Diffuser

    Type

    Q = Square flush faceQL = Square lay in T barQM15 = Square lay in threadline 15 x 16QM15 = Square lay in threadline 26 x 16QS15 = Square lay in threadline 15 x 8QS26 = Square lay in threadline 26 x 8QB = Burgess Ceiling

    Z = SupplyA = ExtractF = Face Only 2)

    Blank oroversized ceilingmodule size

    Number of blades

    Diffuseractive size 1)

    Not used

    0 = Supply air: black air control bladesExtract air: no air blades

    Q11 = Extract air: black air control bladesQ21 = Supply air: white air control blades

    Extract air: white air control blades

    Powder coat finish

    SDW - QS - Z 500 - 24 - 600 0 P3Q21 RAL 9010 20% Gloss/ / / / //

    Note: 1) Standard sizesQ - 300 x 8, 400 x 16, 500 x 24, 600 x 24, 600 x 48, 625 x 24, 625 x 54QS15 - 300 x 8 x 600, 400 x 16 x 600, 500 x 24 x 600, 600 x 24 x 600QB/QL/QS26 - 300 x 8 x 600, 400 x 16 x 600, 500 x 24 x 600, 600 x 24 x 600, 600 x 48 x 600QM15/QM26 - 300 x 8 x 600, 300 x 8 x 750, 400 x 16 x 600, 400 x 16 x 750, 500 x 24 x 600, 500 x 24 x 750, 600 x 24 x 600,600 x 24 x 750, 600 x 48 x 600, 600 x 48 x 750, 625 x 24 x 750, 625 x 54 x 750

    2) Face section without central fixing hole, for use on lay in ceilings QL, QS15, QS26, QM15 & QM26 without rear plenum

    Order Code - Plenum

    Plenum

    Diffuser

    ZH = Horizontal Spigot (Supply)AH = Horizontal Spigot (Extract)ZV = Vertical Spigot (Supply)AV = Vertical Spigot (Extract)

    M = Spigot Damper

    MN = Spigot damper and test point connection1)or no entry

    Spigot2)

    Size (mm)

    D = Liningor no entry

    Number of blades

    1) Only available on ZH type2) Refer to product data sheet for spigot sizes available with each plenum size

    Diffuser Active Size

    AK - SDW - ZH - D - MN 500 x 198 x 24/

    42

  • Spigot Lengths

    Spigot Length Dimension XSpigot Damper Order Suffix

    Up to 178 198 to 398

    YES - M - 75mm 100mm

    NO - 40mm 40mm

    SECTION 11Swirl Diffusers

    Performance Data

    Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entryplenum box and spigot damper (fully open).

    For Selection Methodology see page 40.

    Type QFace-mounted

    Type QS15To Lay-on Tegular tee-bar15mm wide x 8mm deep

    Type QLTo Lay-onFLAT tee-bar

    Type QM15To Lay-on Tegular tee-bar15mm wide x 16mm deep

    Q Size D P K298 x 298 300 x 8 158 250 288398 x 398 400 x 16 198 295 370498 x 498 500 x 24 198 295 474598 x 598 600 x 24 248 345 565598 x 598 600 x 48 248 345 588

    K I/S PLENUM X

    P

    D

    See Type below

    K I/S PLENUM

    250

    See Type below

    Q

    8 1525

    595 face size

    15584 face size

    8 15

    16

    584 face size

    Diffuser Centres (m)Size Selection Method 1.2 m 1.8 m 2.4 m 3.0 m 3.6 m 4.2 m

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa1, Centres A 100 37 95 30 105 40 120 46 140 65 - -

    400 x 16 2, Centres B 75 20 70 18 75 20 85 27 100 47 - -3, Centres C 25 5 45 7 65 15 85 27 110 43 - -1, Centres A 140 40 120 27 130 33 140 38 160 50 - -

    500 x 24 2, Centres B 100 20 85 14 90 18 100 20 120 27 - -3, Centres C 35 5 55 9 75 11 100 20 120 27 - -1, Centres A 150 18 145 17 110 20 180 25 210 35 250 50

    600 x 24 2, Centres B 110 10 105 9 110 10 130 14 152 18 180 253, Centres C 40 3 65 4 85 6 115 11 170 23 220 381, Centres A 190 23 170 18 180 20 195 24 220 30 300 55

    600 x 48 2, Centres B 130 11 110 8 120 9 140 13 180 22 200 293, Centres C 50 2 80 4 90 6 120 9 180 22 230 33

    Note: Vol = Volume (l/s) Pa = Pressure Drop

    Dimensions

    43

    26 573

    16

    599

    35

    26 5848

    Type QM26To Lay-on Tegular tee-bar26mm wide x 16mm deep

    Type QBTo Push-In spring tee-barSuitable for tee or omega type

    Type QS26To Lay-on Tegular tee-bar26mm wide x 8mm deep

    Tile levelled via centrescrew i.e. no location pip

  • Swirl D

    iffusers

    SECTION 11

    Type VDWAdjustable swirl diffusers type VDW are supplied in a range of sizes. The faceplate is circular to suit the architectural requirements

    The removable face plate is held in the plenum box with a centre screwfixing. The head of the screw is covered with a decorative cap.

    The plenum box is available with side or top entry spigot, with volumecontrol damper and / or lip seal on request.

    For full details see publication 2/7/EN/...

    Order Code

    Type

    R = Circular

    Z = SupplyA = Extract

    V = Top entry plenumH = Side entry plenum

    L = Spigot with lip seal

    M = Volume control damperwith adjustable lever

    1) MN = Volume control damperwith cable and test connection

    0 = Supply air: black air control bladesExtract air: no air blades

    Q11 = Extract air: black air control bladesQ21 = Supply air: white air control blades

    Extract air: white air control blades

    Size (mm) Not Used Powder coat finish

    VDW - R - Z - V - M - L 600 x 24 0 P10 RAL 9010/ / / / / 20% Gloss/

    NOTE: 1)Only for supply air with side entry

    R/Q

    B

    D

    40

    H1

    R

    ~32

    K

    H2

    35

    R

    P

    8

    D

    Type VDW-...-V

    Type VDW-R-...-

    Type VDW-R-...-H

    44

  • Performance Data

    Diffuser Centres (m)Size Selection Method 1.2 m 1.8 m 2.4 m 3.0 m 3.6 m 4.2 m

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa1, Centres A 100 37 95 30 105 40 120 46 140 65 - -

    400 x 16 2, Centres B 75 20 70 18 75 20 85 27 100 47 - -3, Centres C x C 25 5 45 7 65 15 85 27 110 43 - -1, Centres A 140 40 120 27 130 33 140 38 160 50 - -

    500 x 24 2, Centres B 100 20 85 14 90 18 100 20 120 27 - -3, Centres C x C 35 5 55 9 75 11 100 20 120 27 - -1, Centres A 150 18 145 17 160 20 180 25 210 35 250 50

    600 x 24 2, Centres B 110 10 105 9 110 10 130 14 152 18 180 253, Centres C x C 40 3 65 4 85 6 115 11 170 23 220 381, Centres A 190 23 170 18 180 20 195 24 220 30 300 55

    600 x 48 2, Centres B 130 11 110 8 120 9 140 13 180 22 200 293, Centres C x C 50 2 80 4 90 6 120 9 180 22 230 33

    Note: Vol = Volume (l/s) Pa = Pressure Drop

    SECTION 11Swirl Diffusers

    Dimensions

    R Size B D H1 H2 P K300 300 x 8 280 158 200 250 278 290400 400 x 16 364 198 200 295 362 372500 500 x 24 462 198 200 295 460 476600 600 x 24 559 248 200 345 557 567600 600 x 48 580 248 300 345 578 590

    Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entryplenum box and spigot damper (fully open).

    For Selection Methodology see page 40.

    If the diffuser is installed below a closed ceiling (i.e. freely suspended) a stable discharge can be achieved if aperipheral collar > 50mm is fitted.

    45

  • Swirl D

    iffusers

    SECTION 11

    Type FD Type FD swirl diffusers are available in various sizes. Depending on thearchitectural requirements, the face plate can be circular or square. The fixedair control blades on the diffuser face are arranged radially.

    The diffuser face can be attached or removed via a centre fix screw into theplenum box. The screw head is covered with a decorative cap. The plenumbox can be supplied with either top or side entry spigots and on request,with spigot lip seals and volume control damper.

    If a circular diffuser face is ordered, the plenum box with side entry spigothas a 35mm extension piece fitted to the plenum.

    For full details see publication 2/6/EN/...

    Order Code

    Type

    Q = SquareR = Circular

    Z = SupplyA = Extract

    V = Top entry plenumH = Side entry plenum

    L = Spigot with lip seal

    M = Volume control damper with single blade1)MN = Volume control damper with cable and test connection

    Size Not Used Powder coat finish

    FD - Q - Z - V - M - L 400 0 P10 RAL 9010/ / / / / 20% Gloss/

    NOTE: 1) Only for side entry spigot

    K

    H2

    D

    Q

    8

    35

    K

    H2

    D

    R

    P

    8

    R L

    fixing screwfor diffuser face

    H

    R/Q

    B

    D

    40

    200

    Type FD-Q-...-H Type FD-R-...-H

    Type FD-R-...- Type FD-Q-...-

    Type FD-...-V

    46

  • SizeH = (side entry) V = (top entry)

    Vol Pa Vol Pa

    300 65 40 65 65

    400 110 40 115 70

    500 170 45 140 80

    600 200 40 180 55

    Selections shown meet NC38 assuming 5dB room attenuation.

    Diffuser Centres (m)Size Selection Method 1.2 m 1.8 m 2.4 m 3.0 m 3.6 m 4.2 m

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa1, Centres A 85 65 75 60 80 63 - - - - - -

    300 2, Centres B 60 36 54 30 58 33 60 36 70 50 80 633, Centres C x C - - 35 13 45 20 58 33 80 63 - -1, Centres A 125 55 110 40 118 48 120 50 140 65 - -

    400 2, Centres B 85 25 78 20 82 23 90 27 100 35 120 503, Centres C x C - - 52 9 68 15 80 21 100 35 130 551, Centres A 150 40 130 28 135 30 150 40 170 48 - -

    500 2, Centres B 105 18 92 14 97 16 105 18 120 23 140 303, Centres C x C - - 65 7 85 12 100 17 125 25 155 421, Centres A 160 26 145 20 150 21 160 26 185 30 220 45

    600 2, Centres B 115 12 100 9 110 11 120 13 135 15 160 253, Centres C x C - - 70 5 95 8 115 12 145 20 175 28

    Note: Vol = Volume (l/s) Pa = Pressure Drop

    Performance Data

    SECTION 11Swirl DiffusersSwirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entry

    plenum box and spigot damper (fully open).

    For Selection Methodology see page 40.

    If the diffuser is installed below a closed ceiling (i.e. freely suspended) a stable discharge can be achieved if aperipheral collar > 50mm is fitted.

    DimensionsSize B D L Q R H2 K P300 280 158 254 298 300 250 290 278400 364 198 336 398 400 295 372 362500 462 198 440 498 500 295 476 460600 559 248 530 598 600 345 567 557

    47

    Max Extract for Noise

    Note: Vol = Volume l/s Pa = Pressure Drop

  • Swirl D

    iffusers

    SECTION 11

    Type DCS Type DCS-P air diffusers consist of the perforated face plate with a thin acousticfleece lining on the rear. In type DCS-N, the face plate is made of plain sheetsteel with perimeter returned edge with central perforated plate insert.

    The rear swirl diffuser includes a discharge nozzle ring and radially arrangedfixed air control blades and connection collar. If required, can be supplied withtop entry spigot piece or side entry plenum box with circular spigot. Plenum boxcan have internal acoustic insulation if specified.

    For full details see publication 2/4.1/EN/...

    Order Code

    Type

    Face PlateP = PerforatedN = Non-perforatedC = With discharge

    nozzle ring

    V = Visible1)

    H = Hidden2)

    K = Connecting collarUS = Top entry spigotA = Plenum boxAK = Plenum box with acoustic insulation

    Size (mm)5931)

    5982)

    Not Used Powder coat finish

    DCS - P - V - AK 593 x 315 0 P10 RAL 9010/ / / / / 20% Gloss/

    NOTE: 1)For exposed Tee bar fitting...-V (overall face 593)2) For hidden Tee bar fitting...-H (overall face 598)

    Type DCS-P-...-K

    H2

    8

    A

    C

    RB

    593 ( 598)

    Type DCS-P-...-USSize...x 125 and ...x 160without perforated plate

    C

    RB

    593 ( 598)

    D

    40

    8

    H3

    Type DCS-P-...-A/DCS-P-...-AK

    H2

    H1

    D

    C

    RB

    8

    593 ( 598)

    K

    K1

    Type DCS-...-H-US

    600

    Hanging

    Bracket

    598

    48

  • Performance Data

    Diffuser Centres (m)Size Selection Method 1.2 m 1.8 m 2.4 m 3.0 m 3.6 m 4.2 m

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa1, Centres A - - 50 65 50 65 - - - - - -

    160 2, Centres B 35 31 35 31 38 41 39 43 45 50 50 653, Centres C - - 23 14 30 24 40 45 - - - -1, Centres A 70 50 62 44 62 44 68 45 75 55 - -

    200 2, Centres B 42 20 45 24 47 25 51 27 56 29 65 453, Centres C - - 32 10 40 17 55 28 70 50 - -1, Centres A 95 40 78 26 76 25 90 35 - - - -

    250 2, Centres B 51 11 54 13 57 18 63 17 70 20 80 273, Centres C - - 35 5 47 9 63 17 75 25 100 451, Centres A 125 25 105 18 110 20 120 22 140 30 170 45

    315 2, Centres B 70 7 75 9 80 11 85 12 100 17 110 203, Centres C - - 45 4 65 6 85 12 110 20 140 301, Centres A 125 8 115 7 125 8 140 12 155 11 170 16

    400 2, Centres B - - - - - - 100 6 115 7 130 93, Centres C - - - - - - 100 6 130 9 150 10

    Note: Vol = Volume (l/s) Pa = Pressure Drop

    Dimensions

    Size A B C D H1 H2 H3 K K1 R...X 160 158 235 210 123 180 79 159 215 237 250...X 200 198 275 250 158 215 79 162 255 277 300...X 250 248 325 300 198 255 76 167 305 327 350...X 315 313 410 385 248 305 89 184 370 392 450...X 400 398 495 470 313 361 89 194 454 476 500

    SECTION 11Swirl Diffusers

    Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entryplenum box and spigot damper (fully open).

    For Selection Methodology see page 40.

    Type DCS-...-V-A / DCS-..-V-AK Type DCS-...-V-K

    600

    Hanging

    bracket

    593

    600

    Hanging

    bracket

    593

    49

  • Swirl D

    iffusers

    SECTION 11

    Type TDFTDF - SilentAIR swirl diffusers are available in various sizes. In accordancewith architectural requirement the face plate can be circular or square. Thefixed air guiding elements of diffuser face are radially arranged.

    The diffuser can be fastened to the plenum box by means of a centralscrew and cover cap.

    The plenum box can be supplied with a horizontal or vertical airconnection, or upon request with a volume control damper and / or asealing lip.

    For full details see publication 2/6.2/EN/...

    Order Code

    Type

    Silent Air

    Q = SquareR = Circular

    Z = SupplyA = Extract

    V = Top entryH = Side entry

    L = Spigot with lip seal

    1)MN = Volume control damper with sheathed cable and measuring nippleM = Volume control with operating rod

    Size (mm)300400500600

    Not Used Powder coat finish

    TDF - SA - Q - Z - V - M - L 400 0 P10 RAL 9016/ / / / / 20% Gloss/

    NOTE: 1) MN only with side entry

    R

    L

    R L

    R

    Q

    L

    Central fixing screw fordiffuser face

    Type TDF-SilentAIR-R-...-V

    Type TDF-SilentAIR-Q-...-H Type TDF-SilentAIR-R-...-H

    Type TDF-SilentAIR-Q-...-V

    50

  • Performance Data

    Diffuser Centres (m)Size Selection Method 1.2 m 1.8 m 2.4 m 3.0 m 3.6 m 4.2 m

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa1, Centres A 80 45 80 45 80 45 80 45 80 45 80 45

    300 2, Centres B 62 28 62 28 62 28 62 28 70 38 80 453, Centres C 25 5 37 10 48 17 62 28 80 45 80 451, Centres A 92 20 92 20 92 20 92 20 100 28 110 33

    400 2, Centres B 80 17 80 17 80 17 80 17 100 28 120 373, Centres C - - 45 5 65 11 80 17 110 33 135 451, Centres A 135 30 135 30 135 30 135 30 140 33 150 38

    500 2, Centres B 100 17 100 17 100 17 100 17 120 22 150 383, Centres C - - 60 6 80 10 95 14 125 25 165 451, Centres A 160 22 160 22 160 22 160 22 165 24 190 30

    600 2, Centres B 115 10 115 10 115 10 115 10 135 14 180 273, Centres C - - - - 90 7 115 10 145 17 190 30

    Note: Vol = Volume (l/s) Pa = Pressure Drop

    SECTION 11Swirl Diffusers

    Dimensions

    Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entryplenum box and spigot damper (fully open).

    For Selection Methodology see page 40.

    If the diffuser is installed below a closed ceiling (i.e. freely suspended) a stable discharge can be achieved if aperipheral collar > 50mm is fitted.

    Q/R

    B

    D

    40

    200

    Q

    K

    H2

    8

    D

    ~32

    R

    P

    K

    H2

    D

    ~32

    8

    35

    Size B D L Q R H2 K P300 280 158 254 298 300 250 290 278400 364 198 336 398 400 295 372 362500 462 198 440 498 500 295 476 460600 559 248 530 598 600 345 567 557625 559 248 530 623 623 345 567 557

    Type TDF-SilentAIR-...-V Type TDF-SilentAIR-Q-...-H Type TDF-SilentAIR-R-...-H

    51

  • Swirl D

    iffusers

    SECTION 11

    Type TDV The diffuser face of the type SilentAIR offers a high volume flow rate at lowsound power levels. The horizontal swirl-type discharge of the supply air ensureshigh induction and hence rapid reduction in jet velocity and temperaturedifferential. Suitable for supply air temperature differentials up to 10K.

    Depending on requirements, the diffuser can be supplied with a circular or squareface and with either white or black air control blades. For the air connection a plenum box is used. The connection can be top or sideentry. Face fixing with centre screw and cover cap.

    For full details see publication 2/7.1/EN/...

    Order Code

    Type

    Silent Air

    Q = SquareR = Circular

    Z = SupplyA = Extract

    V = Top entryH = Side entry

    L = Spigot with lip seal

    M = Volume control with operating rod1)MN = Volume control damper with sheathed cable and measuring nipple

    Size (mm)300400500600

    Not Used

    Air control blades0 = Supply air: black

    Extract air: noQ11 = Extract air: blackQ21 = Supply air: white

    Extract air: white

    Powder coat finish

    TDV - SA - Q - Z - V - M - L 400 0 P1Q21 RAL 9010/ / / / / 20% Gloss/

    NOTE: 1) Only with side entry

    R

    L

    Q

    L

    Central fixing screw fordiffuser face

    Type TDV-SilentAIR-R-...- Type TDV-SilentAIR-Q-...-

    52

  • Performance Data

    Diffuser Centres (m)Size Selection Method 1.2 m 1.8 m 2.4 m 3.0 m 3.6 m 4.2 m

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa1, Centres A 80 45 80 45 80 45 80 45 80 45 80 45

    300 2, Centres B 65 30 65 30 65 30 65 30 70 37 80 453, Centres C - - 40 13 50 19 60 25 75 40 80 451, Centres A 120 36 120 36 120 36 120 36 120 36 120 36

    400 2, Centres B 85 19 85 19 85 19 85 19 100 27 120 363, Centres C - - 50 6 65 12 80 16 110 30 120 361, Centres A 150 38 150 38 150 38 150 38 155 39 160 40

    500 2, Centres B 100 17 100 17 100 17 100 17 125 25 150 383, Centres C - - 65 8 80 10 100 17 140 30 160 401, Centres A 170 25 170 25 170 25 170 25 180 28 200 34

    600 2, Centres B 120 12 120 12 120 12 120 12 140 16 190 303, Centres C - - - - 100 9 120 12 150 18 180 28

    Note: Vol = Volume (l/s) Pa = Pressure Drop

    Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entryplenum box and spigot damper (fully open).

    For Selection Methodology see page 40.

    SECTION 11Swirl Diffusers

    Q/R

    B

    D

    40

    200

    Q

    K

    H2

    8

    D

    ~32

    R

    P

    K

    H2

    D

    ~32

    8

    35

    Size B D L Q R H2 K P300 280 158 254 298 300 250 290 278400 364 198 336 398 400 295 372 362500 462 198 440 498 500 295 476 460600 559 248 530 598 600 345 567 557625 559 248 530 623 623 345 567 557

    Type TDV-SilentAIR-...-V

    Dimensions

    Type TDV-SilentAIR-Q-...-H Type TDV-SilentAIR-R-...-H

    53

  • R2

    A

    U2

    Q2

    Q2

    D

    U4

    40

    8

    Q2

    R2

    D

    U6

    40

    Swirl D

    iffusers SECTION 11

    Type RFD Available in either circular or square face plate, with or without dischargenozzle, to suit architect requirements.

    Type RFD-...-UO or RFD-...-UD, top entry plenum boxes are inclusive ofinternal subframe which holds the diffuser in position by central fixing boltand covering cap.

    For full details see publication 2/4/EN/...

    Order Code

    Type RFD-R-D-K Type RFD-Q-D-US

    Type RFD-R-D-US Type RFD-R-D-UD

    Type

    Diffuser FaceQ = SquareR = Circular

    D = nozzle

    K = Connecting ringUS = Top entry plenumUD1) = Top entry plenum withinternal subframe (dischargenozzle construction)UC1) = Top entry plenum with internal subframe (no discharge nozzle)A = plenum box side entryN1) = Low profile plenum box

    L = Plenum box with lip seal

    M = Volume control damper with operating rod2)MN = Volume control damper with sheathed cable and test nipple

    Size (mm)125160200250315400

    Powder coat finish

    RFD - Q - D - A - M - L 200 0 P10 RAL 9010

    Not Used

    / / / / / 20% Gloss/

    NOTE: 1) Only available with circular construction2) Not available with N

    H1

    wK

    H3

    H4

    xD

    8

    wQ1xR1

    xC

    48

    32

    54

  • Performance Data

    Diffuser Centres (m)Size Selection Method 1.2 m 1.8 m 2.4 m 3.0 m 3.6 m 4.2 m

    Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa Vol Pa1, Centres A 40 70 35 50 35 50 38 60 45 80 50 100

    125 2, Centres B 25 28 24 20 27 35 29 38 32 45 38 603, Centres C - - 18 15 23 19 29 38 40 70 50 1001, Centres A 55 55 47 40 47 40 53 50 60 65 70 95

    160 2, Centres B 32 18 33 19 35 21 37 27 40 30 47 403, Centres C 15 9 24 12 30 16 40 30 55 55 70 951, Centres A 67 37 63 34 63 34 68 38 75 45 85 65

    200 2, Centres B 43 14 45 15 48 18 50 20 55 24 65 353, Centres C - - 30 8 38 9 50 20 68 38 90 701, Centres A 110 40 80 23 80 23 100 36 120 50 140 70

    250 2, Centres B 52 10 53 11 54 11 55 12 68 15 78 203, Centres C - - 35 4 45 7 55 12 60 13 95 321, Centres A 115 18 105 15 105 15 110 17 130 25 140 27

    315 2, Centres B 72 8 75 8 78 9 80 9 90 11 100 143, Centres C - - 45 2 60 5 80 9 105 15 145 291, Centres A 130 14 118 11 120 12 140 16 155 18 175 25

    400 2, Centres B - - - - 90 7 105 9 120 12 135 153, Centres C - - - - - - 100 8 125 13 150 17

    Note: Vol = Volume (l/s) Pa = Pressure Drop

    Swirl diffuser with ceiling effect (horizontal throw). Minimum diffuser centres ensure maximum terminal velocity is0.25 m/s at 1.0 m below ceiling. All selections shown meet NC38 assuming 5dB room attenuation including side entryplenum box and spigot damper (fully open).

    For Selection Methodology see page 40.

    SECTION 11Swirl Diffusers

    Size A C D H1 H3 H4 K Q1 Q2 R1 R2 U2 U4 U6125 123 123.5 98 259 195 178 216 198 198 158 200 75 153 192160 158 158.5 123 284 220 190 266 198 248 197 250 78 158 196200 198 198.5 158 314 250 202 290 248 248 241 300 78 161 197250 248 248.5 198 359 295 227 476 298 298 295 350 75 166 202315 313 313.5 248 409 345 252 567 398 398 364 450 88 183 219400 398 398.5 313 474 410 285 615 498 498 450 580 88 193 229

    Dimensions

    55

  • Jet Nozzles

    SECTION 12

    Type DUK - Standard SupplyJet nozzles type DUK are suitable for almost all situations because of the widerange of variants available.

    Fixed construction type DUK-F consists of a nozzle with fixing holes. Adjustableconstruction type DUK-V consists of a spherical discharge nozzle mounted flangeand circular spigot for direct connection to a circular duct. The nozzle can beadjusted manually up to max. 30 in any direction. The adjustment can bemotorised with an electric or pneumatic actuator. With an actuator the nozzle canonly be rotated in one plane up to 30 upwards (cooling) and up to 30downwards (heating).

    For full details see publication 1/5/EN/...

    Order Code

    Type

    P1) = Fixed V = Adjustable

    Only with construction VK = Duct connection elementA = As K plus spigotR = Duct connection element for circular ducting

    Only with construction VP = With pneumatic actuatorE1 = external Rotary actuator 220 V, 50 HzE2 = external Rotary actuator 24 V, 50 HzE3 = external Rotary actuator 24 V, 50 Hz, 0...V-E4 = internal linear actuator 220 V, 50 HzE5 = internal linear actuator 24 V, 50 HzE6 = internal linear actuator 24 V, 50 Hz, 0...V+

    Size (mm) Not Used

    DUK - V - K - E1 250 0 0/ / / /

    NOTE: 1) Drilled for fixing as standard: extra text required on order if no holes are required.For sizes 100 and 125, construction with actuator not available

    Performance Data

    Based on horizontal discharge with air temperature 10k above or below room temperature to a terminal velocity of0.75 m/s without ceiling effect. Selections meet NC45 assuming 15dB room attenuation.

    SizeVolume (l/s) 13 17 22 28 35

    100 Throw L (m) 3.9 4.5 5.8 6.9 9Rise + Fall (m) 0.6 0.43 0.44 0.5 0.62Volume (l/s) 17 25 35 45 55

    125 Throw L (m) 3.9 5 7 8.5 11Rise + Fall (m) 0.55 0.5 0.75 0.9 1.3Volume (l/s) 23 35 50 70 95

    160 Throw L (m) 3.5 5.1 7.5 10.5 14Rise + Fall (m) 0.38 0.3 1.1 1.6 1.8Volume (l/s) 29 55 85 120 180

    200 Throw L (m) 3.8 6.5 10 13 21Rise + Fall (m) 0.6 1.1 2 3.3 3.4Volume (l/s) 37 60 95 140 190

    250 Throw L (m) 3.8 5.4 8.5 12.5 17.8Rise + Fall (m) 0.9 1.5 1.6 2.8 3.3Volume (l/s) 50 100 200 300 400

    315 Throw L (m) 3.9 7 13.8 21 28Rise + Fall (m) 1.3 1.8 3 4.9 9Volume (l/s) 65 150 250 350 500

    400 Throw L (m) 3.9 9 13 18.5 25Rise + Fall (m) 1.7 2.5 4 4.6 7

    56

    Powder coat finish

    P3 RAL 9010/ 20% Gloss/

  • SECTION 12Jet Nozzles

    Dimensions

    L2

    D

    4

    D

    5

    D

    3

    E

    F

    DUK V

    D

    5

    D

    2

    D

    1

    L19Counterpunched hole 4.5mmfor raised countersunkself-tappingscrews 4.2 x 16, DIN 7973

    DUK-F

    15

    10

    Type DUK-V-RExamples of circular duct connection

    Type DUK-V-KExamples of rectangular duct connection

    Type DUK-V

    Type DUK-F

    K

    R

    L3*

    60

    15

    D

    3

    DUK-V-R-E1...E3 (shown)DUK-V-R-P

    Rotary actuator

    E

    L3*

    K

    60

    D

    3

    D

    4

    Rotary actuator

    E

    DUK-V-A-E1...E3 (shown)DUK-V-K-E1...E3 (shown)DUK-V-A-PDUK-V-K-P

    Size D1 D2 D3 D4 D5 E F K L1 L2 L3

    100 136 115 146 98 50 10 -2 134 94 78 80125 159 138 169 123 64 10 4 157 112 89 90160 225 201 200 158 82 11 10 188 122 106 110200 265 241 257 198 108 16 14 242 153 127 140250 315 291 302 248 136 16 23 287 187 159 170315 400 376 384 313 174 23 29 358 224 189 220400 485 461 467 398 230 24 47 441 287 223 260

    DUK-V-R-E1...E3 (shown)DUK-V-R-P

    DUK-V-A-E1...E3 (shown)DUK-V-K-E1...E3 (shown)DUK-V-A-PDUK-V-K-P

    Type DUK-V-R-E (1-3 shown) Type DUK-V-A-E/DUK-V-K-E (1-3 shown)

    SizePossible Circular Duct Diameters R

    200 250 315 500 630 800100 125 160 200 250 315 400

    Drop and rise is directly proportional to supply airtemperature differential.

    L